60
CB2200 Series Supplemental Circuit Breakers
CB2200 Series
Single Pole
CB2200 Series
Double Pole
CB2200 Series
Triple Pole
Ordering Data Type: Single Pole* Type: Double Pole Type: Triple Pole
Current Ratings N/O Aux. Current Ratings N/O-N/C Current Ratings N/O-N/C
(amps) Part No. (amps) Part No. (amps) Part No.
0.1 9911010005 0.1 9912010003 0.1 9913010003
0.2 9911020005 0.2 9912020003 0.2 9913020003
0.3 9911030005 0.3 9912030003 0.3 9913030003
0.4 9911040005 0.4 9912040003 0.4 9913040003
0.5 9911050005 0.5 9912050003 0.5 9913050003
0.6 9911060005 0.6 9912060003 0.6 9913060003
0.8 9911080005 0.8 9912080003 0.8 9913080003
1.0 9911100005 1.0 9912100003 1.0 9913100003
1.5 9911150005 1.5 9912150003 1.5 9913150003
2.0 9911200005 2.0 9912200003 2.0 9913200003
2.5 9911250005 2.5 9912250003 2.5 9913250003
3.0 9911300005 3.0 9912300003 3.0 9913300003
4.0 9911400005 4.0 9912400003 4.0 9913400003
5.0 9911500005 5.0 9912500003 5.0 9913500003
6.0 9911600005 6.0 9912600003 6.0 9913600003
8.0 9911800005 8.0 9912800003 8.0 9913800003
10 9921100005 10 9922100003 10 9923100003
12 9921120005 12 9922120003 12 9923120003
15 9921150005 15 9922150003 15 9923150003
16 9921160005 16 9922160003 16 9923160003
18 9921180005 18 9922180003 18 9923180003
20 9921200005 20 9922200003 20 9923200003
25 9921250005
32 9921320005
*All part numbers with N/O Auxiliary Contacts on each pole when the main breaker contact is open (in the OFF position)
Circuit Breakers
Thermal Magnetic Type
Rated from 0.1 to 32.0 amps
Available in single, double and triple
pole configurations
Offers normally open (N/O) and normally
closed (N/C) auxiliary contacts
Lever-switch trip/reset function
Mounts on 32mm or 35mm DIN-rail
UL 1077 recognized
CSA C22.2 No. 235
Ordering Data Type: Single Pole Type: Double Pole Type: Triple Pole
Current Ratings Current Ratings Current Ratings
(amps) Part No. (amps) Part No. (amps) Part No.
0.1 9911010000 0.1 9912010000 0.1 9913010000
0.2 9911020000 0.2 9912020000 0.2 9913020000
0.3 9911030000 0.3 9912030000 0.3 9913030000
0.4 9911040000 0.4 9912040000 0.4 9913040000
0.5 9911050000 0.5 9912050000 0.5 9913050000
0.6 9911060000 0.6 9912060000 0.6 9913060000
0.8 9911080000 0.8 9912080000 0.8 9913080000
1.0 9911100000 1.0 9912100000 1.0 9913100000
1.5 9911150000 1.5 9912150000 1.5 9913150000
2.0 9911200000 2.0 9912200000 2.0 9913200000
2.5 9911250000 2.5 9912250000 2.5 9913250000
3.0 9911300000 3.0 9912300000 3.0 9913300000
4.0 9911400000 4.0 9912400000 4.0 9913400000
5.0 9911500000 5.0 9912500000 5.0 9913500000
6.0 9911600000 6.0 9912600000 6.0 9913600000
8.0 9911800000 8.0 9912800000 8.0 9913800000
10 9921100000 10 9922100000 10 9923100000
12 9921120000 12 9922120000 12 9923120000
15 9921150000 15 9922150000 15 9923150000
16 9921160000 16 9922160000 16 9923160000
18 9921180000 18 9922180000 18 9923180000
20 9921200000 20 9922200000 20 9923200000
25 9921250000 25 9922250000 25 9923250000
32 9921320000 32 9922320000 32 9923320000
All part numbers with N/C Auxiliary Contacts on each pole when the main breaker contact is open (in the OFF position)
61
Technical Data
Rated voltage & current
UL
CSA
VDE
Auxiliary contacts
Creepage resistance
Dielectric strength
Insulation resistance
Interrupting capacity
(VDE 0660, Part 101, P-2)
Interrupting capacity
(UL 1077/EN 60934 PC1)
Typical life at 2 x rated current
Shock
Torque Nm (lb. in.)
Vibration
Temperature range
Corrosion
Humidity
Weight
Wire size (UL)
Accessories
Jumpers Daisy Chain 50
Busbars
Marking Tags
Special print only
Consecutive horizontal
Consecutive vertical
CB2200 Series Supplemental Circuit Breakers
Voltage Ratings Current Ratings
277 / 480 VAC (50/60 Hz); 65 VDC 0.1…32 A
277 / 480 VAC (50/60 Hz); 65 VDC 0.1…32 A
250 / 415 VAC / 65 VDC 0.1…32 A
250 VAC / 65 VDC, 1 A
PTI 600 to IEC 112
3,000 VAC; IEC 664 & 664 A
> 100 MM(DC 500 V)
Rated current Rated voltage Rupture capacity (3 times)
0.05…0.8 A 250 / 415 VAC 400 A
6…32 A 250 / 415 VAC 800 A
Rated current Rated voltage Max. rupture capacity (3 times)
0.1…16 A 277 / 480 VAC 5000 A
20…32 A 277 / 480 VAC 2000 A
0.1…32 A 65 VDC 2000 A
5,000 operations
25 g (11 ms) to IEC 68-2-27, Test Ea
0.6 (5.3) Auxiliary contact: 0.5 (4.4)
5 g (57 to 500 Hz / ±0.38 mm, 10 to 57 Hz) to IEC 68-2-6, Test Fc
-30…+60°C (-22°F…+140°F)
96 hours at 5% salt spray, to IEC 68-2-11, Test Ka
240 hours at 95% RH, to IEC 68-2-3, Test Ca
Approximately 60 g per pole
max 6 mm2…8 AWG max 1.5 mm2…14 AWG (Aux. contact)
Type Part No.
BDC 50, 20 A maximum 9970290000
1 pole (CB2200) 9986510000
2 pole (CB2200) 9987360000
DEK 5/6 0490360000*
DEK 5/6 0468660001
DEK 5/6 0468760001
CB2200 Series
123456
Dimensions in mm
Note: Resistive and inductive loads (0.05 - 16 A)
*Please specify horizontal or vertical print when ordering.
Note: Part numbers shown are for a single
card of pre-printed tags numbered 1-50.
Trip Curves—Thermal Magnetic Type
Typical time/current characteristics at 23ºC
CB2200 Series
F1 0.1 to 32 A
1
.8 123468
10 20 30 50 70 100
0.001
0.01
0.1
10
100
1,000
10,000
…times rated current
Trip time in seconds
–30°C
+23°C
+55°C
10
T
-M1 0.1 to 7.5 A
DC
AC
.8 123468
10 20 30 50 70 100
0.001
0.01
0.1
10
100
1,000
10,000
…times rated current
Trip time in seconds
–30°C
AC +23°C
DC +23°C
+55°C
.8 123468
10 20 30 50 70 100
0.001
0.01
0.1
1
10
100
1,000
10,000
…times rated current
Trip time in seconds
–30°C
+23°C
+55°C
-T1 8 to 32 A
-T1 0.1 to 7.5 A
.8 123468
10 20 30 50 70 100
0.001
0.01
0.1
10
100
1,000
10,000
…times rated current
Trip time in seconds
–30°C
+23°C
+55°C
-M1 8 to 32 A
DC
AC
.8 123468
10 20 30 50 70 100
0.001
0.01
0.1
10
100
1,000
10,000
…times rated current
Trip time in seconds
–30°C
AC +23°C
DC +23°C
+55°C