1
Monitoring technique
Undervoltage relay BA 9043, AA 9943
varimeter
According to IEC 255, EN 60 255, VDE 0435 part 303
3-phase
For nominal voltage of 3 AC 100 / 57 to 690 / 400 V
Measures arithmetic mean value
Adjustable operate and release value
For 3p3w or 3p4w systems
BA 9043 optionally with adjustable time delay
Closed circuit operation
LED indicator for operation and state of contact
Insensitive to harmonics
Frequency up to 400 Hz
Width 45 mm
Function diagram
Undervoltage detection in 3 phase systems
Approvals and marking
Application
Circuit diagram
BA 9043, BA 9043/002 BA 9043/001, BA9043/003
AA 9943 AA 9943/001
Indicators
upper LED: on, when voltage connected
(only BA 9043)
lower LED: on, when output contact activated
Technical data
Input
Nominal voltage UN
BA 9043, BA 9043/002
AA 9943: 3/N AC 100/57 V; 230/127 V; 400/230 V
415/240 V; 440/254 V; 500/290 V
50 ... 400 Hz
BA 9043, BA 9043/002: 3 AC 50 / 60 Hz 400 / 690 V
BA 9043/001, BA 9043/003
AA 9943/001: 3 AC 100 V; 230 V; 400 V; 415 V, 440 V;
500 V; 50 ... 400 Hz
BA 9043/001, BA 9043/003: 3 AC 50 / 60 Hz 690 V
Max. overload
BA 9043: 1,2 UN continuously
AA 9943: 1,1 UN continuously
Nominal consumption: AC 4 VA
Nominal frequency: 50 ... 400 Hz
Frequency range: ± 5 %
Temperature influence: < 0,05 % / K
Setting ranges
Response value: 0,85 ... 1,05 UN, infinite variable with
upper potentiometer
Hysteresis: 0,75 ... 0,95 of operate value
Setting accuracy: ≤ ± 10 %
Switching delay tM:see diagram switching delay
Time delay tv:infinite variable from 0,5 ... 10 sec for
BA 9043/002, BA 9043/003
Between 0,4 and 0,6 UN the contacts
fall back according to the diagram
without additional delay
BA 9043, AA 9943 / 04.09.03 d
BA 9043 AA 9943
0221539
All technical data in this list relate to the state at the moment of edition. We reserve the right
for technical improvements and changes at any time.
tv
tv
BA9043
BA9043/001
AA9943
BA9043/002
BA9043/003
11-14
11-14
11-12
11-12
t
3 phases L1, L2, L3
0,4-0,6UN
U
operate value
hysteresis
M6864_a
Notes
In units with time delay the delay is only active at > 0,4 UN. At < 0,4 UN
the rela y switches without dela y.
L1
L1
11 21L2
L3
12 22
L3
L2
N
14 24 N
M7520
2111
2212 2414
L1
L1
11 21L2
L3
12 22
L3
L2
14 24
M7521
2111
2212 2414
2
Continuous current limit curve
A = Devices mounted with 2 cm distance
B = Devices mounted without distance
Diagr am switching dela y
Switching delay t M:
When the voltage changes fast on the measur ing input, the arithmetic
mean value can only adjust after a short delay.
Example:
F = F = = 1,26
U applied = 190 V
U setting = 240 V
according to diagr am:
tMon = approx . 800 ms
tMoff = appro x. 100 ms
Output
Contacts
BA 9043: 2 changeover contacts
AA 9943.11: 1 changeover contact
AA 9943.12: 2 changeover contacts
Thermal current Ith:6 A; see diagramm
Continuous current limit curve
Switching capacity
to AC 15
NO contact: 3 A / AC 230 V IEC/EN 60 947-5-1
NC contact: 1 A / AC 230 V IEC/EN 60 947-5-1
Electrical life IEC/EN 60 947-5-1
to AC 15 at 3 A, AC 230 V: 3 x 10 5 switching cycles
Short circuit strength
max. fuse rating: 4 A gL IEC/EN 60 947-5-1
Mechanical life: > 30 x 106 switching cycles
General data
Operating mode: Continuous operation
Temperature range: - 20 ... + 60°C
Clearance and creepage
distances
overvoltage category /
contamination level: 4 kV / 2 IEC 60 664-1
EMC
Electrostatic discharge: 8 kV (air) IEC/EN 61 000-4-2
HF irradiation: 10 V/m IEC/EN 61 000-4-3
Fast transients: 2 kV IEC/EN 61 000-4-4
Surge voltages
between
wires for power supply: 1 kV IEC/EN 61 000-4-5
between wire and ground: 2 kV IEC/EN 61 000-4-5
HF wire guided: 10 V IEC/EN 61 000-4-6
Interference suppression: Limit value class B EN 55 011
Degree of protection: Housing: IP 40 IEC/EN 60 529
Terminals: IP 20 IEC/EN 60 529
Housing: Thermoplastic with V0 behaviour
according to UL subject 94
Vibration resistance: Amplitude 0,35 mm IEC/EN 60 068-2-6
frequency 10 ... 55 Hz
Climate resistance: 20 / 060 / 04 IEC/EN 60 068-1
Terminal designation: DIN EN 50 005
Wire connection: 2 x 2,5 mm2 solid or
2 x 1,5 mm2 stranded wire with sleeve
DIN 46 228-1/-2/-3/-4
Wire fixing: Flat terminals with self-lifting
clamping piece IEC/EN 60 999-1
Mounting: DIN rail IEC/EN 60 715
Weight
BA 9043: 310 g
AA 9943: 300 g
Dimensions
Width x height x depth
BA 9043: 45 x 73 x 132 mm
AA 9943: 45 x 77 x 127 mm
Technical data
Accessories
AA 9943:
K 70-34 Cov er
Characteristics
U applied
U setting 240 V
190 V
t [s]
1,0
0 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1 1,2
1,2
1,4
1,6
1,8
2,0
F
M6866_a
x off
xon
Variants
AA 9943/001: without neutral
AA 9943/175: earth quake proof
BA 9043/001: without neutral
BA 9043/002: with neutral, adjustable time dela y
tv = 0,5 ... 10 sec
BA 9043/003: without neutral, adjustab le time delay
tv = 0,5 ... 10 sec
Standard type
BA 9043 3/N AC 400 / 230 V 50 ... 400 Hz
Article number: 0039676 stock item
f or 3p4w systems
Nominal voltage UN: 3/N A C 400 / 230 V
Output: 2 changeov er contacts
Width: 45 mm
Variants
Ordering example f or Variants
BA 9043 /_ _ _ 3/N AC 400/230 V 50 ... 400 Hz
Nominal frequency
Nominal voltage
Variant, if required
Type
AA 9943 .11 /_ _ _ 3/N AC 400/230 V 50 ... 400 Hz
Nominal frequency
Nominal voltage
Variant, if required
Contact
Type
I (A)
ambient temperature
contact current
M6865_a
1
-20 0 204060
A
B
T (°C)
2
3
4
5
6
3
Specification for tender for BA 9043
Undervoltage relay according to IEC 255, VDE 0435 for nominal voltage
of 3 AC 100/57 to 500/290 V. Adjustable operate and release value, for
3p4w systems
Width 45 mm
Type BA 9043
Manufactured by E. DOLD & SÖHNE KG
Undervoltage relay according to IEC 255, VDE 0435 for nominal voltage
of 3 AC 100/57 to 500/290 V. Adjustable operate and release value, for
3p4w systems, adjustable time delay up to 10 s.
Width 45 mm
Type BA 9043/002
Manufactured by E. DOLD & SÖHNE KG
Undervoltage relay according to IEC 255, VDE 0435 for nominal voltage
of 3 AC 100/57 to 500/290 V. Adjustable operate and release value, for
3p3w systems
Width 45 mm
Type BA 9043/001
Manufactured by E. DOLD & SÖHNE KG
Undervoltage relay according to IEC 255, VDE 0435 for nominal voltage
of 3 AC 100/57 to 500/290 V. Adjustable operate and release value, for
3p3w systems, adjustable time delay up to 10 s.
Width 45 mm
Type BA 9043/003
Manufactured by E. DOLD & SÖHNE KG
4
E. DOLD & SÖHNE KG • D-78114 Furtwangen
e-mail dold-relays
@t-online.de • internet http://www.dold.com
Postf. 1251 • Tel. +49 7723 654 0 • Telefax +49 7723 654 356