1
New Product News
Solid-state Timers
H3DK
DIN Track-mounted, 22.5-mm-width
Standard Timer Series
A wide AC/DC power supply range (24 to 240 VAC/DC).*1
All sub-series include models with 12-VDC power supply.*1
G-type Models (H3DK-G) now include model with 240 to 440-
VAC power supply.
•UL*
2, CSA*3, and CCC certification and EN 61812-1 compliance.
CE Marking.
EMC (EN 61812-1) compliance for application in heavy industri-
al, residential, commercial, or light industrial environments.
Finger-safe terminal block and captive screws according to EN 50274.
*1. Except for the H3DK-H.
*2. Except for the H3DK-GE.
*3. Scheduled to obtain certification in April 2012.
LR
Model Number Structure
The Entire H3DK Series
Model Number Legend (Not all models that can be represented with the model number legend can necessarily be produced.)
H3DK Series
H3DK-M/-S Multi-range,
Multi-mode Timers
Eight-mode Timer
H3DK-M1/M2
Operating Modes
A: ON Delay
B: Flicker OFF Start
B2: Flicker ON Start
C: Signal ON/OFF Delay
D: Signal OFF Delay
E: Interval
G: Signal ON/OFF Delay
J: One-shot Output
Four-mode Timer
H3DK-S1/S2
Operating Modes
A: ON Delay
B2: Flicker ON Start
E: Interval
J: One-shot Output
H3DK-F
Twin Timers
H3DK-H Power
OFF-delay Timers
H3DK-G
Star-delta Timers
Operating Modes
Power OFF-delay
Timer
Operating Modes
Star-delta Timer
Operating Modes
Flicker-OFF Start/
Flicker-ON Start
Page 2 Page 11 Page 15 Page 21
1234
H3DK-@@@@
1. Type 2. Control Output
* M- and S-type models only.
3. Supply Voltage
*1 H-type models only.
*2 G-type models only.
4. Time Ranges (H-type
Models Only)
Symbol Meaning
M Eight-mode Timer
S Four-mode Timer
F Twin Timer
G Star-delta Timer
H Power OFF-delay Timer
Symbol Meaning
1 SPDT
2DPDT
Symbol Meaning
Blank 24 to 240 VAC/DC
A12 VDC
B 24 to 48 VAC/DC
C *1 100 to 120 VAC
D *1 200 to 240 VAC
E *1 240 to 440 VAC *2
Symbol Meaning
S 0.1 to 1.2 s or 1 to 12 s
L 1 to 12 s or 10 to 120 s
2
New Product News
Multi-range, Multi-mode Timer
H3DK-M/H3DK-S
Multiple time ranges and operating modes let you cover a wide
range of applications.
The time-limit DPDT output contacts can be changed to time-limit
SPDT and instantaneous SPDT output contacts using a switch.
Sequence checks are easily performed by setting an instanta-
neous output to 0.
Start signal control for the H3DK-M.
LR
Ordering Information
List of Models
Accessories (Order Separately)
Model Structure
Supply voltage Control output Eight-mode Timer Four-mode Timer
24 to 240 VAC/DC
Contact output, DPDT (time-limit DPDT, or time-limit
SPDT + instantaneous SPDT)
Changed using a switch. Model H3DK-M2 H3DK-S2
Contact output, SPDT (time-limit SPDT) Model H3DK-M1 H3DK-S1
12 VDC
Contact output, DPDT (time-limit DPDT, or time-limit
SPDT + instantaneous SPDT)
Changed using a switch. Model H3DK-M2A H3DK-S2A
Contact output, SPDT (time-limit SPDT) Model H3DK-M1A H3DK-S1A
Item Specification Model
Mounting Track
50 cm (l) x 7.3 mm (t) PFP-50N
1 m (l) x 7.3 mm (t) PFP-100N
1 m (l) x 16 mm (t) PFP-100N2
End Plate --- PFP-M
Spacer --- PFP-S
Model Operating modes Terminal block Input type Output type Mounting method Safety standards Accessories
H3DK-M2 A: ON Delay
B: Flicker OFF start
B2: Flicker ON start
C: Signal ON/OFF Delay
D: Signal OFF Delay
E: Interval
G: Signal ON/OFF Delay
J: One-shot Output
9 terminals Voltage input
Relay, DPDT
DIN Track mounting
cURus (UL 508
CSA C22.2 No. 14)
EN 61812-1
IEC 60664-1 4 kV/2
EN 50274
User label
H3DK-M1 Relay, SPDT
H3DK-S2 A: ON Delay
B2: Flicker ON start
E: Interval
J: One-shot Output
--- Relay, DPDT
H3DK-S1 6 terminals Relay, SPDT
H3DK-M/H3DK-S
3
Specifications
Time Ranges
Ratings
Time range setting 0.1 s 1 s 10 s 1 min 10 min 1 h 10 h 100 h
Set time range 0.1 to 1.2 s 1 to 12 s 10 to 120 s 1 to 12 min 10 to 120 min 1 to 12 h 10 to 120 h 100 to 1,200 h
Scale numbers 12
Power supply voltage *1 24 to 240 VAC/ DC, 50/60 Hz *2
12 VDC *2
Allowable voltage fluctuation
range 24 to 240 VAC/DC: 85% to 110% of rated voltage
12 VDC: 90% to 110% of rated voltage
Power reset Minimum power-OFF time: 0.1 s
Reset voltage 10% of rated voltage
Voltage input
24 to 240 VAC/DC
High level: 20.4 to 264 VAC/DC, Low level: 0 to 2.4 VAC/DC
12 VDC
High level: 10.8 to 13.2 VDC, Low level: 0 to 1.2 VDC
*3
Power con-
sumption
H3DK-M2/-S2 At 240 VAC: 6.6 VA max. *4
H3DK-M1/-S1 At 240 VAC: 4.5 VA max. *4
H3DK-M2A/-S2A At 12 VDC: 0.9 W max.
H3DK-M1A/-S1A At 12 VDC: 0.6 W max.
Control output Contact output, 5 A at 250 VAC with resist iv e load (cosφ = 1),
5 A at 30 VDC with resistive load *4, *5
Ambient operating temperature 20 to 55°C (with no icing)
Storage temperature 40 to 70°C (with no icing)
Ambient operating humidity 25% to 85%
*1. When using a 24 -VDC power supply voltage, there will
be an inrush current of app roximately 0.25 A. Allow fo
r
this inrush current when turning ON and OFF the
power supply to the Timer with device with a solid-
state output, such as a sensor.
*2. DC ripple: 20% max.
*3. The power consumption is for mode A after the Time
r
times out.
For the H3DK-M@, the maximum power consumption
is given, including the current consumed by the inpu t
circuit.
*4. Refer to DC Power Consumptions (Reference Infor
-
mation) on page 27 for DC power consumptions.
*5. The control outp ut ratings are for one H3DK operating
alone. If you o perate two or more Timers side by side,
refer to I nstallation Pitch and Output Switching Capa c
-
ity (Reference Values) on the next page.
*6. 125 VDC: 0.15 A max. with resistive load, 125 VDC:
0.1 A with L/R of 7 ms.
Minimum load: 10 mA at 5 VDC (P level, reference
value)
H3DK-M/H3DK-S
4
Characteristics
I/O
*If the INST/TIME switch on the front of the Timer is set to INST on the H3DK-M2/-S2, relay R2 will
operate as instantaneous cont acts and will turn ON/OFF in synchronization with the power supply.
Item Model H3DK-M1/-M2 H3DK-S1/-S2
Input Start Functions to star t timing. There is no start input.
Output Control
output The output is turned ON/OFF according to the operati ng mode when the value
that is set on the dial is reached . *
Installation Pitch and Output
Switching Capacity (Reference Val-
ues)
The relation between t he installation pitch
and the load current is shown in the follow-
ing graph. (Except for the H3DK-GE)
If Timer is used under load conditions that
exceed the specified values, the tempera-
ture inside the Timer will increase, reduc ing
the life expectancy of internal parts.
0 1 2 3 4 5 6
80
70
60
50
40
30
20
10
d = 5 mm
d=0 A
d = 10 mm
d = 50 mm
Ambient temperature (°C)
Maximum ambient operating
temperature in specifications
Load current (A)
DIN Track Timer installation pitch: d
Tested Timer: H3DK-M/-S
Applied voltage: 240 VAC
Installation pitch: 0, 5, 10, and 50 mm
Test
timer
1
Test
timer
2
Test
timer
3
Test
timer
4
Test
timer
5
Testing Method
* With the H 3DK-M@, if the voltage exceeds 26.4 VAC/DC in mode C, D, or G, the OFF trigger sig nal char-
acteristics are as follows:
Accuracy of operating time: ±1% ±50 ms max.
Setting error: ±10% max.
Minimum input signal width: 100 ms
Applicable standards
Accuracy of operating
time ±1% of FS max. (±1% ±10 ms max. at 1.2-s range)*
Setting error ±10% of FS ±0.05 s max.*
Minimum input signal
width 50 ms* (start input)
Influence of voltage ±0.5% of FS max. (±0.5% ±10 ms max. at 1.2-s range)
Influence of tempera-
ture ±2% of FS max. (±2% ±10 ms max. at 1.2-s range)
Insulation resistance 100 M min. at 500 VDC
Dielectric strength
Between current-car rying metal parts and exposed non-current-carrying metal
parts: 2,000 VAC 50/ 60 Hz for 1 min.
Between control out put terminals and o peratin g circuit: 2,0 00 VAC 50/60 Hz for
1 min.
Between contacts not located next to each other: 1,000 VAC 50/60 Hz for
1min.
Impulse withstand volt-
age
24 to 240 VAC/VDC: 3 kV between power termina ls, 4.5 kV between current-
carrying metal parts and exposed non-current-carrying metal parts
12 VDC: 1 kV bet ween po wer t erminals, 1. 5 kV b et ween curren t-car rying met al
parts and exposed non-current-carrying metal parts
Noise immunity Square-wave noise generated by noise simulator (pulse width: 100 ns/1 µs,
1-ns rise): ±1.5 kV
Static immunity Malfunction: 4 kV, Destruction: 8 kV
Vibration
resistance Destruction 0.75-mm single amplitude at 10 to 55 Hz for 2 h each in 3 directions
Malfunction 0.5-mm single amplitude at 10 to 55 Hz for 10 min each in 3 directions
Shock re-
sistance Destruction 1,000 m/s2 3 times each in 6 directions
Malfunction 100 m/s2 3 times each in 6 directions
Life ex-
pectancy Mechanical 10 million operations min. (under no load at 1,800 operations/h)
Electrical 100,000 operations min. (5 A at 250 VAC, resistive load at 360 operations/h)
Degree of protection IP30 (Terminal block: IP20)
Weight Approx. 120 g
Safety standards
cURus: UL 508/CSA C22.2 No. 14
EN 50274: Finger protection, back-of-hand proof
EN 61812-1: Polluti on degree 2, Overvoltage category III
CCC: Pollution degree 2, Overvoltage category II, section DB14048.5-2008 part 5-1
LR: Test Specification No. 1-2002 Category ENV 1.2
EMC
(EMI) EN61812-1
Radiated Emissions: EN 55011 class B
Emission AC Mains: EN 55011 class B
Harmonic Current: EN 61000-3-2
Voltage Fluctuations and Flicker: EN61000-3-3
(EMS) EN61812-1
ESD Immunity: EN 61000-4-2: 6 kV contact discharge,
8 kV air discharge
Radiated Radio-Frequency Electromagnetic Field Immunity (AM Radio Waves):
EN 61000-4-3: 10 V/m (80 MHz to 1 GHz)
Burst Immunity: EN 61000-4-4: 2 kV power line,
1 kV I/O signal line
Surge Immunity: EN 61000-4-5: 2 kV common mode,
1 kV differential mode
+100 ms
50 ms
H3DK-M/H3DK-S
5
Connections
Block Diagrams
H3DK-M1/-M2
H3DK-S1/-S2
Output circuit
RAMROM
Indicator circuitInput circuit
Power supply circuit
AC (DC) input
Start input
Power
indicator Output
indicator
Time setting
detection circuit Time specification
switches Operating mode
switch
One-chip microcomputer
Clock
Output circuit
Indicator circuit
Power supply circuit
AC (DC) input
Power
indicator Output
indicator
Time setting
detection circuit Time specification
switches Operating
mode switch
RAMROM
One-chip microcomputer
Clock
H3DK-M/H3DK-S
6
Terminal Arrangement
Input Connections
The start input of t he H3DK-M1/-M2 is a voltage input.
A1 15
B1
A2
18 16
A1 15
25/21
B1
26/2228/24
A2
18 16
A1 15
25/21
26/2228/24
A2
18 16
A1 15
A2
18 16
15
R1
1618
15
R1
1618
25/21
R2
*
26/2228/24
15
R1
1618
15
R1
1618
25/21
R2
*
26/2228/24
H3DK-M1 H3DK-M2 H3DK-S1 H3DK-S2
Start
See note 3.
(DIN notation) (DIN notation) (DIN notation) (DIN notation)
Start
See note 3. See note 3. See note 3.
A2
A1 15
1816
B1
A2
A1 15
1816
B1
(21)
25
28
(24)
26
(22)
A2
A1 15
1816 A2
A1 15
1816
(21)
25
28
(24)
26
(22)
Note 1: The time-limit contact symbol for previous models of Timers was . The time-limit contact symbol for the H3DK is . A different symbol is
used because the H3DK supports multiple operating modes.
Note 2: *The relay R2 can be set to either instantaneous or time-limit contacts using the switch on the front of the Timer.
Note 3: The power supply terminals do not have polarity.
Sensor Timer
A1 (+)
A2 ()
B1
Start
24
VDC
24 VDC
(sensor
power supply)
(+)
()
Sensor
Timer
A1 ()
A2 (+)
B1
Start
24
VDC ()
(+)
Timer
A1
A2
B1
Start
Operates when PNP transistor turns ON. Operates when NPN transistor turns ON. Operates when relay turns ON.
24 VDC
(sensor
power supply)
Voltage Input Signal Levels
Tran-
sistor
input
1. Transistor ON
Residual voltage: 1 V max.
Voltage between terminals B1
and A2 must be equal to or
higher th an th e r at ed high level
voltage (20.4 VDC min.).
2. Transistor OFF
Leakage current: 0.01 mA max.
Voltage between terminals B1
and A2 must be equal to or
below the rated low level voltage
(2.4 VDC min.).
Relay
input
Use relays that can adequately
switch 0.1 mA at the imposed
voltage.
When the relay is ON or OFF, the
voltage between terminals B1 and
A2 must be within the following
ranges:
24 to 240 VAC/DC
When relay is ON: 20.4 to 264
VAC/DC
When relay is OFF: 0 to 2.4 V
12 VDC
When relay is ON: 10.8 to 13.2 V
When relay is OFF: 0 to 1.2 V
PNP Transistor Input NPN Transistor Input Relay Input
Consider the minimum load
of the relay. (See signal
levels on the right.)
H3DK-M/H3DK-S
7
Nomenclature
*If the switch is left between settings, proper operation may not be possible.
Make sure that the switch is set properly.
Note: The default settings are for 0.1 s in mode A.
Terminal Block
(See notes 1 and 2.)
Bottom ViewFront View
Time range switch
Operating mode switch
Output indicator (orange)
(Lit while Timer gives output.)
Operation/power indicator (green)
(Lit while the power is ON.)
INIT/TIME switch for relay R2
(Default setting is for time-limit
output.)*
Main dial (for
setting the time)
User label
attachment location
Note 1. Use solid wire (2.5 mm2 max.) or fer-
rules with insulative sleeves to connect
to the terminals.
To maintain the withstand voltage after
connecting the terminals, insert no
more than 8 mm of exposed conductor
into the terminal.
Recommended Ferrules
Phoenix Contact
•AI@@@ Series
•AI-TWIN@@@ Series
Note 2. Screw Tightening Torque
Recommended torque: 0.49 N·m
Maximum torque: 0.98 N·m
8 mm max. 8 mm max.
Using Solid Wire
(2.5 mm2 Max.) Using Ferrule with
Insulative Sleeve
H3DK-M2
H3DK-S2
User label attachment
location
Main dial
(for setting the time)
Front View
Time range switch
Output indicator (orange)
(Lit while Timer gives output.)
Operation/power indicator (green)
(Lit while the power is ON.)
Operating mode switch
*If the switch is left between settings, proper operation may not be possible.
Make sure that the switch is set properly.
Note: The default settings are for 0.1 s in mode A.
User label attachment
location
Main dial
(for setting the time)
Front View
Time range switch*
Output indicator (orange)
(Lit while Timer gives output.)
Operation/power indicator (green)
(Lit while the power is ON.)
Operating mode switch*
*If the switch is left between settings, proper operation may not be possible.
Make sure that the switch is set properly.
Note: The default settings are for 0.1 s in mode A.
H3DK-M1 H3DK-S1
H3DK-M/H3DK-S
8
Dimensions (Unit: mm)
Timers
Track Mounting Products (Sold Separately)
Refer to page 28 for details.
Operating Procedures
Basic Operation
Setting Switches
Each switch has a snap mechanism that secures the switch at given positions. Set the switch to one of these positions.
Do not set it midway between t wo positions. Malfunction could result from an improper setting.
H3DK-M1
H3DK-S1
89.4
100
88.2
22.522.5 69.1
79
H3DK-M2
H3DK-S2 H3DK-M1
65.6 52
4
22.5
H3DK-S1
H3DK-M
H3DK-S
H3DK-M2
H3DK-S2
Setting the Operating Mode
The H3DK-M can be set to any of eight
operating modes. The H3DK-S can be
set to any of four operati ng modes. Tu rn
the operating mode switch with a flat-
blade or Phillips screwdriver. The H3DK-
M can be set to any of eight modes; t he
H3DK-S, to any of fo ur m o de s.
Switching Relay R2 between
Instantaneous and Time-limit
Contacts (H3DK-M2/-S2 Only)
The INIT/TIME switch can be used to
switch relay R2 between instantaneous
and time-limit operation.
Setting the Time Range
The time range swi tch can be used to set
the time range. Turn the switch with a
flat-blade or Phillips screwdriver.
Setting the Operating Mode
Operating
mode switch
Setting the INIT/TIME Switch
INIT/TIME
switch
Setting the Time Range
Time range
switch
H3DK-M/H3DK-S
9
Timing Charts
There is no start input with the H3DK-S. Timer operation starts when the power is turned ON.
There is no instantaneous output with the H3DK-@1.
Note 1.The reset time is 0. 1 s min. Make sure the signal input time is 0.05 s or longer.
Note 2.“t” is the se t time . “t a” is a time that is less that the set time.
A: ON Delay
B: Flicker OFF Start
B2: Flicker ON start
C: Signal ON/ OFF Delay
tt−a t
Power (A1 and A2)
Start (B1 and A1)
Time-limit contacts: NC
15 and 16 (25 and 26)
Time-limit contacts: NO
(output indicator)
15 and 18 (25 and 28)
Instantaneous contacts: NC
(21 and 22)
Instantaneous contacts: NO
(21 and 24) Power indicator
Power
*
Start input
Output Timing
**
* For power ON-delay operation, connect start input
terminals B1 and A1. The Timer starts operating
as soon as the power turns ON.
** The start input is ignored while the Timer is in
operation.
Basic Oper ation
tt ttt
t−a t−a
Power (A1 and A2)
Start (B1 and A1)
Time-limit contacts: NC
15 and 16 (25 and 26)
Time-limit contacts: NO
(output indicator)
15 and 18 (25 and 28)
Instantaneous contacts: NC
(21 and 22)
Instantaneous contacts: NO
(21 and 24) Power indicator
Power
*
Start input
Output Timing
**
* To start with the power supply, connect start input
terminals B1 and A1. The Timer starts operating
as soon as the power turns ON.
** The start input is ignored while the Timer is in
operation.
TimingTiming
Timing
Basic Operation
tt ttt
t−a t−a
Power (A1 and A2)
Start (B1 and A1)
Time-limit contacts: NC
15 and 16 (25 and 26)
Time-limit contacts: NO
(output indicator)
15 and 18 (25 and 28)
Instantaneous contacts: NC
(21 and 22)
Instantaneous contacts: NO
(21 and 24) Power indicator
Power
*
Start input
Output Timing
**
* To start with the power supply, connect start input
terminals B1 and A1. The Timer starts operating
as soon as the power turns ON.
** The start input is ignored while the Timer is in
operation.
TimingTiming
Timing
Basic Operation
tttt
t−a t−a
Power (A1 and A2)
Start (B1 and A1)
Time-limit contacts: NC
15 and 16 (25 and 26)
Time-limit contacts: NO
(output indicator)
15 and 18 (25 and 28)
Instantaneous contacts: NC
(21 and 22)
Instantaneous contacts: NO
(21 and 24) Power indicator
Power
*
Start input
Output
Timing
* The start input is valid while the Timer is in
operation.
Timing
Timing
Timing
Basic Operation
H3DK-M/H3DK-S
10
Note 1.The reset time is 0.1 s min. Make sure the signal input time is 0.05 s or longer.
Note 2.“t” is the set time. “ta” is a time that is less that the set time.
D: Signal OFF delay
E: Interval
G: Signal ON/ OFF Delay
J: One-shot Output (ON delay)
tt
t−a
Power (A1 and A2)
Start (B1 and A1)
Time-limit contacts: NC
15 and 16 (25 and 26)
Time-limit contacts: NO
(output indicator)
15 and 18 (25 and 28)
Instantaneous contacts: NC
(21 and 22)
Instantaneous contacts: NO
(21 and 24) Power indicator
t−a t−a
Power
*
Start input
Output
* The start input is valid while the Timer is in
operation.
Timing
Basic Operation
tt t
t−a
Power (A1 and A2)
Start (B1 and A1)
Time-limit contacts: NC
15 and 16 (25 and 26)
Time-limit contacts: NO
(output indicator)
15 and 18 (25 and 28)
Instantaneous contacts: NC
(21 and 22)
Instantaneous contacts: NO
(21 and 24) Power indicator
t−a
Power
*
Start input
Output Timing
**
* For power ON-delay operation, connect start input
terminals B1 and A1. The Timer starts operating
as soon as the power turns ON.
** The start input is valid while the Timer is in
operation.
Basic Operation
tttt
t−a
Power (A1 and A2)
Start (B1 and A1)
Time-limit contacts: NC
15 and 16 (25 and 26)
Time-limit contacts: NO
(output indicator)
15 and 18 (25 and 28)
Instantaneous contacts: NC
(21 and 22)
Instantaneous contacts: NO
(21 and 24) Power indicator
t−a
Power
Start input
Output
*
* The start input is valid while the Timer is in
operation.
Timing
Timing
Timing
Timing
Basic Operation
tt t
1 s±0.6 s
(fixed)
1 s±0.6 s
(fixed)
1 s±0.6 s
(fixed)
t−a
Power (A1 and A2)
Start (B1 and A1)
Time-limit contacts: NC
15 and 16 (25 and 26)
Time-limit contacts: NO
(output indicator)
15 and 18 (25 and 28)
Instantaneous contacts: NC
(21 and 22)
Instantaneous contacts: NO
(21 and 24) Power indicator
t−a
Power
*
Start input
Output Timing
**
* To start with the power supply, connect start input
terminals B1 and A1. The Timer starts operating
as soon as the power turns ON.
** The start input is valid while the Timer is in
operation.
1 s±0.6 s
(fixed)
Basic Operation
11
New Product News
Twin Timer
H3DK-F
Switch between flicker-OFF or flicker-ON start mode.
Independent ON time and OFF time settings.
Eight time ranges from 0.1 s to 1,200 h.
LR
Ordering Information
List of Models
Accessories (Order Separately)
Model Structure
Specifications
Time Ranges
Ratings
Operating
modes Supply voltage Control output H3DK-F
Flicker OFF
start/flicker ON
start
24 to 240 VAC/DC Contact out-
put: SPDT Model H3DK-F
12 VDC Contact out-
put: SPDT Model H3DK-FA
Item Specification Model
Mount ing Track
50 cm (l) x 7.3 mm (t) PFP-50N
1 m (l) x 7.3 mm (t) PFP-100N
1 m (l) x 16 mm (t) PFP-100N2
End Plate --- PFP-M
Spacer --- PFP-S
Model Operating modes Terminal block Output typ e Mounting method Safety standards Accessories
H3DK-F Flicker OFF start/flicker ON
start 6 terminals Relay, SPDT DIN Track mounting
cURus
(UL508
CSA C22.2 No. 14)
EN 61812-1
IEC 60664-1 4 kV/2
EN 50274
User label
Time range setting 0.1 s 1 s 10 s 1 min 10 min 1 h 10 h 100 h
Set time range 0.1 to 1.2 s 1 to 12 s 10 to 120 s 1 to 12 min 10 to 120 min 1 to 12 h 10 to 120 h 100 to 1,200 h
Scale numbers 12
Power supply voltage *1 24 to 240 VAC/DC, 50/60 Hz *2
12 VDC *2
Allowable voltage fluctuat ion range 24 to 240 VAC/DC: 85% to 110% of rated voltage
12 VDC: 90% to 110% of rated volta g e
Power reset Minimum power-OFF time: 0.1 s
Reset voltage 10% of rated voltage
Power co nsumptio n H3DK-F At 240 VAC: 4.5VA max. *3
H3DK-FA At 12 VDC: 0.6 W max.
Control output Contact output (SPDT): 5 A at 250 VAC with resistive load (cosφ = 1)
5 A at 24 VDC with resistive load *3, *4
Ambient operating temperature 20 to 55°C (with no icing)
Storage temperature 40 to 70°C (with no icing)
Ambient operating humidity 25% to 85%
H3DK-F
12
*1. When using a 24-VDC power supply voltage, there will be an inrush current of approximately 0.25 A. Allow for this inrush current when turning ON and OFF the
power supply to the Timer with device with a solid-state output, such as a sensor.
*2. DC ripple: 20% max.
*3. Refer to DC Power Consumptions (Reference Information) on page 27 for DC power consumptions.
*4. The cont rol output ratings are for one H3DK operating alone. If you operate two or more Timers side by side, refer to Installat ion Pitch and Output Switchin g Capacity
(Reference Values) on the next page.
*5. 125 VDC: 0. 15 A max. with resistive load, 125 VDC: 0.1 A with L/R of 7 ms.
Minimum load: 10 mA at 5 VDC (P level, reference value)
Characteristics
Installation Pitch and Output
Switching Capacity (Reference
Values)
The relation between the installation pitch
and the load current is shown in th e fol low-
ing graph. (Except for the H3DK-GE)
If Timer is used under load conditions that
exceed the specified values, the tempera-
ture inside the Timer will increase, reduc-
ing the life expectancy of internal parts.
0 1 2 3 4 5 6
80
70
60
50
40
30
20
10
d = 5 mm
d
= 0 mm
d = 10 mm
d = 50 mm
Ambient temperature (°C)
Maximum ambient operating
temperature in specifications
Load current (A)
DIN Track Timer installation pitch: d
Tested Timer: H3DK-F
Applied voltage: 240 VAC
Installation pitch: 0, 5, 10, and 50 mm
Test
timer
1
Test
timer
2
Test
timer
3
Test
timer
4
Test
timer
5
Testing Method
Applicable standards
I/O
Accuracy of operating
time ±1% of FS max. (±1% ±10 ms max. at 1.2-s range)
Setting error ±10% of FS ±0.05 s max.
Influence of voltage ±0.5% of FS max. (±0.5% ±10 ms max. at 1.2-s range)
Influence of tempera-
ture ±2% of FS max. (±2% ±10 ms max. at 1.2-s range)
Insulation resistance 100 M min. at 500 VDC
Dielectric strength
Between current-car rying metal parts and exposed non-current-carrying metal
parts: 2,000 VAC 50/ 60 Hz for 1 min.
Between control out put terminals and o peratin g circuit: 2,0 00 VAC 50/60 Hz for
1 min.
Between contacts not located next to each other: 1,000 VAC 50/60 Hz for
1min.
Impulse withstand volt-
age
24 to 240 VAC/VDC: 3 kV between power termina ls, 4.5 kV between current-
carrying metal parts and exposed non-current-carrying metal parts
12 VDC: 1 kV bet ween po wer t erminals, 1. 5 kV b et ween curren t-car rying met al
parts and exposed non-current-carrying metal parts
Noise immunity Square-wave noise generated by noise simulator (pulse width: 100 ns/1 µs,
1-ns rise): ±1.5 kV
Static immunity Malfunction: 4 kV, Destruction: 8 kV
Vibration
resistance Destruction 0.75-mm single amplitude at 10 to 55 Hz for 2 h each in 3 directions
Malfunction 0.5-mm single amplitude at 10 to 55 Hz for 10 min each in 3 directions
Shock re-
sistance Destruction 1,000 m/s2 3 times each in 6 directions
Malfunction 100 m/s2 3 times each in 6 directions
Life ex-
pectancy Mechanical 10 million operations min. (under no load at 1,800 operations/h)
Electrical 100,000 operations min. (5 A at 250 VAC, resistive load at 360 operations/h)
Degree of protection IP30 (Terminal block: IP20)
Weight Approx. 110 g
Safety standards
cURus: UL 508/CSA C22.2 No. 14
EN 50274: Finger protection, back-of-hand proof
EN 61812-1: Polluti on degree 2, Overvoltage category III
CCC: Pollution degree 2, Overvoltage category II, section DB14048.5-2008 part 5-1
LR: Test Specification No. 1-2002 Category ENV 1.2
EMC
(EMI) EN61812-1
Radiated Emissions: EN 55011 class B
Emission AC Mains: EN 55011 class B
Harmonic Current: EN 61000-3-2
Voltage Fluctuations and Flicker: EN61000-3-3
(EMS) EN61812-1
ESD Immunity: EN 61000-4-2: 6 kV contact discharge,
8 kV air discharge
Radiated Radio-Frequency Electromagnetic Field Immunity (AM Radio Waves):
EN 61000-4-3: 10 V/m (80 MHz to 1 GHz)
Burst Immunity: EN 61000-4-4: 2 kV power line,
1 kV I/O signal line
Surge Immunity: EN 61000-4-5: 2 kV common mode,
1 kV differential mode
Input None
Output Control output Output is turned ON/O FF according to the time set on the ON
time setting dial and OFF time se tting dial.
H3DK-F
13
Connections
Nomenclature
Block Diagrams
H3DK-F
AC (DC)
input
ON
indicator OFF
indicator
One-chip microcomputer
Output circuit
Indicator
circuit
RAMROM Clock
ON/OFF start switch
Power supply
circuit
Time
specification
switches
ON/OFF time setting
detection circuit
Terminal Arrangement
H3DK-F
Note: The power supply terminals do not have po-
larity.
A1 15
A2
18 16
15
R1
1618
A2
A1 15
1816
(DIN notation)
Terminal Block
(See notes 1 and 2.)
ON time range switch
Bottom ViewFront View
ON time setting dial
(Sets the ON time.)
OFF time setting dial
(Sets the OFF time.)
ON output
indicator (orange)
OFF output
indicator (green)
OFF time range switch
ON/OFF start switch
(Default setting is for
an OFF start.)
User label
attachment location
H3DK-F
Note 1. Use solid wire (2.5 mm2 max.) or fer-
rules with insu lative sleeves to connect
to the terminals.
To maintain the withstand voltage after
connecting the terminals, insert no
more than 8 mm of exposed conductor
into the terminal.
Recommended Ferrules
Phoenix Contact
•AI@@@ Series
•AI-TWIN@@@ Series
Note 2. Screw Tightening Torque
Recommended torque: 0.49 N·m
Maximum torque: 0.98 N·m
8 mm max. 8 mm max.
Using Solid Wire
(2.5 mm2 Max.) Using Ferrule with
Insulative Sleeve
H3DK-F
14
Dimensions (Unit: mm)
Timers
Track Mounting Products (Sold Separately)
Refer to page 28 for details.
Operating Procedures
Basic Operation
Timing Charts
Note 1. The reset time is 0.1 s min.
Note 2. When power is supplied in flicker ON start mode, the OFF indicator lights momentarily. This, however, has no effect on the performance of the Timer.
89.4
100
88.2
22.5 69.1
79 65.6 52
4
H3DK-F
Setting the Time Ranges
Use the ON time range switch to set the
ON time range and the OFF ti me range
switch to set the OF F time range. Turn
the switches with a flat-blade or Phillips
screwdriver.
Setting an ON Start or OFF Start
The ON/OFF start switch can be used to
switch between ON-start and OFF-start
operation.
Setting the Times
Use the ON time setting dial and the
OFF time setting dial to set the ON time
and OFF time.
Setting the Time Ranges
OFF time range
switch
ON time range
switch
Setting the ON/OFF Start Switch
ON/OFF start
switch
Setting the Times
ON time setting dial
OFF time setting dial
Flicker OFF start Flicker ON start
tON tOFF tOFFtOFFtOFF tON
tON: ON set time
tOFF: OFF set time
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Power (A1 and A2)
ON indicator (15 and 18)
OFF indicator (15 and 16)
0.1 s min.
Output (15 and 18)
tOFF tOFF tONtONtONtON
ON
OFF
ON
OFF
ON
OFF
ON
OFF tON: ON set time
tOFF: OFF set time
Power (A1 and A2)
ON indicator (15 and 18)
OFF indicator (15 and 16)
0.1 s min.
Output (15 and 18)
15
New Product News
Set two time ranges between 1 and 120 s with one Timer.
Models with 240 to 440-VAC power supply added to series. LR
Ordering Information
List of Models
Accessories (Order Separately)
Model Structure
*1. Except for the H3DK-GE.
Specifications
Time Ranges
Ratings
Operating modes Supply voltage Control output H3DK-G
Star-delta Timer
24 to 240 VAC/DC Contact outputs
Delta circuit: SPDT, Star circuit: SPDT
Model H3DK-G
12 VDC Model H3DK-GA
240 to 440 VAC Model H3DK-GE
Item Specification Model
Mount ing Track
50 cm (l) x 7.3 mm (t) PFP-50N
1 m (l) x 7.3 mm (t) PFP-100N
1 m (l) x 16 mm (t) PFP-100N2
End Plate --- PFP-M
Spacer --- PFP-S
Model Terminal block Operati n g/ resettin g method Output typ e Mounting method Safety standards Accessories
H3DK-G 9 terminals Time-limit operation/self-
resetting
Time-limit (relay)
Star circuit: SPDT
Delta circuit: SPDT DIN Track mounting
cURus*1
(UL 508
CSA C22.2 No. 14)
EN 61812-1
IEC 60664-1 4 kV/2
EN 50274
User label
Time range setting t1x1 t1x10
Star set time (t1) range 1 to 12 s 10 to 120 s
Star-Delta transfer time (t2) Select from 0.05, 0.1, 0.25, or 0.5 s.
H3DK-G, -GA H3DK-GE
Power supply voltage *1 24 to 240 VAC/DC, 50/60 Hz *2
12 VDC *2 240 to 440 VAC (50/60 Hz) *6
Allowable voltage fluctuat ion range 24 to 240 VAC/DC: 85% to 110% of rated voltage
12 VDC: 90% to 110% of rated volta g e 80 % to 110% of rated voltage
Power reset Minimum power-OFF time: 0.5 s
Reset voltage 10% of rated voltage
Power co nsumptio n H3DK-G At 240 VAC: 6.6 VA max. *3 At 440 VAC: 34 VA max.
H3DK-GA At 12 VDC: 0.9 W max.
Control output
Contact output (Time-limit output: relay, Star output:
SPDT, Delta output: SPDT):
5 A at 250 VAC with resistive load (cosφ = 1)
5 A at 24 VDC with resistive load *3, *4
Ith 2 A
AC-15 120 VAC: 1.5 A
AC-15 240 VAC: 1 A
AC-15 440 VAC: 0.3 A
Ambient operating temperature 20 to 55°C (with no icing)
Storage temperature 40 to 70°C (with no icing)
Ambient operating humidity 25% to 85%
Star-delta Timer
H3DK-G
H3DK-G
16
*1. When using a 24-VDC power supply voltage, there will be an inrush current of approximately 0.25 A. Allow for this inrush current when turning ON and OFF the
power supply to the Timer with device with a solid-state output, such as a sensor.
*2. DC ripple: 20% max.
*3. Refer to DC Power Consumptions (Reference Information) on page 27 for DC power consumptions.
*4. The cont rol output ratings are for one H3DK operating alone. If you operate two or more Timers side by side, refer to Installat ion Pitch and Output Switchin g Capacity
(Reference Values) on the next page.
*5. 125 VDC: 0. 15 A max. with resistive load, 125 VDC: 0.1 A with L/R of 7 ms.
Minimum load: 10 mA at 5 VDC (P level, reference value)
*6. For the H3DK-GE, approx. 6 A of inrush current will flow when the power supply is turned ON. When selecting the device connected to the Timer, allow leeway in
the current ratings.
Characteristics
Installation Pitch and Output
Switching Capacity (Reference
Values)
The relation bet ween the installat ion pitch
and the load current is shown in the fol-
lowing graph. (Except for the H3DK-GE)
If Timer is used under load conditi ons that
exceed the spec ifi ed va lu es, th e t empera -
ture inside the Timer will increase, reduc-
ing the life expectancy of internal parts.
0 1 2 3 4 5 6
80
70
60
50
40
30
20
10
d = 5 mm
d = 0 mm
d = 10 mm
d = 50 mm
Ambient temperature (°C)
Maximum ambient operating
temperature in specifications
Load current (A)
DIN Track Timer installation pitch: d
Tested Timer: H3DK-G
Applied voltage: 240 VAC
Installation pitch: 0, 5, 10, and 50 mm
Test
timer
1
Test
timer
2
Test
timer
3
Test
timer
4
Test
timer
5
Testing Method
* Except for the H3DK-GE
H3DK-G, -GA H3DK-GE
Accuracy of operating
time ±1% of FS max.
Setting error ±10% of FS ±0.05 s max.
Transfer time Total error ± (25% of transfer time + 5 ms) max.
Influence of voltage ±0.5% of FS max.
Influence of tempera-
ture ±2% of FS max.
Insulation resistance 100 M min. at 500 VDC
Dielectric strength
Between current-car rying metal parts
and exposed non-current-carrying metal
parts: 2,000 VAC 50/ 60 Hz for 1 min.
Between control output terminals and
operating circuit: 2,000 VAC 50/60 Hz
for 1 min.
Between con t acts not locat e d n ext to
each other: 1,000 VAC 50/60 Hz for
1min.
Between current-carrying metal parts
and exposed non-current-carrying metal
parts: 2,500 VAC 50/60 Hz for 1 min.
Between control output terminals and
operating circuit: 2,500 VAC 50/6 0 Hz
for 1 min.
Between contacts not located next to
each other: 1,000 VAC 50/60 Hz for
1min.
Impulse withstand volt-
age
H3DK-G: 24 to 240 VAC/VDC: 3 kV
between power terminals, 4.5 kV
between current-carrying metal
parts and exposed non-current-
carrying metal parts
H3DK-GA: 12 VDC: 1 kV between
power terminals, 1.5 kV between
current-carrying metal parts and
exposed non-current-carrying
metal parts
---
Noise immunity Square-wave noise generated by noise simulator (pulse width: 100 ns/1 µs,
1-ns rise): ±1.5 kV*
Static immunity Malfunction: 4 kV, Destruction: 8 kV
Vibration
resistance Destruction 0.75-mm single amplitude at 10 to 55 Hz for 2 h each in 3 directions
Malfunction 0.5-mm single amplitude at 10 to 55 Hz for 10 min each in 3 directions
Shock re-
sistance Destruction 1,000 m/s2 3 times each in 6 directions
Malfunction 100 m/s2 3 times each in 6 directions
Life ex-
pectancy
Mechanical 10 million operations min. (under no
load at 1,800 operations/h) 10 million operations min.
(under no load at 1,800 operat ions/h)
Electrical 100,000 operations min. (5 A at 250
VAC, resistive load at 360 operations/ h)
100,000 operations min.
(0.3 A at 440 VAC, resistive load at
1,800 operations/h)
Degree of protection IP30 (Terminal block: IP20)
Weight Approx. 120 g
H3DK-G
17
Applicable standards
*1. This standard is not applicable to the H3DK-GE.
*2. This standard is not applicable if the output is used with a rating that exceeds 250 VAC.
I/O
Connections
Safety standards
cURus: UL 508/CSA C22.2 No. 14 *1
EN 50274: Finger protection, back-of-hand proof
EN 61812-1: Pollution degree 2, Overvoltage category III *2
CCC: Pollution degree 2, Overvoltage category II, section DB14048.5-20 08 part 5-1
LR: Test Specification No. 1-2002 Category ENV 1.2 *1
EMC
(EMI) EN61812-1
Radiated Emissions: EN 55011 class B
Emission AC Mains: EN 55011 class B
Harmonic Current: EN 61000-3-2 *1
Voltage Fluctuations and Flicker: EN61000-3-3 *1
(EMS) EN61812-1
ESD Immunity: EN 61000-4-2: 6 kV contact discharge,
8 kV air discharge
Radiated Radio-Frequency Electromagnetic Field Immunity (AM Radio Waves):
EN 61000-4-3: 10 V/m (80 MHz to 1 GHz)
Burst Immunity: EN 61000-4-4: 2 kV power line,
1 kV I/O signal line
Surge Immunity: EN 61000-4-5: 2 kV common mode,
1 kV differential mode
Input None
Output Contr ol output The star output is turned OFF when the dial set value is reache d and the
delta output is turned ON af ter the preset transfer time elapses.
Block Diagrams
H3DK-G
Indicator circuit
AC (DC) input
Star output
Power supply
circuit
Star time
setting
switch
Star-delta
transfer time
switch
Output
circuit
Delta output
Star output ON
indicator Delta output ON
indicator
One-chip microcomputer
RAMROM Clock
Terminal Arrangement
H3DK-G
Note: The power supply terminals do not have po-
larity.
A1 15
25
2628
A2
18 16
15
R1
1618
25
R2
2628
A2
A1 15
1816
25
2826
(DIN notation)
Star
contacts Delta
contacts
H3DK-G
18
Nomenclature
Terminal block
(See notes 1 and 2.)
Main dial
(Sets the star time.)
Bottom ViewFront View
User label
attachment location
Star operation
indicator (green)
Star-delta transfer time
switch
Delta operation
indicator (orange)
Bottom ViewFront View
Main dial
(Sets the star time.)
User label
attachment location
Star operation
indicator (green)
Star-delta transfer time
switch
Delta operation
indicator (orange)
Terminal block
(See notes 1 and 2.)
Front cover
(See note 3.)
H3DK-
G
Note 1. Use solid wire (2.5 mm2 max.) or fer-
rules with insulative sleeves to connect
to the terminals.
To maintain the withstand voltag e after
connecting the ter m inals, insert no
more than 8 mm of exposed conductor
into the terminal.
Recommended Ferrules
Phoenix Contact
•AI@@@ Series
AI-TWIN@@@ Series
Note 2. Screw Tig ht ening Tor q ue
Recommended torque: 0.49 N·m
Maximum torque: 0.98 N·m
Note 3. Always keep the front cover mounted
when using the Timer.
8 mm max. 8 mm max.
Using Solid Wire
(2.5 mm2 Max.) Using Ferrule with
Insulative Sleeve
H3DK-GE
H3DK-G
19
Dimensions (Unit: mm)
Timers
Track Mounting Products (Sold Separately)
Refer to page 28 for details.
89.4
100
88.269.1
79 65.6 52
22.5 4
89.4
88.2 69.1
102
55
65.6
79
4
22.5
26
H3DK-G
H3DK-GE
H3DK-G
20
Operating Procedures
Basic Operation
Setting the Delta Time Range and the Star-delta Transfer
Time (t2)
Star Time (t1) Range
Set the star-de lta tra n sf e r time .
For ×1 (1 to 12 s), use side (A) (labeled “t1×1”).
For ×10 (10 to 120 s), use side (B) (lab eled “t10×1”).
(See following diagram.)
Setting the Time
The start time is set with the main dial.
Timing Chart
Setting the Time Ranges
t2t2
0.5s
0.25s
0.1s
0.05s
0.5s
0.25s
0.1s
0.05s
t1x10t1x1
(A) (B)
Star-delta transfer
time setting (t2)
Switches the start
time (t1) range.
Setting the Time
Main dial
Note: “t1” is the start set time. “t2” is the transfer time.
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
t1t2
t1: Star time setting
t2: Transfer time
Power (A1 and A2)
Star contacts (15 and 18)
Delta contacts (25 and 26)
0.5 s min.
Star operation indicator
Delta operation indicator
21
New Product News
Power OFF-delay Timer
H3DK-H
Set two time ranges with each Timer, from 0.1 to 12 seconds for
the S Series and from 1.0 to 120 seconds for the L Series.
Ordering Information
List of Models
Accessories (Order Separately)
Model Structure
Specifications
Time Ranges
Ratings
Operating modes Supply voltage Control output
H3DK-H
S Series
(time range: 0.1 to 12 s) L Series
(time range: 1.0 to 120 s)
Power OFF Delay 100 to 120 VAC Contact output: SPDT Model H3DK-HCS H3DK-HCL
200 to 240 VAC Contact output: SPDT Model H3DK-HDS H3DK-HDL
24 to 48 VAC/DC Contact output: SPDT Model H3DK-HBS H3DK-HBL
Item Specification Model
Mount ing Track
50 cm (l) x 7.3 mm (t) PFP-50N
1 m (l) x 7.3 mm (t) PFP-100N
1 m (l) x 16 mm (t) PFP-100N2
End Plate --- PFP-M
Spacer --- PFP-S
Model Terminal block Operati n g/ resettin g method Output typ e Mounting method Safety standards Accessories
H3DK-H 6 terminals Instantaneous operation/
time-limit reset Relay, SPDT DIN Track mounting
cURus
(UL 508
CSA C22.2 No. 14)
EN 61812-1
IEC 60664-1 4 kV/2
EN 50274
User label
S Series L Series
Time range setting x0.1 x1 x1 x10
Set time range 0.1 to 1.2 s 1 to 12 s 1 to 12 s 10 to 120 s
Power ON time 0.1 s min. 0.3 s min.
Scale numbers 12
Supply voltage 100 to 120 VAC, 50/60 Hz
200 to 240 VAC, 50/60 Hz
24 to 48 VAC/DC, 50/60 Hz *1
Allowable voltage fluctuat ion range 85% to 110% of rated voltage
Power co nsumptio n H3DK-HCS/-HCL At 120 VAC: 11.7 VA max.
H3DK-HDS/-HDL At 240 VAC: 29.5 VA max.
H3DK-HBS/-HBL At 48 VAC: 1.2 VA max. *2
Control output Contact output, 5 A at 250 VAC with resistive load (cosφ = 1), 5 A at 30 VDC with
resistive load *2
Ambient operating temperature 20 to 55°C (with no icing)
Storage temperature 40 to 70°C (with no icing)
Ambient operating humidity 25% to 85%
H3DK-H
22
*1. DC ripple: 20% max. (A single-phase, full-wave rectifyin g power supply can be connected.)
*2. Refer to DC Power Consumptions (Reference Information) on page 27 for DC power consumptions.
*3. The control output ratings are for one H3DK operating alone.
If you operate two or more Timers side by side, refer to Installation Pitch and Output Switching Capacity (Refer ence Values) on the next page.
Characteristics
Applicable standards
I/O
Accuracy of operating
time ±1% of FS max. (±1% ±10 ms max. at 1.2-s range)
Setting error ±10% of FS ±0.05 s max.
Influence of voltage ±0.5% of FS max. (±0.5% ±10 ms max. at 1.2-s range)
Influence of tempera-
ture ±2% of FS max. (±2% ±10 ms max. at 1.2-s range)
Insulation resistance 100 M min. at 500 VDC
Dielectric strength
Between current-car rying metal parts and exposed non-current-carrying metal
parts: 2,000 VAC 50/ 60 Hz for 1 min.
Between control out put terminals and o peratin g circuit: 2,0 00 VAC 50/60 Hz for
1 min.
Between contacts not located next to each other: 1,000 VAC 50/60 Hz for
1min.
Impulse withstand volt-
age
Between power supply t erminals: 1 kV for 24-VAC/ DC and 48-VAC/DC models,
3 kV for all other models.
Between current-car rying metal parts and exposed non-current-carrying metal
parts): 1.5 kV for 24-VAC/D C and 48-VAC/DC models, 4.5 kV for all other
models.
Noise immunity Square-wave noise generated by noise simulator (pulse width: 100 ns/1 µs,
1-ns rise): ±1.5 kV (between power supply terminals)
Static immunity Malfunction: 4 kV, Destruction: 8 kV
Vibration
resistance Destruction 0.75-mm single amplitude at 10 to 55 Hz for 2 h each in 3 directions
Malfunction 0.5-mm single amplitude at 10 to 55 Hz for 10 min each in 3 directions
Shock re-
sistance Destruction 1,000 m/s2 3 times each in 6 directions
Malfunction 100 m/s2 3 times each in 6 directions
Life ex-
pectancy Mechanical 10 million operations min. (under no load at 1,200 operations/h)
Electrical 100,000 operations min. (5 A at 250 VAC, resistive load at 1,200 operations/h)
Degree of protection IP30 (Terminal block: IP20)
Weight Approx. 120 g
Safety standards
cURus: UL 508/CSA C22.2 No. 14
EN 50274: Finger protection, back-of-hand proof
EN 61812-1: Polluti on degree 2, Overvoltage category III
CCC: Pollution degree 2, Overvoltage category II, section DB14048.5-2008 part 5-1
LR: Test Specification No. 1-2002 Category ENV 1.2
EMC
(EMI)EN61812-1
Radiated Emissions:EN 55011 class B
Emission AC Mains:EN 55011 class B
Harmonic Current:EN 61000-3-2
Voltage Fluctuations and Flicker:EN61000-3 -3
(EMS)EN61812-1
ESD Immunity:EN 61000-4-2: 6 kV contact discharge,
8 kV air discharge
Radiated Radio-Frequency Electromagnetic Field Immunity (AM Radio Waves):
EN 61000-4-3: 10 V/m (80 MHz to 1 GHz)
Burst Immunity:EN 61000-4-4: 2 kV power line,
1 kV I/O signal line
Surge Immunity:EN 61000-4-5: 2 kV common mode,
1 kV differential mode
Input None
Output Control output The Timer operates as soon as the Timer is turned ON. The
Timer starts timing when the po wer is turned OFF and the output
is turned OFF when the time set on the dial ela pses.
Installation Pitch and Output
Switching Capacity (Reference
Values)
The relati on between the i nstalla tion pit ch
and the load current is shown in the fol-
lowing graph. (Except for the H3DK-GE)
If Timer is used u nder load conditions t hat
exceed the specified values, the tempera-
ture inside the Timer will increase, reduc-
ing the life expectancy of internal parts.
0 1 2 3 4 5 6
80
70
60
50
40
30
20
10
d = 5 mm
d
= 0 mm
d = 10 mm
d = 50 mm
Ambient temperature (°C)
Maximum ambient operating
temperature in specifications
Load current (A)
DIN Track Timer installation pitch: d
Tested Timer: H3DK-H
Applied voltage: 240 VAC
Installation pitch: 0, 5, 10, and 50 mm
Test
timer
1
Test
timer
2
Test
timer
3
Test
timer
4
Test
timer
5
Testing Method
H3DK-H
23
Connections
Nomenclature
Block Diagrams
H3DK-H
Output circuitCounting circuitOscillation circuit
Indicator circuit
AC (DC) input
Power supply
circuit
Time specification
switches
Power
interruption
detection circuit
Terminal Arrangement
H3DK-H
Note 1: The above figure shows the terminal ar-
rangement for a 24 to 48-VAC/DC model.
Models with 100 to 120-VAC or 200 to
240-VAC power input do not have a DC
input.
Note 2: The power supply terminals do not have
polarity.
A1 15
A2
18 16
15
R1
1618
A2
A1 15
1816
(DIN notation)
Terminal block
(See notes 1 and 2.)
Bottom View
Main dial
(for setting the time)
Front View
Time range switch
(S Series: ×0.1 or
×1, L Series: ×1 or
×10)
Power indicator
(green) (Lit while
the power is ON.)
User label
attachment location
H3DK-H
Note 1. Use solid wire (2.5 mm2 max.) or fer-
rules with insulative sleeves to connect
to the terminals.
To maintain the withstand vo ltage after
connecting the terminals, insert no
more than 8 mm of exposed conductor
into the terminal.
Recommended Ferrules
Phoenix Contact
•AI@@@ Seri e s
•AI-TWIN@@@ Series
Note 2. Screw Tightening Torque
Recommended torque: 0.49 N·m
Maximum torque: 0.98 N·m
8 mm max. 8 mm max.
Using Solid Wire
(2.5 mm2 Max.) Using Ferrule with
Insulative Sleeve
H3DK-H
24
Dimensions (Unit: mm)
Timers
Track Mounting Products (Sold Separately)
Refer to page 28 for details.
Operating Procedures
Basic Operation
Setting the Time Ranges
The scale multiplier can be changed with the timer range switch.
It can be changed bet ween ×0.1 s and ×1 s for an S-series Ti mer
and between ×1 s and ×10 s for an L-series Timer.
Setting the Time
The operation time is set with the main dial.
Timing Charts
89.4
100
88.2
22.5 69.1
79 65.6 52
4
H3DK-H
Setting the Time Ranges
Time range
switch
Setting the Time
Main dial
t: Set time
Rt: Minimum power-ON time
(The output may never turn ON if the power is not ON for at least this time.)
ON
OFF
ON
OFF
ON
OFF
Rt t t
Rt
Power (A1 and A2)
Output relay: NO (15 and 18)
Indicator
S Series: 0.1 s min.
L Series: 0.3 s min.
H3DK
25
Safety Precautions
Refer to Safety Precautions for All Timers.
Note: The following is common for all H3DK models.
Switching arcs or relay heating may cause fire or
explosion. Do no t use the Timer in the presence of
inflammable or explosive gases.
The H3DK Series uses a transformerless power
supply system. An electrical shock may occur if
an input terminal is touched while power is being
supplied.
The inrush current will depend on the type of load
and may influence the contact switching fre-
quency and number of o peration s. Chec k b oth the
rated current and the inrush current, and allow
leeway in the circuit design.
The life of the output relay largely depends on the
switching current and other switch conditions.
Consider the actual application conditions and do
not exceed the rated load or electrical life. If the
output relay is used beyond its service life, the contacts
may fuse or burning may occur. Also, never exceed the
rated load current. When using a heater, also place a ther-
mal switch in the loa d ci rc ui t.
Do not remove the external case.
Minor electric shock, fire, or equipment failure
may sometimes occur. Do not disassemble, mod-
ify, or repair the Timer or touch any in ternal parts.
Use ferrules to wire t he H3DK. If stranded wires are use d, wire
scraps may enter the Timer, possibly shorting the circuits.
Rapid changes in temperature or high humidity may cause
condensation in Timer circuits, possibly resulting in malfunc-
tion or damage to components. Check the application environ-
ment.
Store the Timer within the rated ranges given for the Timer
model you are using. If the Timer is stored below 20°C, allo w
it to warm up for three hours at room temperature before turn-
ing ON the power supply.
Use the Timer within the ambient operating temperature and
ambient operating humidity ranges given for the Timer model
you are using.
Use the Time within the characteristics for water and oil expo-
sure given fo r t he Tim e r m o de l yo u ar e us ing.
Do not use the Timer in locations subject to excessive dust,
corrosive gas, or direct sunlight.
Do not use the Timer in locations subject to vibration and
shock. Long-term exposure may damage the Timer due to
stress.
Separate the Timer from any sources of excessive static elec-
tricity, such as forming materials and pipes carrying power or
liquid materials.
Maintain the variations in the power supply voltage to within
the specified allowable range.
If a voltage that exceeds the rating is applied, internal compo-
nents may be destroyed.
Wire all terminals correctly.
Use only the specified wires for wi ring.
Applicable wire gauge: AWG18 to AWG22
Install and clearly label a switch or circuit breaker so that the
operator can quickly turn OFF the power supply.
If th e T imer is lef t in the t i med o ut cond it io n for a lon g pe ri od of
time at high temperatures, internal components (such as elec-
trolytic capacitors) may deteriorate quickly.
The ext erior of t he Timer may b e damaged by organic so lvents
(such as thinners or benzene), strong alkali, or strong acids.
For Timers wi th AC power input , use a commerci al power sup -
ply for the power supply voltage. Although some inverters give
50/60 Hz as the output frequency, do not use an inverter out-
put as the power supply for a Timer. Doing so may result in
smoking or burning due to internal temperature increases in
the Timer.
Use the same type of wiring for all Timer wiring.
When disposing of the Timer, observe all local ordinances as
they apply.
The Timer may not operate properly in locations that are sub-
ject to sulfide gas, such as in sewers or incinerators. Products
that are suitable for operation in sulfide gas are not available
for OMRON Timers or general control devices. Seal the Timer
to isolate it from sulfide gas. If the Timer cannot be sealed,
OMRON can make special products with resistance to sulfide
gas for some Timers. Ask your OMRON representative for
details.
Confirm that the power and output indicators are operating
normally. Depend ing on th e operati ng environme nt, th e indica-
tors and plastic parts may deteriorate faster than expected,
causing the indicators to fail. Periodically perform inspections
and replacements.
Caution Precautions for Safe Use
H3DK
26
Changing Switch Settings
Do not change the time uni t, time sca le, opera ting mode, or INI T/
TIME switch while the Timer is in operation. Doing so may result
in malfunction. Turn OFF the power supply before changing the
setting of any switch.
Mounting and Dismoun tin g
Although there are no particular mounting restrictions, the
Timer should be mounted as horizontally as possibl e.
When mounting the Timer on a mounting Track, loosen the
two hooks, press the Timer onto the Track, and then insert the
hooks.
When removing the Timer, pull out the two hooks, and then
remove the Timer from the Track
It will be easier to mount and dismount the Timer if a distance
of 30 mm or more is provided between the bott om of the Timer
and other equipment.
Power Supply
The power supply can be connected to the power input termi-
nals without considering polarity.
A DC power supply can be connected if its ri pple factor is 20%
or less and the average voltage is within the allowable voltage
fluctuation range of the Timer.
For the power supply of the input device, use an isolating
transformer in which the primary and secondary windings are
mutually isolat ed and the secondary winding is not grounded.
(H3DK-M1 and H3DK-M2 only)
The H3DK-H has a large inrush current. Provide sufficient
power supply capacity.
If the power supply capacity is too small, there may be delays
in turning ON the output.
Relationship between Input and Power Supply Cir-
cuits (H3DK-M1/-M2)
The input circuit and the power supply circuit are configured
independently. The input circuit can be turned ON and OFF
without considering the ON/OFF state of the power supply.
A voltage equivalent to the power supply voltage is also
applied to the input circuit.
If a relay or transistor is connected to two or more Timers, the
input terminals of those Timers must be wired properly so that
they will not be dif f erent in p hase o r the t ermin als wi ll be short-
circuited to one another. Always use the same power supply
phases.
Environment
When using the Timer in an area with excessive electronic
noise, separate the Timer and input device as far as possible
from the noise sources. It is also recommended to shield the
input signal wiring to prevent electronic interference.
The extern al impuls e voltage entering across the power s upply
terminals has been checked against a ±1.2×50 µs standard
waveform according to JEC-210, Impulse Voltage/Current
Test, of The Institute of Electrical Engineers of Japan. Surge
or noise superimposed on the power supply may damage
internal components or cause t hem to malfu nction . We recom-
mend that you check the circuit waveform and use surge
absorbers. The effects on components depend on the type of
surge and noise that are generated. Always perform testing
with the actual equipment.
Precautions for Correct Use
Hook
Hook
30 mm min.
Hook
Hook
A1
B1
A2
Circuit
Power
H3DK
Isolation transformer is required.
Rectifier circuit
Start
input
Input circuit
Power supply circuit
B1 A1
A2
AC/DC
power supply
H3DK
H3DK
Power
B1
A1
A2
A1
A2
B1
H3DK
H3DK
Power
B1
A1
A2
A1
A2
B1
Contact or transistor for
external input signal
Contact or transistor for
external input signal
H3DK
27
Wiring
The H3DK-H acts like a high-impedance circuit. Therefore, the
Timer may not reset if it is influenced by inductive voltage. To
eliminate inductive voltage, the wires connected to the Timer
must be as short as possible and should not be installed parallel
to power lines. If the Ti mer is inf luence d by i ndu ctiv e volt age tha t
is 30% or more of the rated voltage, connect a CR filter with a
capacitance of approximately 0.1 µF and a resistance of approx-
imately 120 or a bleeder resistor between the power supply
terminals.
If there is any residual voltage due to current leakage, connect a
bleeder resistor between the power supply terminals.
Operating Frequency
The H3DK-H may malfunction if it is used as shown below. Do
not use the H3DK-H in these ways.
Timer Repeatedly Ti mes Out in Cycles of 3 s or Less
In the above case, use the H3DK-M2/-M1 in D mode (signal
OFF delay).
DC Power Consumptions (Reference Information)
Other Precautions
If the Timer is mounted on a control panel, dismount the Timer
from the control panel before carrying out a voltage withstand
test between the electric circuits and non-current-carrying
metal parts o f the T imer. (Ot herwise , the i nt ernal ci rcui ts o f the
Timer may be damaged.)
The H3DK-H uses a latching relay for the output. Shock, such
as dropping the H3DK-H during shipment or handling, can
cause the output contacts to reverse to the neutral position.
Check the output status with a tester before using the H3DK-
H.
The life expectancy of the control output contacts is greatly
affected by switching conditions. Always confirm operation
using the actual conditions and equipment before using the
Timer and make sure that the number of switching operations
presents no problems in performance. If Timer application is
continued after performance has deteriorated, insulation fail-
ure between circuits, burning of the control output relay, or
other problem will eventual ly occur.
If the power supply voltage is gradually increased, a power
reset may occur or the Timer may time out. Use a switch,
relay, or other device with contacts to apply the power supply
voltage all at once.
Make sure that residual voltage or inductive voltage is not
applied afte r the p ower turns OFF.
Error in the operation time of the Timer is given as a percent-
age of the full-scale time. The absolute value of the error will
not change even if the set time is changed. Therefore, always
use the Tim er with the set time set as c lose as poss ible to th e
full-scale value of the set time range.
When switching a microload, check the specified minimum
load given for the Timer model you are using.
When setting the operating time, do not turn the dial beyond
the scale range.
If better accuracy is required in the set time, adjust the dial
while measuring the operation time.
If the Timer is reset immediately after timing out, make sure
that the circuit configuration allows sufficient resetting time.
Errors will occur in the sequence if there is not sufficient reset-
ting time.
When directly switching a DC load, the switching capacity will
be lower than when switching an AC load.
Refer to the datasheet for the H3DK for cable selection and
other conditions for compliance with EMC standards.
The power supply terminals and input terminals are not iso-
lated. There is basic insulation between the power supply ter-
minals and output terminals.
If double or reinforced insulation is required, use the double or
reinforced insulation defined in IEC 60664 that is suitable for
the maximum applied voltage for the clearance, solid insula-
tion, and other factors.
Notice to Users of the H3DK in the USA and Canada
Please use the following installation information instead of the
general information in this document in order to use the product
under certified conditions of UL and CSA when the product is
installed in the USA or Canada . These conditions are required by
NFPA 70, National Electrical Code in the USA and the Canadian
Electrical Code, Part I in Canada and may vary from information
given in this document.
Use an isolated source for power input for the H3DK-@A.
Use an isolated source with external overcurrent protection of
16 A maximum for the source and input. (The input is applica-
ble to the H3DK-M only.)
Environment
Surrounding Air Temperature: 55°C
Power Supply: The inputs are non-isolated (applicable to
H3DK-M only).
The same power supply as the main power source must be
used for that for input.
Pol lution Degree
Pollution degree II
H3DK-M2/-S2 At 24 VDC: 1.2 W max.
H3DK-M1/-S1 At 24 VDC: 1.1 W max.
H3DK-F At 24 VDC: 1.1 W max.
H3DK-G At 24 VDC: 1.2 W max.
H3DK-HBS/-HBL At 24 VDC: 1.2 W max.
Power
Output
3 s
or less
3 s
or less
EN/IEC Standard Compliance Precautions for Compliance with UL Standards
and CSA Standards
H3DK
28
Track Mounting Products (Sold Separately)
(Unit: mm)
Note 1: Order the above products in multiple s of 10.
Note 2: The Tracks conform to DIN standards.
1
35±0.3
7.3±0.15
27±0.15
4.5
15 25 25
10 15 (5)*
10
25 25
*Dimensions in parentheses are for the PFP-50N.
1,000 (500)*
DIN Track
PFP-100N
PFP-50N
15 25 25 1,000
4.5
25 25 15
10 1
242735
±0.3
16
1.5
29.2
10
DIN Track
PFP-100N2
4.8
1.3
35.5 35.3
1.8
1
1.8
10 6.2
M4 screw
and washer
50
11.5
10
M4x8
panhead
screw
End Plate
PFP-M
516
12
44.3 34.8
16.5
Spacer
PFP-S
Warranty and Application Considerations
Read and Understand This Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have
any questions or comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's e xclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or
other period if specified) from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT,
MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER
A CKNO WLEDGES THAT THE BUYER OR USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET
THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR
IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NO T BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL D AMA GES, LOSS OF PR OFITS ,
OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON
CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY.
In no e vent shall the responsibility of OMRON f o r any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR O THER CLAIMS REGARDING THE
PRODUCTS UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED,
INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE
MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of
products in the customer's application or use of the products.
Take all necessary steps to determine the suitability of the product for the systems, machines, and equipment with which it will
be used.
Know and observe all prohibitions of use applicable to this product.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT
ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON
PRODUCTS ARE PR OPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE O VERALL EQUIPMENT OR
SYSTEM.
Disclaimers
PERFORMANCE DATA
Performance data gi ven in this catalog is provided as a guide for the user in determining suitability and does not constitute a
warranty. It may repre sent the result of OMRON's test conditions, and the users must correlate it to actual application
requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability.
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons. Consult with
your OMRON representative at any time to confirm actual specific ations of purchased product.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when to lerances are shown.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Authorized Distributor:
In the interest of product improvement,
specifications are subject to change without notice.
Cat. No. L118-E1-02 Printed in Japan
0910
© OMRON Corporation 2010 All Rights Reserved.
OMRON Corporation Industrial Automation Company
OMRON ELECTRONICS LLC
One Commerce Drive Schaumburg,
IL 60173-5302 U.S.A.
Tel: (1) 847-843-7900/Fax: (1) 847-843-7787
Regional Headquarters
OMRON EUROPE B.V.
Wegalaan 67-69-2132 JD Hoofddorp
The Netherlands
Tel: (31)2356-81-300/Fax: (31)2356-81-388
Contact: www.ia.omron.com
Tokyo, JAPAN
OMRON ASIA PACIFIC PTE. LTD.
No. 438A Alexandra Road # 05-05/08 (Lobby 2),
Alexandra Technopark,
Singapore 119967
Tel: (65) 6835-3011/Fax: (65) 6835-2711
OMRON (CHINA) CO., LTD.
Room 2211, Bank of China Tower,
200 Yin Cheng Zhong Road,
PuDong New Area, Shanghai, 200120, China CSM_3_1_0212
Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Omron:
H3DK-HCS AC100-120V H3DK-HDL AC200-240V