Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com. 37
1
Power Protection and Conditioning
Group 4 – MCR Series, 50 Hz Only (±5% output voltage regulation)
Selection Tables: Single Phase
Group 3 – MCR Series, 60 Hz Only
Specifications
VA Catalog Number Voltage Input Voltage Output Height
(inch)
Width
(inch)
Depth
(inch)
Ship weight
(lbs)
Design
Style
Elec
Conn
500 63-31-150-8 600 120, 208, 240 13 9 7 38 1B
1000 63-32-210-8 600 120, 208, 240 17 9 7 62 1 B
2000 63-32-220-8 600 120, 208, 240 18 13 10 109 1 B
3000 63-32-230-8 600 120, 208, 240 19 13 10 142 1B
5000 63-29-250-8 * 208, 240, 480, 600 120, 208, 240 28 13 10 221 1 A
7500 63-29-275-8 * 208, 240, 480, 600 120, 208, 240 27 25 10 360 2A
10000 63-29-310-8 * 208, 240, 480, 600 120, 208, 240 28 25 10 441 2A
15000 63-29-315-8 * 208, 240, 480, 600 120, 208, 240 28 38 10 706 3 A
VA Catalog Number Voltage Input Voltage Output Height
(inch)
Width
(inch)
Depth
(inch)
Ship weight
(lbs)
Design
Style
Elec
Conn
120 63-23-612-8 110, 120, 220, 240, 380, 415 110, 120, 220, 240 9 6 8 24 1 C
250 63-23-625-8 110, 120, 220, 240, 380, 415 110, 120, 220, 240 11 6 827 1 C
500 63-23-650-8 110, 120, 220, 240, 380, 415 110, 120, 220, 240 13 9 7 40 1 C
1000 63-23-710-8 110, 120, 220, 240, 380, 415 110, 120, 220, 240 18 9 7 64 1 C
2000 63-23-720-8 110, 120, 220, 240, 380, 415 110, 120, 220, 240 18 13 10 113 1 C
3000 63-23-730-8 110, 120, 220, 240, 380, 415 110, 120, 220, 240 27 13 10 162 1 C
5000 63-23-750-8 110, 120, 220, 240, 380, 415 110, 120, 220, 240 30 13 10 266 1 C
7500 63-28-775-8 220, 240, 380, 415 110, 120, 220, 240 28 26 10 393 2 C1
10000 63-28-810-8 220, 240, 380, 415 110, 120, 220, 240 30 26 10 490 2 C2
15000 63-28-815-8 220, 240, 380, 415 110, 120, 220, 240 30 38 10 776 3C2
Parameter Condition Value
Input
Voltage
Continuous at full load (lower input voltage possible at lighter load) +10% to -20% of nominal
For temporary surge or sags +20% to -35% of nominal
Current1at Full Load & 80% of nominal input voltage Iin ≅ (VA/.89)/(Vin x 80%)
Frequency See Operating Characteristics section for details. 50 Hz or 60 Hz depending on model
Output
Line Regulation Vin >80% and <110% of nominal ± 5% for 50 Hz units, ± 3% for 60 Hz units
Overload Protection At Nominal Input Voltage Current limited at 1.65 times rated current
Output Harmonic Distortion At full load within input range 3% total RMS content
Noise Attenuation Common Mode
Transverse Mode
120 dB
60 dB
General
Efficiency At Full Load Up to 92%
Storage Temperature Humidity <95% non-condensing -20° to +85°C
Operating Temperature Humidity <95% non-condensing -20° to 50°C
Audible Noise Full Resistive Noise 35 dBA to 65 dBA
Approvals
60 Hz Models UL1012, CSA evaluated by UL
50 Hz Models CE (EMC & LVD)
Warranty See General Information section for details 10 + 2 Years
Notes: 1 - Consult user manual for fuse sizing.
2 - It is recommended that the unit run at a minimum of 40-50% load.
* CSA only models.