338
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany (06 21) 7 76-0 • USA (330) 4 25 35 55 • Singapore 7 79 90 91 • Internet http://www.pepperl-fuchs.com
Dimensions
Model number Technical data
Function
Ausgabedatum 22.01.2002
Electrical connection
Accessories
Ø
5.3
Ø
9.6
18.5 18.5
80
36
26
2636
45
U-G1FA General specifications
Addressing via addressing jack
Ambient conditions
Ambient temperature -25 ... 60 °C (248 ... 333 K)
Storage temperature -25 ... 85 °C (248 ... 358 K)
Mechanical specifications
Protection degree IP67 based on EN 60529
(only in connection with module or cover)
Connection type 2 AS-i flat cables
Dimensions about 80, 45, 20 mm (L, W, H)
Mounting top hat section rail or screw mounting
Base with addressing jack for con-
nection to flat cable (EMS; AS-i only)
The U-G1FA base allows slaves in the nor -
mal design to be connected to AS-i without
additional supply (EMS) . It has two connec-
tions to AS-Interface, which are intercon-
nected. Thus it can also be used as
distributor from one AS-i segment to
another. When mounting the upper part
(module or cover VAZ-DK-G1) the flat cable
are pressed in the contact prongs and the-
reby connected.
Moreover, an integrated addressing jack
can configure the upper part in the wired
AS-i network. In this case the controller indi-
cates Alarm Config, since the slave is dis-
connected from the supply. After removing
the addressing plug, the controller restarts
independently.
Accessories
VAZ-DK-G1
Cover for bases -G1F- and -G1P-
Addressing
jack
Contacts to module
+
-
+
-
+ -
AS-i
AS-i
AS-i base