1
Thermal (T- and TA-Line) T13-211
https://www.schurter.com /PG17_20
Circuit Breakers
Circuit Breaker for Equipment thermal, Threaded neck type, Reset type, Quick connect terminals
See below:
Approvals and Compliances
Description
- Threaded neck type
- Thermal circuit breaker
- 1-pole
- Reset type
- Wide current range
- High breaking capacity
- Quick connect terminals 6.3 x 0.8 mm
Unique Selling Proposition
- Compact design
- Positively trip-free release
- Available with cover
- Different mounting possibilities
Applications
- Power supplies
- Uninterruptible power supply
- Power tools
- Household appliances
Weblinks
pdf data sheet, html datasheet, General Product Information, Distributor-
Stock-Check, Detailed request for product, Product News
Technical Data
Rated Voltage AC AC 240/277 VAC, see approbations
Rated Voltage DC 28 VDC
Rated current range AC 0.05 - 30 A
Conditional short circuit ca-
pacity
IEC: Inc, PC1, AC 240 V: 1 kA
Short circuit capacity Icn at In < 7 A/240 VAC : 8 x In
at In 7 A/240 VAC : 400 A
AC/DC 28 V : 400 A
Degree of Protection from front side IP40 acc. to IEC 60529
Dielectric Strength 50 Hz: 1.5 kV
Impulse 1.2/50 μs: > 2.5 kV
Insulation Resistance 500 VDC > 100 MΩ
Endurance typical 2 x Ir: 3000 switching cycles
Endurance minimum Reset type
AC : 2 x Ir , cos φ 0.6 :
DC : 2 x Ir , L/R = 2 - 3 ms :
50 switching cycles
Overload IEC: min. 40 trips
@ 6 x Ir, cos φ 0.6
UL / CSA: min. 50 trips
@ 1.5 x Ir, cos φ 0.75
Allowable Operation Temp. -5 °C to 60 °C
Vibration Resistance ± 1.5 mm @ 10 - 60 Hz
acc. to IEC 60068-2-6, test Fc
10 G @ 60 - 500 Hz
acc. to IEC 60068-2-6, test Fc
Shock Resistance 100 G / 6 ms
acc. to IEC 60068-2-27, test Ea
Tripping Type Thermal
Actuation Type Reset type
Weight ca. 10 g
Approvals and Compliances
Detailed information on product approvals, code requirements, usage instructions and detailed test conditions can be looked up in Details about
Approvals
SCHURTER products are designed for use in industrial environments. They have approvals from independent testing bodies according to national
and international standards. Products with specific characteristics and requirements such as required in the automotive sector according to IATF
16949, medical technology according to ISO 13485 or in the aerospace industry can be offered exclusively with customer-specific, individual agree-
ments by SCHURTER.
2
Thermal (T- and TA-Line)
T13-211 https://www.schurter.com /PG17_20
Circuit Breakers
Approvals
The approval mark is used by the testing authorities to certify compliance with the safety requirements placed on electronic products.
Approval Reference Type: T13
Approval Logo Certificates Certification Body Description
VDE Approvals VDE VDE Certificate Number: 123283
UL Approvals UL UL File Number: E71572
CSA Approvals CSA CSA Certification Record: LR 37712
CCC Approvals CCC CCC Certificate Number: 2012010307571195
Product standards
Product standards that are referenced
Organization Design Standard Description
Designed according to IEC 60934 Circuit-breakers for equipment (CBE)
Designed according to UL 1077 Standard for Supplementary Protectors for Use in Electrical Equipment
Designed according to CSA C22.2 No. 235 Supplementary Protectors
Designed according to GB 17701 Circuit-breaker for equipment
Application standards
Application standards where the product can be used
Organization Design Standard Description
Designed for applications acc. IEC/UL 60950 IEC 60950-1 includes the basic requirements for the safety of information
technology equipment.
Compliances
The product complies with following Guide Lines
Identification Details Initiator Description
CE declaration of conformity SCHURTER AG The CE marking declares that the product complies with the applicable
requirements laid down in the harmonisation of Community legislation on
its affixing in accordance with EU Regulation 765/2008.
RoHS SCHURTER AG Directive RoHS 2011/65/EU, Amendment (EU) 2015/836
China RoHS SCHURTER AG The law SJ / T 11363-2006 (China RoHS) has been in force since 1 March
2007. It is similar to the EU directive RoHS.
REACH SCHURTER AG On 1 June 2007, Regulation (EC) No 1907/2006 on the Registration,
Evaluation, Authorization and Restriction of Chemicals 1 (abbreviated as
"REACH") entered into force.
3
Thermal (T- and TA-Line) T13-211
https://www.schurter.com /PG17_20
Circuit Breakers
Dimension [mm]
T13-211
18.7
31 +0.4
-0.0
945 - 0.3 20
16
3/8-27UNS-2A
8
Ø5
11.5
12
Ø13
8.8
6.3
11.5
- 0.3
Ø 9.6
14
Diagrams
T13-...
1
2
4
Thermal (T- and TA-Line)
T13-211 https://www.schurter.com /PG17_20
Circuit Breakers
Approval Rated current Rated Voltage AC Rated Voltage DC
UL 1077 0.05...30 A 277 V 28 V
CSA C22.2 No. 235 0.05...30 A 277 V 28 V
EN 60934 0.05...30 A 240 V -
GB 17701 0.05...30 A 240 V -
Typical internal resistance
Rated Current [A] Internal Resistance []
0.05 376.500
0.50 4.40
1.00 1.10
2.00 0.31
3.00 0.14
4.00 0.068
5.00 0.048
6.00 0.033
8.00 0.026
9.00 0.0125
10.00 0.0125
11.00 0.0085
12.00 0.0085
13.00 0.0085
14.00 0.007
15.00 0.007
16.00 0.007
17.00 0.0047
18.00 0.0047
19.00 0.0047
20.00 0.004
21.00 0.0035
22.00 0.003
23.00 0.003
24.00 0.003
25.00 0.003
26.00 0.0022
27.00 0.002
28.00 0.002
29.00 0.002
30.00 0.002
5
Thermal (T- and TA-Line) T13-211
https://www.schurter.com /PG17_20
Circuit Breakers
Effect of ambient temperature
The units are calibrated for an ambient temperature of +23°C. To determine the rated cur-
rent for a lower or higher ambient temperature, use a correction factor (typical value) from
the table below:
Ambient Temperature [°C] Correction factor
-5 0.88
0 0.90
10 0.95
23 1.00
30 1.05
40 1.10
50 1.18
60 1.26
Example: Rated current = 5 A, Environmental temperature = 40 °C, --> Correction factor =
1.1, Resulting current = 5.5 A --> Fount to next higher rated current: 6 A
Time-Current-Curves
Time in Seconds
< 7,0 A
> 7,0 A
10'000
60
2`000
1`000
500
200
100
50
20
10
5
2
1
0,5
0, 3
0, 2
0,1
[ sec ][ min ]
10
5
1
30
20
1,05 10854321,32
Multiple of Rated Current In
Reference Temperature +23°
Config. Code
T13|-|1|2|3|B|-|1.23|
The characters are placeholders for the correspondingly keys of selections from the key tables.
T13|-| 1 |2|3|B|-|1.23| = Mounting
Mounting Configuration
key
Threaded neck type with knurled nut 2
T13|-|1| 2 |3|B|-|1.23| = Actuation Type
Actuation Type Configuration
key
Reset type 1
T13|-|1|2| 3 |B|-|1.23| = Terminal
Terminal Configuration
key
Quick connect terminal 6.3x0.8mm 1
T13|-|1|2|3| B |-|1.23| = Setting indication
Setting indication Configuration
key
Setting indication R
6
Thermal (T- and TA-Line)
T13-211 https://www.schurter.com /PG17_20
Circuit Breakers
T13|-|1|2|3|B|-| 1.23 | = Rated current
Rated current Configuration
key
0.05 A 0.05
0.1 A 0.1
0.15 A 0.15
0.2 A 0.2
0.3 A 0.3
0.4 A 0.4
0.5 A 0.5
0.6 A 0.6
0.7 A 0.7
0.8 A 0.8
0.9 A 0.9
1.0 1
1.1 A 1.1
1.2 A 1.2
1.3 A 1.3
1.4 A 1.4
1.5 A 1.5
1.6 A 1.6
1.7 A 1.7
1.8 A 1.8
1.9 A 1.9
2.0 A 2
2.1 A 2.1
2.3 A 2.3
2.5 A 2.5
2.8 A 2.8
3.0 A 3
3.3 A 3.3
Other rated currents on request
Rated current Configuration
key
3.5 A 3.5
4.0 A 4
4.5 A 4.5
5.0 A 5
5.5 A 5.5
6.0 6
6.5 A 6.5
7.0 A 7
7.5 A 7.5
8.0 A 8
8.5 A 8.5
9.0 A 9
9.5 A 9.5
10.0 A 10
11.0 A 11
12.0 A 12
13.0 A 13
14.0 A 14
15.0 A 15
16.0 A 16
17.0 A 17
18.0 A 18
19.0 A 19
20.0 A 20
22.0 A 22
25.0 A 25
28.0 A 28
30.0 A 30
Other rated currents on request
Variants
Rated current Setting indication Config. Code Order Number
15.0 A T13-211-15 4411.0007
20.0 A T13-211-20 4411.0010
30.0 A T13-211-30 4411.0017
18.0 A T13-211-18 4411.0019
25.0 A T13-211-25 4411.0073
30.0 A lT13-211R-30 4411.0221
Most Popular.
Availability for all products can be searched real-time:https://www.schurter.com/en/Stock-
Check/Stock-Check-SCHURTER
Packaging Unit 20 Pcs
7
Thermal (T- and TA-Line) T13-211
https://www.schurter.com /PG17_20
Circuit Breakers
Accessories
Description
T-Line Accessories
Accessories to T-Line
The specifications, descriptions and illustrations indicated in this document are based on current
information. All content is subject to modifications and amendments. Information furnished is believed
to be accurate and reliable. However, users should independently evaluate the suitability and test each
product selected for their own applications.
03.07.2019