https://www.phoenixcontact.com/us/products/2800674
06/05/2020Page1/13
Lightning/surge arrester type 1/2-VAL-MS-T1/T2 175/12.5/1+1-
FM-2800674
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Universal varistor-based plug-in lightning/surge arrester for 1-phase power supply networks with separate N and
PE (3-conductor system: L1, N, PE), with remote indication contact.
Your advantages
Plugs can be checked with CHECKMASTER
With floating remote indication contact
Secure hold of plugs in the event of high lightning current loads and strong vibrations thanks to new latching
Mechanical coding of all slots
Optical, mechanical status indication for the individual arresters
Pluggable
Thermal disconnect device for each individual plug
Key Commercial Data
Packing unit 1 pc
GTIN
GTIN 4046356624336
Weight per Piece (excluding packing) 320.000 g
Custom tariff number 85363030
Country of origin Germany
Technical data
Dimensions
Height 96.8 mm
https://www.phoenixcontact.com/us/products/2800674
06/05/2020Page2/13
Lightning/surge arrester type 1/2-VAL-MS-T1/T2 175/12.5/1+1-
FM-2800674
Technical data
Dimensions
Width 35.6 mm
Depth 77.5 mm (incl. DIN rail 7.5mm)
Horizontal pitch 2 Div.
Ambient conditions
Degree of protection IP20 (only when all terminal points are used)
Ambient temperature (operation) -40 °C ... 80 °C
Ambient temperature (storage/transport) -40 °C ... 80 °C
Altitude ≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation) 5 % ... 95 %
Shock (operation) 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation) 7.5g (10 ... 500 Hz / 2.5 h / X, Y, Z)
General
IEC test classification I / II
I
T1 / T2
T1
EN type T1 / T2
T1
IEC power supply system TT
TN-C
TN-S
Mode of protection L-N
L-PE
N-PE
Mounting type DIN rail: 35 mm
Color jet black RAL 9005
Housing material PA 6.6
PBT
Degree of pollution 2
Flammability rating according to UL 94 V-0
Type DIN rail module, two-section, divisible
Surge protection fault message Optical, remote indicator contact
Additional descriptions
Note Nominal voltage UN = 120 V AC/240 V AC split-phase (separate GND)
https://www.phoenixcontact.com/us/products/2800674
06/05/2020Page3/13
Lightning/surge arrester type 1/2-VAL-MS-T1/T2 175/12.5/1+1-
FM-2800674
Technical data
Protective circuit
Nominal voltage UN120VAC (TN-S)
120VAC (TT)
Nominal frequency fN50 Hz (60Hz)
Maximum continuous operating voltage UC (L-N) 175 VAC
Maximum continuous operating voltage UC (L-PE) 175 VAC
Maximum continuous voltage UC (N-PE) 264 VAC
Rated load current IL80 A
Residual current IPE ≤ 5 µA
Standby power consumption PC≤ 140 mVA
Nominal discharge current In (8/20) µs (L-N) 12.5 kA
Nominal discharge current In (8/20) µs (L-PE) 12.5 kA
Nominal discharge current In (8/20) µs (N-PE) 50 kA
Maximum discharge current Imax (8/20) µs 50 kA
Impulse discharge current (10/350)µs (L-N), charge 6.25 As
Impulse discharge current (10/350) µs (L-N), specific energy 39 kJ/Ω
Impulse discharge current (10/350)µs (L-N), peak current value Iimp 12.5 kA
Impulse discharge current (10/350) µs (L-PE), charge 6.25 As
Impulse discharge current (10/350)µs (L-PE), specific energy 39 kJ/Ω
Impulse discharge current (10/350) µs (L-PE), peak current value Iimp 12.5 kA
Impulse discharge current (10/350) µs (N-PE), charge 25 As
Impulse discharge current (10/350) µs (N-PE), specific energy 625 kJ/Ω
Impulse discharge current (10/350) µs (N-PE), peak current value Iimp 50 kA
Total discharge current Itotal (8/20)µs 50 kA
Total discharge current Itotal (10/350)µs 25 kA
Follow current interrupt rating Ifi (N-PE) 100 A
Short-circuit current rating ISCCR 25 kA
Voltage protection level Up (L-N) ≤ 0.8 kV
Voltage protection level Up (L-PE) ≤ 2 kV
Voltage protection level Up (N-PE) ≤ 1.7 kV
Residual voltage Ures (L-N) ≤ 0.8 kV (at In)
≤ 0.65 kV (at 10 kA)
≤ 0.6 kV (at 5 kA)
≤ 0.5 kV (at 3 kA)
Residual voltage Ures (L-PE) ≤ 2 kV (at In)
≤ 1.5 kV (at 10 kA)
https://www.phoenixcontact.com/us/products/2800674
06/05/2020Page4/13
Lightning/surge arrester type 1/2-VAL-MS-T1/T2 175/12.5/1+1-
FM-2800674
Technical data
Protective circuit
≤ 1.4 kV (at 5 kA)
≤ 1.3 kV (at 3 kA)
Residual voltage Ures (N-PE) ≤ 0.6 kV (at In)
≤ 0.5 kV (at 10 kA)
≤ 0.5 kV (at 5 kA)
≤ 0.4 kV (at 3 kA)
TOV behavior at UT (L-N) 208 VAC (5s / withstand mode)
229 VAC (120min / withstand mode)
TOV behavior at UT (N-PE) 1200 VAC (200ms / withstand mode)
Response time tA (L-N) ≤ 25 ns
Response time tA (L-PE) ≤ 100 ns
Response time tA (N-PE) ≤ 100 ns
Max. backup fuse with V-type through wiring 80 A (gG - 16 mm²)
Max. backup fuse with branch wiring 160 A (gG)
Indicator/remote signaling
Switching function PDT contact
Operating voltage 5 VAC ... 250 VAC
30 VDC
Operating current 5 mA AC ... 1.5 A AC
1 ADC
Connection method Plug-in/screw connection via COMBICON
Screw thread M2
Tightening torque 0.25 Nm
Stripping length 7 mm
Conductor cross section flexible 0.14 mm² ... 1.5 mm²
Conductor cross section solid 0.14 mm² ... 1.5 mm²
Conductor cross section AWG 28 ... 16
Connection data
Connection method Screw connection
Screw thread M5
Tightening torque 3 Nm (1.5mm² ... 16mm²)
4.5 Nm (25mm² ... 35mm²)
Stripping length 16 mm
Conductor cross section flexible 1.5 mm² ... 25 mm²
Conductor cross section solid 1.5 mm² ... 35 mm²
https://www.phoenixcontact.com/us/products/2800674
06/05/2020Page5/13
Lightning/surge arrester type 1/2-VAL-MS-T1/T2 175/12.5/1+1-
FM-2800674
Technical data
Connection data
Conductor cross section AWG 15 ... 2
Connection method Fork-type cable lug
Conductor cross section flexible 1.5 mm² ... 16 mm²
UL specifications
SPD Type 4CA
Maximum continuous operating voltage MCOV (L-N) 175 VAC
Maximum continuous operating voltage MCOV (L-G) 175 VAC
Maximum continuous operating voltage MCOV (N-G) 264 VAC
Nom. voltage 120VAC
Mode of protection L-N
L-G
N-G
Power distribution system Single phase
Nominal frequency 50/60 Hz
Measured limiting voltage MLV (L-N) 2200 V
Measured limiting voltage MLV (L-G) 3160 V
Measured limiting voltage MLV (N-G) 2600 V
Nominal discharge current In (L-N) 20 kA
Nominal discharge current In (L-G) 20 kA
Nominal discharge current In (N-G) 20 kA
UL indicator/remote signaling
Operating voltage 125 VAC
Operating current 1 A AC
Tightening torque 4 lbf-in.
Conductor cross section AWG 30 ... 14
UL connection data
Conductor cross section AWG 10 ... 2
Tightening torque 30 lbf-in.
Standards and Regulations
Standards/regulations IEC61643-11 2011
EN61643-11 2012
Environmental Product Compliance
China RoHS Environmentally Friendly Use Period = 50 years
https://www.phoenixcontact.com/us/products/2800674
06/05/2020Page6/13
Lightning/surge arrester type 1/2-VAL-MS-T1/T2 175/12.5/1+1-
FM-2800674
Technical data
Environmental Product Compliance
For details about hazardous substances go to tab “Downloads”, Category
“Manufacturer's declaration”
Drawings
Circuit diagram
https://www.phoenixcontact.com/us/products/2800674
06/05/2020Page7/13
Lightning/surge arrester type 1/2-VAL-MS-T1/T2 175/12.5/1+1-
FM-2800674
Dimensional drawing
Classifications
eCl@ss
eCl@ss 4.0 27140201
eCl@ss 4.1 27130801
eCl@ss 5.0 27130801
eCl@ss 5.1 27130800
eCl@ss 6.0 27130800
eCl@ss 7.0 27130802
eCl@ss 8.0 27130802
eCl@ss 9.0 27130802
ETIM
ETIM 2.0 EC000941
ETIM 3.0 EC000941
ETIM 4.0 EC000381
ETIM 5.0 EC000381
ETIM 6.0 EC000381
ETIM 7.0 EC000381
https://www.phoenixcontact.com/us/products/2800674
06/05/2020Page8/13
Lightning/surge arrester type 1/2-VAL-MS-T1/T2 175/12.5/1+1-
FM-2800674
Classifications
UNSPSC
UNSPSC 6.01 30212010
UNSPSC 7.0901 39121610
UNSPSC 11 39121610
UNSPSC 12.01 39121610
UNSPSC 13.2 39121620
UNSPSC 19.0 39121620
Accessories
Accessories
Bridge
Wiring bridge-MPB F600X16/ 1GS-2818355
Wiring bridge flexible, diameter: 16 mm², with a fork-type cable lug on one side, length: 600 mm
Wiring bridge-MPB F600X16/ 1GS-2818355
Wiring bridge flexible, diameter: 16 mm², with a fork-type cable lug on one side, length: 600 mm
Wiring bridge-MPB F200X16/ 1GS-2818339
Wiring bridge flexible, diameter 16 mm², with a fork-type cable lug on one side, length: 200 mm
https://www.phoenixcontact.com/us/products/2800674
06/05/2020Page9/13
Lightning/surge arrester type 1/2-VAL-MS-T1/T2 175/12.5/1+1-
FM-2800674
Accessories
Wiring bridge-MPB 18/1-10/1.0.0-2830443
Wiring bridge for modules with connecting pitch 17.5 mm, 1-phase, 10 pitches with contact sequence 1-0-0
Wiring bridge-MPB 18/4-12-2809296
Wiring bridge for modules with connecting pitch 17.5 mm, 4-phase, 12-pos.
Wiring bridge-MPB 18/4- 8-2809283
Wiring bridge for modules with connecting pitch 17.5 mm, 4-phase, 8-pos.
Wiring bridge-MPB 18/3- 6-2809241
Wiring bridge for modules with connecting pitch 17.5 mm, 3-phase, 6-pos.
Wiring bridge-MPB 18/1-57-2809238
Wiring bridge for modules with connecting pitch 17.5 mm, 1-phase, 57-pos.
https://www.phoenixcontact.com/us/products/2800674
06/05/2020Page10/13
Lightning/surge arrester type 1/2-VAL-MS-T1/T2 175/12.5/1+1-
FM-2800674
Accessories
Wiring bridge-MPB 18/1-12-2748593
Wiring bridge for modules with connecting pitch 17.5 mm, 1-phase, 12-pos.
Wiring bridge-MPB 18/1- 9-2748580
Wiring bridge for modules with connecting pitch 17.5 mm, 1-phase, 9-pos.
Wiring bridge-MPB 18/1- 8-2748577
Wiring bridge for modules with connecting pitch 17.5 mm, 1-phase, 8-pos.
Wiring bridge-MPB 18/1- 6-2748564
Wiring bridge for modules with connecting pitch 17.5 mm, 1-phase, 6-pos.
Wiring bridge-MPB 18/1- 4-2809225
Wiring bridge for modules with connecting pitch 17.5 mm, 1-phase, 4-pos.
https://www.phoenixcontact.com/us/products/2800674
06/05/2020Page11/13
Lightning/surge arrester type 1/2-VAL-MS-T1/T2 175/12.5/1+1-
FM-2800674
Accessories
Wiring bridge-MPB 18/1- 3-2809212
Wiring bridge for modules with connecting pitch 17.5 mm, 1-phase, 3-pos.
Wiring bridge-MPB 18/1- 2-2809209
Wiring bridge for modules with connecting pitch 17.5 mm, 1-phase, 2-pos.
Device marking
Zack marker strip-ZBN 18:UNBEDRUCKT-2809128
Zack marker strip, Strip, white, unlabeled, can be labeled with: CMS-P1-PLOTTER, PLOTMARK, mounting type: snap
into tall marker groove, for terminal block width: 18 mm, lettering field size: 18 x 5 mm, Number of individual labels: 5
Feed-through terminal block
Feed-through terminal block-DK-BIC-35-2749880
Feed-through terminal block for VAL and FLT applications
Labeled device marker
https://www.phoenixcontact.com/us/products/2800674
06/05/2020Page12/13
Lightning/surge arrester type 1/2-VAL-MS-T1/T2 175/12.5/1+1-
FM-2800674
Accessories
Marker for terminal blocks-ZBN 18,LGS:ERDE-2749589
Marker for terminal blocks, Strip, white, labeled, Horizontal: Grounding symbol, mounting type: snap into tall marker
groove, for terminal block width: 18 mm, lettering field size: 18 x 5 mm, Number of individual labels: 5
Marker for terminal blocks-ZBN 18,LGS:L1-N,ERDE-2749576
Marker for terminal blocks, Strip, white, labeled, Horizontal: L1, L2, L3, N, GND, mounting type: snap into tall marker
groove, for terminal block width: 18 mm, lettering field size: 18 x 5 mm, Number of individual labels: 5
Marker pen
Marker pen-B-STIFT-1051993
Marker pen, for manual labeling of unprinted Zack strips, smear-proof and waterproof, line thickness 0.5 mm
Spare parts
Type 1/2 surge protection plug-VAL-MS-T1/T2 175/12.5 ST-2800676
L-N replacement plug for VAL-MS-T1/T2 175/12.5 plug-in lighting/surge arrester.
https://www.phoenixcontact.com/us/products/2800674
06/05/2020Page13/13
Lightning/surge arrester type 1/2-VAL-MS-T1/T2 175/12.5/1+1-
FM-2800674
Accessories
Type 1/2 surge protection plug-F-MS-T1/T2 50 ST-2800191
N-PE replacement plug for VAL-MS-T1/T2 335/12.5 plug-in lighting/surge arrester.
Phoenix Contact 2020 © - all rights reserved
http://www.phoenixcontact.com