Technical Data 1023 Effective October 2019
Supersedes October 2017
Low-Peak™ LP-CC Class CC 600 Vac/300 Vdc,
1/2-30 A time-delay fuses
Catalog symbol:
LP-CC-(amp)
Description:
Bussmann™ series Ultimate protection Low-Peak
Class CC current-limiting, time-delay fuses. Time-
delay – 12 seconds (minimum) at 200% of rated
current.
Specications:
Ratings
Volts
600 Vac
300 Vdc (1/2 to 2-8/10 A, 20-30 A)
150 Vdc (3-15 A)
Amps 1/2-30 A
IR
200 kA Vac RMS Sym.
20 kA Vdc
Agency information
UL® Listed Class CC, Std. 248-4,
Guide JDDZ, File E4273
CSA® Certified; Class 1422-02, File 53787
CE
RoHS compliant
Catalog numbers (amps)
LP-CC-1/2 LP-CC-1-1/2 LP-CC-3 LP-CC-6 LP-CC-12
LP-CC-6/10 LP-CC-1-6/10 LP-CC-3-2/10 LP-CC-6-1/4 LP-CC-15
LP-CC-8/10 LP-CC-1-8/10 LP-CC-3-1/2 LP-CC-7 LP-CC-20
LP-CC-1 LP-CC-2 LP-CC-4 LP-CC-7-1/2 LP-CC-25
LP-CC-1-1/8 LP-CC-2-1/4 LP-CC-4-1/2 LP-CC-8 LP-CC-30
LP-CC-1-1/4 LP-CC-2-1/2 LP-CC-5 LP-CC-9
LP-CC-1-4/10 LP-CC-2-8/10 LP-CC-5-6/10 LP-CC-10
Carton quantity:
Amp rating Carton qty.
1/2-30 10
Dimensions - in (mm)
Features:
200 kA interrupting rating complies with NEC®
Section 110.9 for today’s large capacity systems.
Fast short-circuit protection and dual-element,
time-delay performance provide ultimate
protection.
Reduces existing fuse inventory by up to 33%
when upgrading to Low-Peak fuses.
Consistent 2:1 amp rating ratios for all Low-
Peak fuses make selective coordination easy.
Time-delay characteristic avoids unwanted
fuse openings from surge currents while fast
response speed under fault conditions provides
a high degree of current limitation.
Current-limitation protects downstream
components against damaging thermal and
magnetic effects of fault currents.
A superior, all-purpose, space-saving branch
circuit fuse that meets most protection
requirements up to 30 A.
Very compact physical size that’s only 13/32” x
1-1/2” (10 x 38 mm) with rejction tip.
Proper sizing can provide “No DamageType 2
coordinated protection for NEMA and IEC motor
controllers.
Can be used where either a time-delay or a
fast-acting fuse is needed, making selection
easier and reducing spare fuse inventories for
substantial cost reduction.
Superior protection for small horsepower motor
circuits.
1.5 (38) 0.41 (10)
2
Technical Data 1023
Effective October 2019
Low-Peak™ LP-CC Class CC 600 Vac/300 Vdc, 1⁄2-30 A time-delay fuses
Eaton.com/bussmannseries
Recommended fuse blocks and holders:
Fuse amps 1-pole 2-pole 3-pole
Modular open blocks
up to 30 BCM603-1_ BCM603-2_ BCM603-3_
DIN-Rail holders
Up to 30
CHCC1D_ CHCC2D_ CHCC3D_
OPM-NG-_
OPM-1038_
OPM-1038_SW
Panel mount holders
Up to 30 HPS-RR
HPF-RR
In-line holders
Up to 30 HEY
HEZ
For additional information on Class CC fuse blocks and holders, see
data sheets:
Modular open blocks No. 10241 (BCM)
DIN-Rail holders No. 10430 (CHCC), No. 1109 (OPM-NG), No. 1102
(OPM-1038), No. 1103 (OPM-1038_SW)
Panel mount holders No. 2113 (HPS), No. 2114 (HPF)
In-line holders No. 2126 (HEY), No. 2130 (HEZ)
3
Technical Data 1023
Effective October 2019
Low-Peak™ LP-CC Class CC 600 Vac/300 Vdc, 1⁄2-30 A time-delay fuses
Eaton.com/bussmannseries
Time-current curves - average melt:
200
100
10
TIME IN SECONDS
1
0.1
0.01
1
3
4
6
8
10
12
15
20
25
30
AMP RATING
0.4
1
10
100
1000
CURRENT IN AMPS
1/2
6/10
8/10
1-1/4
3-1/2
4-1/2
Low-Peak™ LP-CC Class CC 600 Vac/300 Vdc, 1⁄2-30 A time-delay fusesTechnical Data 1023
Effective October 2019
Eaton, Bussmann and Low-Peak are valuable
trademarks of Eaton in the US and other
countries. You are not permitted to use
the Eaton trademarks without prior written
consent of Eaton.
UL is a registered trademark of the
Underwriters Laboratories, Inc.
CSA is a registered trademark of the Canadian
Standards Group.
NEC is a registered trademark of the National
Fire Protection Association, Inc.
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
Eaton.com
Bussmann Division
114 Old State Road
Ellisville, MO 63021
United States
Eaton.com/bussmannseries
© 2019 Eaton
All Rights Reserved
Publication No. 1023
October 2019
Follow us on social media to get the
latest product and support information.
The only controlled copy of this data sheet is the electronic read-only version located on the Eaton network drive. All other copies of this document are
by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the
end user with design applications. Eaton reserves the right, without notice, to change design or construction of any products and to discontinue or limit
distribution of any products. Eaton also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once
a product has been selected, it should be tested by the user in all possible applications.
Current-limitation curves:
B
A
Amp Rating
30
25
20
15
2-8/10
1-1/4
RMS SYMMETRICAL CURRENT IN AMPS
A-B = ASYMMETRICAL AVAILABLE PEAK (2.3 X SYM RMS AMPS)
INSTANTANEOUS PEAK-LET-THROUGH CURRENT IN AMPS
Current-limiting effects:
Prospective
S.C.C.
Let-through current
(apparent RMS symmetrical vs. fuse rating)
1-1/4 A 2-8/10 A 15 A 20 A 25 A 30 A
1000 100 135 240 305 380 435
3000 140 210 350 440 575 580
5000 165 255 420 570 690 710
10,000 210 340 540 700 870 1000
20,000 260 435 680 870 1090 1305
30,000 290 525 800 1030 1300 1520
40,000 315 610 870 115 0 1390 1700
50,000 340 650 915 1215 1520 1820
60,000 350 735 1050 1300 1650 1980
80,000 390 785 113 0 1500 1780 2180
100,000 420 830 1210 1600 2000 2400
200,000 525 110 0 1600 2000 2520 3050
NOTE: To calculate Ip (Ipeak) multiply IRMS value by 2.3.