LEM reserves the right to carry out modications on its transducers, in order to improve them, without prior notice. www.lem.com
Page 1/3
100121/18
IPN = 200 .. 1500 A
VOUT = ± 4 V
Features
Hall effect measuring principle
Galvanic isolation between
primary and secondary circuit
Isolation voltage 3000 V
Low power consumption
Extended measuring range
(3 x IPN)
Isolated plastic case recognized
according to UL 94-V0.
Advantages
Easy installation
Small size and space saving
Only one design for wide current
ratings range
High immunity to external
interference.
Applications
DC motor drives
Switched Mode Power Supplies
(SMPS)
AC variable speed drives
Uninterruptible Power Supplies
(UPS)
Battery supplied applications
Power supplies for welding
applications.
Application domain
Industrial
Current Transducer HAT 200 .. 1500-S
For the electronic measurement of currents: DC, AC, pulsed,...,
with galvanic isolation between the primary circuit (high power) and
the secondary circuit (electronic circuit).
Electrical data
Type Primary nominal Primary current, RoHS since
current rms measuring range1) date code
IPN (A) IPM (A)
HAT 200-S 200 ± 600 47143
HAT 400-S 400 ± 1200 46115
HAT 500-S 500 ± 1500 46129
HAT 600-S 600 ± 1800 46115
HAT 800-S 800 ± 2400 46115
HAT 1000-S 1000 ± 2500 46097
HAT 1200-S 1200 ± 2500 77271
HAT 1500-S 1500 ± 2500 46158
VC Supply voltage (± 5 %) 1) ± 15 V
IC Current consumption ± 15 mA
RIS Isolation resistance @ 500 VDC > 1000 M
VOUT Output voltage (Analog) @ ± IPN, RL =10 kΩ, TA = 25°C ± 4 V
ROUT Output internal resistance 100
RL Load resistance > 10 k
X Accuracy @ IPN , TA = 25°C (excluding offset) ≤ ± 1 % of IPN
Accuracy - Dynamic performance data
εL Linearity error 2) (0 .. ± IPN) ≤ ± 1 % of IPN
VOE Electrical offset voltage @ TA = 25°C < ± 20 mV
VOH Hysteresis offset voltage @ IP = 0,
after an excursion of 1 x IPN < ± 10 mV
TCVOE Temperature coefcient of VOE < ± 1 mV/K
TCVOUT Temperature coefcient of VOUT (% of reading) < ± 0.1 %/K
tr Response time to 90 % of IPN step < 5 µs
BW Frequency bandwidth 3) (- 3 dB) DC .. 25 kHz
TA Ambient operating temperature - 10 .. + 80 °C
General data
TS Ambient storage temperature - 25 .. + 85 °C
m Mass 300 g
Notes: 1) Operating at ± 12V ≤ VC < ± 15V will reduce the measuring range
2) Linearity data exclude the electrical offset
3) Please refer to derating curves in the technical le to avoid excessive core
heating at high frequency.
LEM reserves the right to carry out modications on its transducers, in order to improve them, without prior notice. www.lem.com
Page 2/3
100121/18
Current Transducer HAT 200 .. 1500-S
Isolation characteristics
Vd Rms voltage for AC isolation test, 50 HZ, 1 min 4.9 kV
Vw Impulse withstand voltage 1.2/50 µs > 9.0 kV
Min
dCp Creepage distance 9.9 mm
dCI Clearance distance 9.9 mm
CTI Comparative Tracking Index (group IIIa) 275
Applications examples
According to EN 50178 and IEC 61010-1 standards and following conditions:
Over voltage category III
Pollution degree PD2
Non-uniform eld
Safety
This transducer must be used in electric/electronic equipment with respect
to applicable standards and safety requirements in accordance with the
manufacturers operating instructions.
Caution, risk of electrical shock
When operating the transducer, certain parts of the module can carry hazardous
voltage (eg. primary busbar, power supply).
Ignoring this warning can lead to injury and/or cause serious damage.
This transducer is a build-in device, whose conducting parts must be inaccessible
after installation.
A protective housing or additional shield could be used.
Main supply must be able to be disconnected.
EN 50178 IEC 61010-1
dCp, dCI,
Rated isolation voltage
Nominal voltage
Single isolation
800 V
800 V
Reinforced isolation
400 V
300 V
Vw
LEM reserves the right to carry out modications on its transducers, in order to improve them, without prior notice. www.lem.com
Page 3/3
100121/18
Dimensions HAT 200 .. 1500-S (in mm. 1 mm = 0.0394 inch)
Mechanical characteristics
General tolerance ± 1 mm
Transducer fastening By base-plate
or on busbar
with M4 screws
All slots 4.5 mm
Recommended fastening torque 0.75Nm ± 20%
(0.6~0.9Nm)
Connection of secondary Molex 5045-04A
Remarks
I s is positive when IP ows in the direction of the arrow.
The temperature of the primary busbar cannot exceed
100°C.
081016/6 www.lem.com
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
Page 3/3
Dimensions HAT 520..850-S (in mm. 1 mm = 0.0394 inch)
Mechanical characteristics
General tolerance ± 1 mm
Transducer fastening By base-plate or on
bus bar with M4
screws.
All slots 4.5 mm
Connection of secondary Molex 5045-04A
Remarks
IS is positive when IP flows in the direction of the arrow.
Temperature of the primary conductor should not exceed
100°C.
70
30.5
40.5
65
20
8
90
4
30
25
9.5
5.8
1.5
1.5
24
37
10
20
3
2.1
12
4.50
6
12
4.50
678 1
29
9.3
5
4 1
Pins Arrangement
1 2 3 4
+ - OUT GND
Current Direction
第一视角
第三视角
第一视角
第三视角