Product leaflet
Single phase electricity meters A41 and A42
EQ meters in Bronze version from ABB
The compact and versatile EQ meters A41 and A42 are
single phase meters with full four quadrants measuring
meaning both active/reactive energy measurements and
import/export of energy. They can be used in most of
the common applications for reliable and trustworthy
metering of energy usage.
EQ meters A41 and A42 in Bronze version can be used
in stand-alone applications or metering network instal-
lations with the option of inbuilt M-Bus or Modbus.
General features
The A series meters are ideal for many applications and
installations. The meters support a wide voltage range as well
as a wide temperature range. The display is pixel-oriented
and can display up to four quantities at the same time.
Navigating the meter is easily done via the push-buttons
below the display. To configure the meter settings, the set
button must be accessed and this button is protected against
unauthorized use when the transparent lid on the front of the
meter is closed and sealed. The power consumption of the
meter is very low, less than 0.8 VA, makes them economical
in the long run - an important feature especially for large
meter populations.
Communication
Data from A41 and A42 in Bronze version can be collected
via pulse output or serial communication. The meters are
equipped with a transistor output for 5-40 VDC external
supply. It can be used for pulses proportionally to the mea-
sured energy or various alarms. The meters are also available
with built-in serial communication interfaces for Modbus RTU
(RS-485) or M-Bus as options.
Import and export measurements
B21 Bronze version measures the energy flowing both in (im-
ported) and out (exported) through the meter and saves the
energy in separate registers.
Approvals
The A41 and A42 meters are type approved according to IEC
as well as type approved and verified according to MID. MID
is the Measure Instruments Directive 2004/22/EC from Euro-
pean Commission. The type approval is according to stan-
dards that covers all relevant technical aspects of the meter.
These include climate conditions, electromagnetic compatibility
(EMC), electrical requirements, mechanical requirements and
accuracy.
Instrumentation
The A41 and A42 meters in Bronze version support reading of
instrument values.
A large number of electrical properties can be read.
Active power - Total and per phase
Reactive power - Total and per phase
Apparent power - Total and per phase
Current
Voltage
Power factor
Frequency
Ordering details
80 A direct connected, 4 DIN
Voltage V Communication Type Order code Weight
1 pc
Bronze
Active and reactive energy, import/export, pulse output, class B (Cl. 1), reactive Cl.2.
57.7...288 V AC RS-485 A41 212 - 100
2CMA170501R1000
0.23
6 A transformer CTVT connected, 4 DIN
Voltage V Communication Type Order code Weight
1 pc
Bronze
Active and reactive energy, import/export, pulse output, class B (Cl. 1), reactive Cl.2.
57.7...288 V AC RS-485 A42 212 - 100
2CMA170511R1000
0.20
dards that covers all relevant technical aspects of the meter.
These include climate conditions, electromagnetic compatibility
Product leaflet 2CMC484001L0201. Rev. A, October 2014. Prod. ABB AB, Low Voltage Products
A series
Technical data
A41 A42
Voltage/current inputs
Nominal voltage 230 V AC
Voltage range 57.7 ... 288 VAC (-20% - +15%)
Power dissipation voltage circuits 0.8 VA (0.8 W) total
Power dissipation current circuits 0.007 VA (0.007 W) at 230 V AC and Ib 0.001 VA (0.001 W) at 230 V AC and Ib
Base current Ib5 A -
Rated current In-1 A
Reference current Iref 5 A -
Transitional current Itr 0.5 A 0.05 A
Maximum current Imax 80 A 6 A
Minimum current Imin 0.25 A 0.02 A
Starting current Ist < 20 mA < 1 mA
Terminal wire area 1 - 25 mm20.5 - 10 mm2
Recommended tightening torque 3 Nm 1.5 Nm
Communication
Terminal wire area 0.5 - 1 mm2
Recommended tightening torque 0.25 Nm
Transformer ratios
Configurable current ratio (VT) -1/999 - 999999/1
Configurable current ratio (CT) -1/9 - 9999/1
Pulse indicator (LED)
Pulse frequency 1000 imp/kWh 5000 imp/kWh
Pulse length 40 ms
General data
Frequency 50 or 60 Hz ± 5%
Accuracy Class B (Cl. 1) and reactive Cl. 2 B (Cl. 1), C (Cl. 0.5 S) or reactive Cl. 2
Active energy 1% 0.5 %, 1%
Display of energy Pixel oriented
Environmental
Operating temperature -40°C - +70°C
Storage temperature -40°C - +85°C
Humidity 75% yearly average, 95% on 30 days/year
Resistance to fire and heat Terminal 960 °C, cover 650°C (IEC 60695-2-1)
Resistance to water and dust IP20 on terminal block without protective enclosure and IP51 in protective enclosure,
according to IEC 60529.
Mechanical environment Class M2 in accordance with the Measuring Instrument Directive (MID). (2004/22/EC).
Electromagnetic environment Class E2 in accordance with the Measuring Instrument Directive (MID), (2004/22/EC).
Outputs
Current 2 - 100 mA
Voltage 5 - 240 V AC/DC. For meters with only 1 output, 5 - 40 V DC.
Pulse output frequency Programmable: 1 - 999999 imp/kWh
Pulse length Programmable: 10 - 990 ms
Terminal wire area 0.5 - 1 mm2
Recommended tightening torque 0.25 Nm
EMC compatibility
Impulse voltage test 6 kV 1.2/50μs (IEC 60060-1)
Surge voltage test 4 kV 1.2/50μs (IEC 61000-4-5)
Fast transient burst test 4 kV (IEC 61000-4-4)
Immunity to electromagnetic HF-fields
80 MHz - 2 GHz at 10 V/m (IEC 61000-4-3)
Immunity to conducted disturbance 150 kHz - 80 MHz (IEC 61000-4-6)
Immunity to disturbance with harmonics 2 kHz - 150 kHz
Radio frequency emission EN 55022, class B (CISPR22)
Electrostatic discharge 15 kV (IEC 61000-4-2)
Standards
IEC 62052-11, IEC 62053-21 class 1& 2, IEC 62053-22 class 0.5 S, IEC 62053-23 class
2, IEC 62054-21, GB/T 17215.211-2006, GB/T 17215.321-2008 class 1 & 2,
GB/T
17215.322-2008, EN 50470-1, EN 50470-3 category A, B and C.
Mechanical
Material Polycarbonate in transparent front glass, bottom case, upper case and terminal cover.
Glass reinforced polycarbonate in polycarbonate in terminal cover.
Dimensions
Width 70 mm
Height 97 mm
Depth 65 mm
DIN modules 4
© Copyright 2014 ABB. All rights reserved.
Specication subject to change without notice.
To get more information, install QR code
reader on your mobile device, scan the
code and see more.
ABB AB
Meters
Low Voltage Products
Box 1005
S-61129 Nyköping, Sweden
Phone +46 155 29 50 00
www.abb.com/lowvoltage
A41
Wiring diagram
A42
34
L
N
16
3 5
L1
N
1 2
P1
P1 P2
S1 S2
Dimensions
89
93
45
97
43
58
65
70