PGFI Series - 30 Amp Multi-Phase Portable (Cord) Series
276
PGFI Series
30 Amp Multi-Phase Portable Series (Cord) GFCI / ELCI
INTRODUCTION
The LineGard™ 30 Amp Portable Series is an industrial grade ground fault interrupter device designed and manufactured by North
Shore Safety, Ltd., a leader in innovated safety products.
Available with an operating voltage of 120/240 VAC, 3Ø 120/208 VAC, 3Ø 240 VAC (certified to CSA 22.2 only) or 3Ø 208 VAC, 3Ø 277
VAC (UL 1053 compliant). This product can be integrated during after-market equipment upgrades or used as a stand-alone portable
cordset. All units are MADE IN THE USA and are listed per UL 943 and CSA 22.2 No.144. Note that any power cord integrated with
this GFCI becomes OSHA compliant for portable power usage in confinded space: OSHA 29 CFR 1926.404 (b)(1)(ii) and OSHA 29 CFR
1926.405 (a)(2)(ii)(G). Additionally, these devices meet NEC requirement 590.6 (a) and (b).
• Powerandfaultstatusindicators
• Doubleinsulateduserinterface
• Industrialdesignforroughservice
• ChemicalandUVresistantenclosure
• cULusListedasaClassAGFCIperUL943and
CSA 22.2 No. 144
• 30ampconfigurationsin120/240VAC4-wire,
3Ø 120/208 VAC 5-wire, 3Ø 240 VAC 4-wire,
3Ø 208 VAC 4-wire, 3Ø 277 VAC 4-wire (UL 1053)
• NEMA4Xand6Pwetlocationrated(indoor/outdoor)
• Availableinautomaticormanualresetconfigurations*
SPECIFICATIONS
Listing Type cULus Listed Class A
UL 943, UL 1053
CSA 22.2 No. 144
Rated Supply Voltage 120/240 VAC, 3Ø 120/208 VAC,
3Ø 240 VAC (CSA only),
3Ø 208 VAC, 3Ø 277 VAC (UL 1053)
Rated Current Up to 30 Amps or rating of wiring
device and/or cable
Horse Power 1HP @ 120 VAC, 3HP @ 240 VAC
Trip Level, Class A 5mA +/– 1mA
Phase Dual voltage and 3 phase
Operating Frequency 60 Hz
Reset Type1Automatic or Manual
Response Time 25mS max
Operating Temperature –35°C to 66°C
Operating Voltage Range 85% to 110% of rated VAC
Let-Go Voltage 60% of supply voltage
Open Neutral Protection Trips upon loss of neutral
Grounded Neutral Protection Trips if ground and neutral touch
at load side
1. Manual configuration should be specified if automatic start-up after power
restoration of circuit power creates an unsafe condition.