Connection technology
Most of our relay couplers are available with
screw or tension clamp connections.
Relay coupler
K.2
K
Relay coupler – overview
Weidmüller relay modules have a universal foot structure so
that they can be fitted in rows on the TS 32, TS 35 x 7.5 and
TX 35 x 15 mounting rails acc. to EN 50 035 and EN 50 022.
In the coil circuit of the relay modules, an LED status indication
shows the switching state of the relay.
Our highlight:
MICROSERIES Coupler modules in terminal format
Holding and ejecting mechanism
The innovative holding and eject mechanism clips
the assembled module securely onto the basic
terminal. With the reliable eject function, the
coupler can be removed quickly and simply from
the base.
The slot-in width of 6.1 mm allows for space-saving installation of the
MICROSERIES relays in a wide range of applications. The MICROSERIES is partic-
ularly suitable for the modification and extension of installations and machinery. In
such cases, it helps to make optimum use of the limited space available in switchgear
cabinets.
Pluggable cross-connectors
The ZQV 4N plug-in cross-connectors are
available in various colours and with different
numbers of poles. They allow for reliable and
distinct cross-connections between the four
input and output potentials.
Relay and optocoupler module
Plug-in relay and optocoupler modules allow for
individual adjustment of the module functions.
Relay couplers are available with different power
outputs with either AgSnO and gold contacts.
Marking
The tab surfaces enable equipment to be clearly
marked using a WS marker.
SSB_K001-K007_GB 24.10.2003 11:57 Uhr Seite K.2
Relay coupler
K.3
K
Relay coupler – overview
Contact types Protective circuits for the contacts Switching small and large capacities
Contact material
Several contact types and combinations
are available ex stock:
1 NCC (EGR EG7, RS 30)
1 NOC (EGR RG7, DKR, RS 30)
1 NCC and
1 NOC (WRS)
2 NOCs (WRS)
3 NOCs (WRS)
1 change-over contact
(EGR/RST EG7, WRS,
DKR, PRS/PRZ MCZ R,
RS 30, RS 31)
2 change-over contacts
(WRS, RS 32, PRS/PRZ)
4/8/16 change-over contacts
(RSM)
The relay modules are suitable for univer-
sal use, with the choice of contact materi-
al the crucial criterion. The contact is
used for safe transmission of control sig-
nals and also for switching power contac-
tors.
Gold-plated or gold-flashed AgNi con-
tacts are used for most applications. Hard
gold plated contacts with gold plating
exceeding 2 µm in thickness allow even
extremely small capacities (up to 40 µW)
to be switched. AgSnO2 or AgCdO con-
tacts are used for switching higher capac-
ities (RS 31).
The switching of inductive or capacitive
loads produces switching sparks which
can influence the electrical service life of
the relays.
The following protective circuits for the
contacts reduce contact wear:
Diode
Diode and Z-diode
RC combination
Varistor
U
D
L
oad
+
U
S
12
U
ZD
L
oad
+
U
S
12
U
R
C
L
oad
+
(
~
)
(
~
)
R
C
U
S
12
U
VDR
L
oad
+
(
~
)
(
~
)
VDR
U
S
12
Advantage: Can be used for all capacities,
low overvoltage, minimum
space required, low price
Disadvantage: Very large release delay
Advantage: Low overvoltage (defined by
Z-diode), low release delay
Disadvantage: Cannot be used for large
capacities
Advantage: Low overvoltage, low release
delay
Disadvantage: High current load on the con-
tacts when switching on;
more complicated and expen-
sive at greater capacities
Advantage: Low release delay, low price
Disadvantage: Cannot be used for all operat-
ing voltages and capacities
USVoltage progression
1 Closing
2 Opening
For automation technology, the EGR EG7
relay coupler is ideal for switching
extremely small capacities (up to 40 µw)
under ohmic load. The signals are reliably
transmitted to the controllers. The switch-
ing of large capacities for energy and
supply technology is achieved by the
RS31 relay coupler, with a guaranteed
switching capacity of 3.5 kVA under
ohmic load.
Switching times of the relay modules
Typical pick-up delay < 10 ms
Typical release delay < 12 ms
Contact service life under ohmic load
DC load-limit curve under ohmic load
Reduction factor under inductive load
cos ¥ < 1
No. of cycles eff. = No. of cycles at (cos ¥ = 1)
x red. factor F
Single contact
Number of operations
Switching capacity (kVA)
Direct current (A)
Direct voltage (V)
Reduction factor F
Power factor (cos )
SSB_K001-K007_GB 24.10.2003 11:57 Uhr Seite K.3
Relay coupler
K.4
K
Relay couplers with plugged relay have
only limited suitability for use in a highly
oscillating environment. Preference should
be given to relay couplers with soldered
relays.
The transition resistance of the relay con-
tacts is a key factor contributing to tem-
perature increase inside the relay mod-
ules. This relationship is illustrated by a
derating curve, defined as the function of
the permissible current plotted against the
ambient temperature.
The permissible current (Curve a) is deter-
mined for the following operating condi-
tions:
Continuous operation
Rated input voltage + 10 percent
Several relay modules working under
load, mounted horizontally in rows on
mounting rail, without any spacing
If the modules are mounted with a spac-
ing > 20 mm, this results in a higher cur-
rent load (Curve b). Curve b also shows
the maximum values for switching or
short-time operation in horizontally
mounted state.
The key data of the triggering device must
be precisely adhered to when using UC
versions in DC circuits. As a result of their
pre-circuitry, UC versions take up larger
quantities of current. The internal current
limit of standard initiators can mean that
the triggered relay couplers are not
switched through.
Relay couplers with 24 V AC/DC input are
not suitable for triggering by initiators;
purely DC versions are recommended for
these applications.
Relay coupler – overview
Relay coupler with plugged relay Derating curve Notes on application
Long leads are subject to greater electri-
cal and electromechanical influences. This
may cause malfunctions and even failure
of the relay modules. One possible reme-
dy is to insert an RC combination to filter
out the interference. RC combinations are
available for all common relay couplers,
as pluggable (PLUGSERIES) solutions or
WDU 12C and DKU 12C terminals.
RC combination
SSB_K001-K007_GB 24.10.2003 11:57 Uhr Seite K.4
Relay coupler
K.5
K
Protective separation
All equipment guaranteeing protective
separation is to be designed so that any
faults (e.g. mechanical faults) cannot
affect the insulation. If a mechanical fault
occurs in a relay (bent soldering post,
broken winding wire or broken spring),
protective separation must also be guar-
anteed in such cases.
Relays are specified and tested to
IEC 255 and VDE 0435. Neither standard
makes reference to EN 50 178 (electronic
equipment for use in high current installa-
tions), nor do they contain a definition of
protective separation. Furthermore,
other measuring conditions are used as
the basis for the test voltages stated for
the relays. So the test voltages cannot be
transferred to EN 50 178 or
DIN VDE 0106 part 101. In view of the
fact that users are increasingly turning to
equipment which guarantees protective
separation, many relay manufacturers
now refer to DIN VDE 0106 and test their
products accordingly. The stated values
then correspond with protective separa-
tion.
Standards
The following standards are fulfilled:
EN 50 178:
Electronic equipment for use in high
current installations
DIN VDE 01206 part 101:
Protection from dangerous body cur-
rents, basic requirements for protec-
tive separation in electrical equipment
IEC 255, DIN VDE 0109:
Insulation coordination for equipment
within low-voltage systems, including
clearance and creepage distances for
configured printed circuit boards
DIN VDE 0435:
Electrical relays, switching relays
Definition of the technical data
Input curcuit
Rated voltage [V] Reference voltage at which the relay coupler works
Typical input voltage
=> 5 Vdc, 12, 24, 48, 60, 115, 230 ac/dc
Rated current [mA] Quotient of input voltage and input resistance
Input resistance => coil resistance + resistance of the triggering
device (R; LED; GL, )
Nominal consumption [W/VA] Input voltage x input current dc/ac
with tolerance +/-10% or +5/-15%
typical range for relay coupler
250 mW > Pv > 1 W 0.4 VA > Pv > 1.2 VA
Operating voltage [V] Smallest input current needed for the relay coupler to respond
(Tu = 293 K)
Pull-in current [mA] Smallest input current at which the relay switches from idle to
working position
(Tu = 293 K)
Response power [W/VA] Product of operating voltage and pull-incurrent
Drop-out voltage [V] Voltage at which the relay reliably drops away
Release current [mA] Input current at which the relay reliably drops away
Output circuit
Max. switching voltage [V] Max. voltage allowed at the relay contact
Switch-on current [A] Current allowed to flow for max. 4 seconds after the relay con-
tact closes
Continuous current [A] Current allowed to flow constantly after the contact closes
Switching power [W/VA] Product of output voltage and switch-on current, under ohmic,
inductive or capacitive load
Min. switching power [µW] Smallest power to be switched via the contact
Service life No. of switching cycles until the contact fails
mechanical => without electric load
electrical => under ohmic or inductive ac/dc load
Response time [ms] Time from closing the exciter voltage until the contact
closes/opens
Release time [ms] Time from opening the exciter voltage until the contact
closes/opens
Switching frequency [Hz] Switching circuits/sec. in pulse duty factor 1:2 (ton = toff)
Voltage strength [kV] Max. test voltage between input and output circuit which does
not cause a discharge
Protective separation Relay coupler acc. to EN 50178 or VDE 0106 part 101
Light arc Flow of current on opening contacts, caused by ionisation
Contact wear The switching of inductivity causes extensive material migration
Results:
=> Scratches and tip formation on contact surfaces
=> Failure caused by contacts interlocking
Spark extinction Limitation of transient overvoltage by switching
the inductive load:
=> RC combinations
=> Z-diodes / suppressor diodes
=> varistors
Reduction factor Factor by which the service life is reduced when switching induc-
tive loads
Relay coupler – overview
SSB_K001-K007_GB 24.10.2003 11:57 Uhr Seite K.5
Relay coupler
K.6
K
Enclosure types for relay couplers
PLUGSERIES
The modular component system repre-
sents a new generation of pluggable relay
couplers. The key element is an innova-
tive relay base designated PXS (screw
clamp) or PXZ (tension clamp). Both
products reflect the functionality of relays
and terminals, and experience gained
from their commercial use. PLUGRELAY
is the ideal connection system between
the relay and the application.
Modular principle
The new PLUGSERIES is extremely easy
to handle. Commercially available relays
are simply plugged in, retaining clips pro-
vide a firm hold, and LED displays with a
freewheel diode can be plugged in.
Relays simply plugged in: suitable for
miniature circuit of both standard and
RT designs
Independent connection technology:
screw connection or tension spring
technology, nominal cross-sectional
area 0.5 2.5 mm2
Robust design of the retaining clip
One or two change-over contacts;
max. switching current 16 A
Minimum wiring workload thanks to
ZQV 2.5N pluggable cross-connectors
Modular system makes for easy han-
dling:
Relay base, LED display, retaining
hook and relay
Clips on to TS 35
Marking with WS tabs on retaining
hook
Pluggable LED with freewheel diode.
MICROSERIES
Relay and optocoupler versions in the
MICROSERIES are used in industrial
automation applications for separating
and coupling digital input and output sig-
nals. The compact design makes them
perfectly suited for use in sub-distributors
or switch cabinets. With its compact
shape, MICROSERIES combines the
functions of the classical coupling level
with the terminal level.
Slot-in width 6.1 mm
Pluggable cross-connection for four
input and output potentials
Tried and tested ZQV 4N
cross-connection system
Wide range of input voltage
from 5 .. 230 V
LED status display, reverse polarity
protection diode, recovery diode
Enclosure material WEMID (com-
bustibility V0 acc. to UL 94)
Innovative holding and ejecting
mechanism
Marking surface to take standard
marking WS 12/6
CE marking
Weidmüller's relay couplers carry the CE
mark and comply with the requirements
laid down by EN 50 081 part 1 and
EN 50 082 part 2. They can be used in
both in a wide range of applications and
industries
Suitable ESD measures must be taken
during installation. Overvoltage protection
must be provided for long leads as pro-
tection from lightning.
WAVESERIES
Innovative electronic components require
an enclosure or housing which reflects
their specific functions. It must allow for
adjusting and control functions and sup-
port technical requirements, such as heat
dissipation or electromagnetic compatibili-
ty. A compact design saves space in the
switch cabinet and reduces assembly
costs. Ergonomic design is increasingly
important for top quality relay coupler
interfaces.
The WAVEBOX fulfils all these criteria,
with outstanding features including:
Assembly without tools
Pluggable circuit board
ZQV 2.5V pluggable cross-connector
Hinged transparent cover
Marking with WS tabs
Clips onto TS 35
Connection systems
The user can choose between BLZ screw plug-in
connectors and BLZF tension clamp plug-in sys-
tems, up to 2.5 mm2and finely stranded, for the
greatest possible flexibility when wiring up the cir-
cuits.
Printed circuit board
If the lateral locking hook is squeezed on the head
end, it can be pulled out of the enclosure together
with the connection level and the circuit board.
The circuit board can only be pulled out without
current voltage.
Cross-connector
The ZQV 2.5 N/2 cross-connectors can be used
to connect rows of Wavebox housings in the lower
part of the enclosure. The cross-connector can
take up to 8 A of current. It can be used for bridg-
ing the supply voltage from one electronic module
to another. The voltage at the cross-connector
must not exceed 50 V.
Ventilation slits
Diagonal ventilation slits ventilate the lower parts
of the enclosures and keep temperatures moder-
ate.
Relay coupler – overview
SSB_K001-K007_GB 24.10.2003 11:57 Uhr Seite K.6
Relay coupler
K.7
K
Enclosure types for relay couplers
EG SERIES
The EG7 integral enclosure has a special
status because it is only suited for the
installation of 10 mm narrow relay cou-
plers. EG7 clip-in base can be mounted
on either the TS 32 or TS 35. An RS EG7
snap-in base is also available for the RST
plug-in relay couplers.
The closed EG 7 enclosures are equipped
with screw connections.
Conductors with the following cross-sec-
tional areas can be connected:
Integral enclosure EG 7:
0.5 1.5 mm2
Change-over contact RST:
0.5 2.5 mm2.
RS SERIES
Clip-in bases with relay RS 30, 31, 32
have a width of 11.2 mm to 25 mm,
depending on the type. The open snap-in
profile means that relay couplers can be
designed for plugging in. The modules on
the snap-in base have screw clamp units
or flat plug-in connections for connection
to the conductor. The following conduc-
tors can be connected:
Solid: 0.54 mm2,
Flexible: 0.52.5 mm2.
Snap-in base with multiple interface
RSM multiple interfaces are assembled
with a choice of 4, 8 or 16 relays.
Versions with a joint plus or minus poten-
tial are available to save wiring on the
input side. LP connection elements are
equipped screw connections and are suit-
able for connecting the following conduc-
tor cross-sectional areas:
Solid: 0.54 mm2,
Flexible: 0.52.5 mm2.
Variations on the RSM coupler have pre-
fabricated male connectors acc. to
IEC 603-1/DIN 41 651.
DK SERIES
All components in the DKR mini-coupler
are extremely narrow: use of advanced
surface-mounted parts (SMD) allows the
width to be kept to just 6 mm. The range
includes 4 or 5 screw connections for
conductor cross-sectional areas of
0.5 4 mm2. The mini couplers offer a
wide range of applications for coupling
digital sensor/actuator signals with
automation devices and the process field.
DKR relay couplers can be used to pick
up and standardise signals from the field
with different voltages.
MCZ SERIES
The MCZ enclosure is only 6 mm wide
and one of the narrowest of its kind. Its
outstanding technical features include:
Tension clamp connection to reduce
assembly costs
Integrated input/output cross-connec-
tion to reduce wiring workload
MCZR mini-conditioners (relay couplers)
have 4 or 5 tension clamp connections.
The cross-sectional area of the clamping
conductor is 0.5 1.5 mm2.
Relay coupler – overview
SSB_K001-K007_GB 24.10.2003 11:58 Uhr Seite K.7
K
Relay coupler
PLUGSERIES
1 change-over contact
Construction kit consists of
• Relay-socket for mounting-rail
• LED-indicator / RC-combination
• Retaining bracket
• Pluggable relay
Cross-connection of the coil connections
and change-over contacts of the relay with
pluggable cross-connection ZQV 2.5N
D
C
versio
n
A2
A
1
14
A
2
A
1
14 12
12
A
C
versio
n
Output
Max. switching voltage AC/Continuous current 250V/10A
Min. switching power 10V/100mA
Response time / Release time 5.8ms/6.9ms
Contact base material AgNi 90/10
Mechanical endurance 30x10^6 switching cycles
Max. switching frequency at rated load 0.1Hz
Rated data
Status indicator/Free wheel diode/Reverse volt. prot. LED green/Yes/not available
Ambient temp., fitted w. distance -25 °C…+50 °C
Storage temperature -40 °C…+50 °C
Climate 40°C/93% rel. humidity without condensation
Approvals CE, cURus
Insulation coordinates (EN 50 178)
Standards EN 50178
Rated voltage 250V
Impulse withstand voltage 6 kV
Creepage and clearance path input - output >8mm
Overvoltage category III
Pollution severity 2
Secure separation acc. to VDE 0106 Part 101 Yes
Dimensions Screw connection Tension clamp connection
Clamping range (rating- / min. / max.) mm22.5 / 0.5 / 2.5 2.5 / 0.5 / 2.5
Length x width x height mm 92.0 / 15.3 / 95.0 92.0 / 15.3 / 87.0
Information
resistive Load
Max. DC load breaking capacity
DC current [A]
DC voltage [Vdc]
...
Electricial life
Operations
DC-coile
AC-coile
250Vac
resistive load
Switching current [A]
12/16A
Coil operating range DC
Coil operating range AC
Coil voltage (U/Un)
Un nominal coil voltage
Ambient temperature [°C]
Ambient temperature [°C]
Coil voltage (U/Un)
Un nominal coil voltage
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
Applications
SSB_K008-K059 25.10.2003 11:14 Uhr Seite K.8
K
Relay coupler
PLUGSERIES
1 change-over contact
Ordering data
Input
Rated voltage
Rated current AC
Rated current DC
Power rating
Oper.-/drop-out volt. AC-coil
Oper.-/drop-out volt. DC-coil
Pull-in curr./release curr. AC-coil
Pull-in curr./release curr. DC-coil
Ordering data
Complete module
Screw connection Type
Order No.
Tension clamp connection Type
Order No.
Ordering data
Spare relay, pluggable
Type
Order No.
Information
12VDC 1CO
12 Vdc +/- 20 %
33mA
400mW
8.4V/1.2V
PRS 12Vdc LD 1CO
8536471001
PRZ 12Vdc LD 1CO
8536571001
RCL 314012 12Vdc-Rel1U
4058470000
24VDC 1CO
24 Vdc +/- 10 %
16mA
400mW
16.8 V / 2.4 V
PRS 24Vdc LD 1CO
8530621001
PRZ 24Vdc LD 1CO
8530691001
RCL 314024 24Vdc-Rel1U
4058480000
115VDC 1CO
115 Vdc +/- 10 %
3.5mA
400mW
76 V / 11 V
PRS 115Vdc LD 1CO
8536510000
PRZ 115Vdc LD 1CO
8536610000
RCL 314110 110Vdc-Rel1U
4058500000
24VAC 1CO
24 Vac +/- 10 %
32mA
0.75VA
17V/3.6V
PRS 24Vac LD 1CO
8536530000
PRZ 24Vac LD 1CO
8536651001
RCL 315524 24Vac-Rel1U
4058510000
Ordering data
Input
Rated voltage
Rated current AC
Rated current DC
Power rating
Oper.-/drop-out volt. AC-coil
Oper.-/drop-out volt. DC-coil
Pull-in curr./release curr. AC-coil
Pull-in curr./release curr. DC-coil
Ordering data
Complete module
Screw connection Type
Order No.
Tension clamp connection Type
Order No.
Ordering data
Spare relay, pluggable
Type
Order No.
Information
120VAC 1CO
120 Vac +/- 10 %
6.6mA
0.75VA
86.3V/17.3V
PRS 120Vac LD 1CO
8530641001
PRZ 120Vac LD 1CO
8530710000
RCL 314615 115Vac-Rel1U
4058520000
230VAC 1CO
230 Vac +/- 10 %
3.2mA
0.75VA
171 V / 34 V
PRS 230Vac LD 1CO
8530671001
PRZ 230Vac LD 1CO
8530731001
RCL 314730 230Vac-Rel1U
4058540000
SSB_K008-K059 25.10.2003 11:14 Uhr Seite K.9
K
Relay coupler
PLUGSERIES
2 change-over contacts
Construction kit consists of
Relay-socket for mounting-rail
LED-indicator / RC-combination
Retaining bracket
Pluggable relay
Cross-connection of the coil connections
and change-over contacts of the relay with
pluggable cross-connection ZQV 2.5N
D
C
versio
n
A
C
versio
n
A2
A
1
14
21
24
12
11
22
A2
A
1
14
21
24
12
11
22
Output
Max. switching voltage AC/Continuous current 250V/10A
Min. switching power 10V/100mA
Response time / Release time 9ms/45ms
Contact base material AgNi 90/10
Mechanical endurance 5x10^6 switching cycles
Max. switching frequency at rated load 0.1Hz
Rated data
Status indicator/Free wheel diode/Reverse volt. prot. LED green/No/
Ambient temp., fitted w. distance -40 °C+50 °C
Storage temperature -40 °C+50 °C
Climate 40°C/93% rel. humidity without condensation
Approvals CE, cURus
Insulation coordinates (EN 50 178)
Standards EN 50178
Rated voltage 250V
Impulse withstand voltage 6 kV
Creepage and clearance path input - output >8mm
Overvoltage category III
Pollution severity 2
Secure separation acc. to VDE 0106 Part 101 Yes
Dimensions Screw connection Tension clamp connection
Clamping range (rating- / min. / max.) mm22.5 / 0.5 / 2.5 2.5 / 0.5 / 2.5
Length x width x height mm 92.0 / 15.3 / 95.0 92.0 / 15.3 / 87.0
Information
Max. DC load breaking capacity
2-pole
resistive load
2 contacts in series
1 contact
DC voltage [Vdc]
DC current [A]
...
Electrical life
Operations
Switching current [A]
250Vac
resistive load
DC-coil
AC-coil
Coil operating range DC
Coil voltage (U/Un)
Ambient temperature [C°]
.
.
.
.
.
.
.
Un nominal coil voltage
Un nominal coil voltage
Ambient temperature [C°]
Coil voltage (U/Un)
.
.
.
.
.
.
.
.
.
Coil operating range AC
Applications
SSB_K008-K059 25.10.2003 11:14 Uhr Seite K.10
K
Relay coupler
PLUGSERIES
2 change-over contacts
Ordering data
Input
Rated voltage
Rated current AC
Rated current DC
Power rating
Oper.-/drop-out volt. AC-coil
Oper.-/drop-out volt. DC-coil
Pull-in curr./release curr. AC-coil
Pull-in curr./release curr. DC-coil
Ordering data
Complete module
Screw connection Type
Order No.
Tension clamp connection Type
Order No.
Ordering data
Spare relay, pluggable
Type
Order No.
Information
12VDC 2CO
12 Vdc +/- 20 %
33mA
400mW
8.4 V / 1.2 V
PRS 12Vdc LD 2CO
8536501001
PRZ 12Vdc LD 2CO
8536591001
RCL 424012 12Vdc-Rel2U
4058560000
24VDC 2CO
24 Vdc +/- 10 %
16mA
400mW
16.8 V / 2.4 V
PRS 24Vdc LD 2CO
8530631001
PRZ 24Vdc LD 2CO
8530701001
RCL 424024 24Vdc-Rel2U
4058570000
115VDC 2CO
115 Vdc +/- 10 %
3.5mA
400mW
76 V / 11 V
PRS 115Vdc LD 2CO
8536520000
PRZ 115Vdc LD 2CO
8536630000
RCL 424110 110Vdc-Rel2U
4058590000
24VAC 2CO
24 Vac +/- 10 %
32mA
0.75VA
17V/3.6V
PRS 24Vac LD 2CO
8536560000
PRZ 24Vac LD 2CO
8536681001
RCL 424524 24Vac-Rel2U
4058600000
Ordering data
Input
Rated voltage
Rated current AC
Rated current DC
Power rating
Oper.-/drop-out volt. AC-coil
Oper.-/drop-out volt. DC-coil
Pull-in curr./release curr. AC-coil
Pull-in curr./release curr. DC-coil
Ordering data
Complete module
Screw connection Type
Order No.
Tension clamp connection Type
Order No.
Ordering data
Spare relay, pluggable
Type
Order No.
Information
120VAC 2CO
120 Vac +/- 10 %
6.6mA
0.75VA
86.3V/17.3V
PRS 120Vac LD 2CO
8530661001
PRZ 120Vac LD 2CO
8530720000
RCL 424615 115Vac-Rel2U
4058610000
230VAC 2CO
230 Vac +/- 10 %
3.2mA
0.75VA
172.5V/34.5V
PRS 230Vac LD 2CO
8530681001
PRZ 230Vac LD 2CO
8530741001
RCL 424730 230Vac-Rel2U
4058630000
SSB_K008-K059 25.10.2003 11:14 Uhr Seite K.11
K
Relay coupler
PLUGSERIES
2 change-over contacts with gold-plated con-
tacts
Construction kit consists of
Relay-socket for mounting-rail
LED-indicator / RC-combination
Retaining bracket
Pluggable relay
Cross-connection of the coil connections
and change-over contacts of the relay with
pluggable cross-connection ZQV 2.5N
D
C
versio
n
A
C
versio
n
A2
A
1
14
21
24
12
11
22
A2
A
1
14
21
24
12
11
22
Output
Max. switching voltage AC/Continuous current 250V/10A
Min. switching power 5 V / 10 mA
Response time / Release time 9ms/45ms
Contact base material AgNi 90/10
Mechanical endurance 5x10^6 switching cycles
Max. switching frequency at rated load 0.1Hz
Rated data
Status indicator/Free wheel diode/Reverse volt. prot. LED green/No/
Ambient temp., fitted w. distance -40 °C+50 °C
Storage temperature -40 °C+50 °C
Climate 40°C/93% rel. humidity without condensation
Approvals CE, cURus
Insulation coordinates (EN 50 178)
Standards EN 50178
Rated voltage 250V
Impulse withstand voltage 6 kV
Creepage and clearance path input - output >8mm
Overvoltage category III
Pollution severity 2
Secure separation acc. to VDE 0106 Part 101 Yes
Dimensions Screw connection Tension clamp connection
Clamping range (rating- / min. / max.) mm22.5 / 0.5 / 2.5 2.5 / 0.5 / 2.5
Length x width x height mm 92.0 / 15.3 / 95.0 92.0 / 15.3 / 87.0
Information
Ordering data
Ordering data
Complete module
Screw connection Type
Order No.
Tension clamp connection Type
Order No.
Ordering data
Spare relay, pluggable
Type
Order No.
Input
Rated voltage
Rated current AC
Rated current DC
Power rating
Oper.-/drop-out volt. AC-coil
Oper.-/drop-out volt. DC-coil
Pull-in curr./release curr. AC-coil
Pull-in curr./release curr. DC-coil
Information
24VDC 2CO AU
24 Vdc +/- 10 %
16mA
400mW
16.8 V / 2.4 V
PRS 24VDC LD 2COAU
8561760000
PRZ 24Vdc LD 2CO AU
8552440000
RCL 425024 24Vdc-Rel2U
4058580000
120VAC 2CO AU
120 Vac +/- 10 %
6.6mA
0.75VA
86.3V/17.3V
PRS 120VAC LD 2CO AU
8595960000
PRZ 120VAC LD 2COAU
8575940000
RCL 425615 115Vac-Rel2U
4058620000
230VAC 2CO AU
230 Vac +/- 10 %
3.2mA
0.75VA
172.5V/34.5V
PRS 230VAC LD 2CO AU
8595990000
PRZ 230VAC LD 2COAU
8575950000
RCL 425730 230Vac-Rel2U
4058640000
SSB_K008-K059 25.10.2003 11:14 Uhr Seite K.12
Relay coupler
K.14
K
PLUGSERIES
Accessories
Empty base for assembly on mounting rail TS 35
Screw connection
Tension clamp connection
Retaining clip
LED display with freewheel diode
6 ... 24 Vdc
LED red, 6 ... 24 Vdc
48 ... 60 Vdc
115 Vdc
12 ... 24 Vac
115 Vac
230 Vac
LED red, 230 Vac
RC combination 120...230 VAC/DC
Plug-in cross-connectors
2-pole Black
Red
Blue
Marking
10 x 5 mm
15 x 5 mm
Order data
Type Qty Order no.
PXS35 10 8533771001
PXZ35 10 8536691001
PRC 100 8536700000
PLED 24 Vdc 20 8536710000
PLED 24 Vdc rot 20 8611010000
PLED 48 Vdc 20 8536720000
PLED 115 Vdc 20 8536730000
PLED 24 Vac 20 8536750000
PLED 120 Vac 20 8536760000
PLED 230 Vac 20 8536780000
PLED 230 Vac rot 20 8611000000
PLRC 200 nF/20020 8566530000
ZQV 2.5N/4-2SW 60 1784270000
ZQV 2.5N/4-2RT 60 1784280000
ZQV 2.5N/4-2BL 60 1784290000
WS 10/5 200 1060860000
WS 15/5 96 1609880000
Empty base
Rated current
Rated voltage
Voltage resistance coil / contacts
Protection
Nominal cross-sectional area
Stripping length Screw connection
Tension clamp connection
Ambient temperature
Flammability acc. to UL 94
16 A
250 V
> 4 kV
IP 20
2,5 mm2
8 mm
10 mm
–40°C ... +60°C
V-0
Technical data
92
87
87 (PXZ35)
95 (PXS35) Cross-connection channel
A1 / A2
Cross-connection channel
11 / 21
Marking field
Retaining clip
92
Relay for high switch-on current
Schrack RP3SL
15,3
15.3
A2 A2
A1
(COIL) A1
(COIL)
24 2414
(NO)
21 2111
(COM) 11
(COM)
22 2212
(NC) 12
(NC)
15.3
DC version
AC version
Tension clamp
connection Screw
connection
A2
A
114
21
24
12
11
22
A2
A
114
21
24
12
11
22
Operating control display
*free wheel
diode
*
14
(NO)
SSB_K014-K019_GB 24.10.2003 12:53 Uhr Seite K.14
Pluggable relay
24 Vdc 1 NOC
Type Qty Order no.
RP3SL 24 Vdc 1NO 20 8588510000
Relay coupler
K.15
K
PLUGSERIES
Relay on plug-in base
No. and type of contacts
Contact material
Switching current
Peak switch-on current
Switching voltage
Switching power
Min. switching current / switching power
Nominal consumption
Voltage strength / contact
Operating voltage / release time: DC coil
Bounce time NCC / NOC
Mechanical service life DC coil
Other data
Protection class
Ambient temperature DC coil
Weight
Approvals
Contact service life Load
12 A, 250 V~, cosϕ=1
TV 8
2500 W, 230 V~,
Halogen lamps
1000 W, 250 V~,
Neon lamps
3000 W, 250 V~,
Neon lamps
1500 VA,
Fluorescent tubes
163 µF
Technical data
Order data
1 NOC
AgSnO2
25 A
120 A / 20 ms
250 V
4 kVA
500 mW
4 kV
typ. 8 / 2 ms
typ. 2 ms
30 x 106switching cycles
IP 40
40°C ... +70°C
18 g
SEV, UL, CSA, VDE
Switching cycles Regulation
3x105
25x103UL 508
>104
2.3x105
3.6x104
104
For high switch-on current
Schrack RP3SL
SSB_K014-K019_GB 24.10.2003 12:53 Uhr Seite K.15
5 A bei 70 °C with MY4 relay
250 Vac
2000 Vac
2000 Vac
IP 20
0.2...1.5 mm2 (doubled)
8 mm
max. 70 °C
V-1
mar%
5 A bei 70 °C with MY4 relay
250 Vac
2000 Vac
2000 Vac
IP 20
0.2...1.5 mm2
8 mm
max. 70 °C
V-1
ar%
Relay coupler
K.16
K
PLUGINDUSTRY
Rated current
Rated voltage
Voltage strength coil / contacts
Creepage and clearance path input / output
Protection class
Nominal cross-sectional area
Stripping length
Ambient temperature
Combustibility acc. to UL 94
Approvals
Technical data
Type Qty Order no.
PXZ4 10 8598710000
Empty base for mounting rail assembly TS 35
Order data
PXZ4 PXS4Base for industrial relays
Type Qty Order no.
PXZ4-PIRC 50 8598610000
PT 28802 25 8572170000
WS PXZ4 100 8598630000
ZQV PXZ4-bl 50 8611090000
ZQV PXZ4-rt 50 8611100000
SD 1 9009030000
Retaining clip
Relay, type: MY4
Relay, type: PT5
Marking
for PXZ4-PIRC only
Cross-connector
2-pole Blue
Red
Screwdriver
Accessories
Type Qty Order no.
PXS4-PIRC 100 8633920000
Tension clamp Screw connection
Type Qty Order no.
PXS4 10 8614350000
41 31 21 11
Wire opening
Tool opening
Wiring method for tension clamp connection
Place the specified screwdriver in the round tool opening
next to the square wire opening
Articles with coloured order number are kept permanently in stock at the central warehouse in Germany.
Delivery times see page X.2
Screw or tension clamp technology
For connecting cross-sectional areas
up to 1.5 mm2
For double and quadruple change-over
contact relays
Insulation in accordance with VDE 0110
Tension clamp connection
Minimum wiring workload
Double wiring of all terminals
Connections can be cross-connected
Separate arrangement of coil and contact
connections
SSB_K014-K019_GB 24.10.2003 12:53 Uhr Seite K.16
Relay coupler
K.17
K
Relay with 4 change-over contacts
With DC or AC voltage coil
Mechanical operating display
Integrated LED for optical
operating display
Test button
(blue = DC coil, red = AC coil)
Cadmium-free contacts with
3 µm gold plating
For plugging onto Weidmüller base
PXZ4 and PXS4
PLUGINDUSTRY
MY4 IN / MY4 IN1
Coil data
Rated voltage
Rated power
Operating voltage/release voltage
Contact data
No. of contacts
Contact material
Rated current
Switching voltage max. DC coil / AC coil
Max. switching power AC
Switching current
Recommended min. load
General data
Flammability class acc. to UL 94
Ambient temperature
Mechanical service life DC coil / AC coil
Response/release time
Duration of bounce
Weight
Dimensions (width x height x length)
Insulation
Voltage strength coil-contact
Insulation acc. to IEC 664 / VDE 0110 (1/89)
Rated voltage / pollution severity / overvoltage category
Insulation acc. to VDE 0110b (2/79)
Insulation group/reference voltage
DC coil AC coil
12 / 24 / 110 V- 24 / 120 / 230 V~
Typically 0.9 W Typically 1.0 VA
80 / 10 (% rated voltage) 80 / 30 (% rated voltage)
4 change-over contacts
AgNi with 3µm Au plating
4 x 5 A
125 V- / 250 V~
1250 VA
4 x 5 A
5 Vdc, 10 mA
V-2
55...+70 °C
>10x107 / >50x106
20 / 20 ms
max. 20 ms
35 g
21.5 x 36 x 28 mm
2000 Vac
240 V / 2 / II
A250 / B125
Switching current (A)
Switching voltage (V)
100
50
30
10
5
3
1
0,5
0,3
0,1 500250100503010531
DC induktive load
(L/R= 7 ms)
AC resistive load
AC inductive load
(cos φ=0,4)
DC resistive load
Breaking capacity
Lifetime (inductive load)
Lifetime (x104 operations)
1000
500
300
100
50
30
10
5
3
1
Switching current (A)
00,5 11,52
30 VDC
30 VDC
250 VAC
250 VAC
Lifetime (resistive load)
Lifetime (x104 operations)
1000
500
300
100
50
30
10
5
3
1
250 VAC
30 VDC
250 VAC
Switching current (A)
30 VDC
01234
5
Type Qty Order no.
MY4 IN1-12 10 8598660000
MY4 IN1-24 10 8598700000
MY4 IN1-110 10 8598640000
MY4 IN-24 10 8598690000
MY4 IN-120 10 8598650000
MY4 IN-230 10 8598670000
Other relays on request
DC coil
12 Vdc
24 Vdc
110 Vdc
AC coil
24 Vac
120 Vac
230 Vac
Order data
Technical data
Miniature power relay MY4
SSB_K014-K019_GB 24.10.2003 12:53 Uhr Seite K.17
Coil data
Rated voltage
Rated power
Operating voltage/release voltage
Working range AC coil, 60 Hz at 70°C
Contact data
No. of contacts
Contact material
Rated current
Switching voltage max. DC coil / AC coil
Max. switching power AC
Switching current
Recommended min. load
General data
Flammability class acc. to UL 94
Ambient temperature
Mechanical service life DC coil / AC coil
Response/release time
Duration of bounce
width x height x length
Insulation
Voltage strength coil-contact
Insulation acc. to IEC 664 / VDE 0110 (1/89)
Rated voltage / pollution severity / overvoltage category
Insulation acc. to VDE 0110b (2/79)
Insulation group/reference voltage
DC coil AC coil
6...220 V- 6...230 V~
Typically 0.75 W Typically 1.0 VA
75 / 10 (% rated voltage) 80 / 10 (% rated voltage)
90...110 % Urated
4 change-over contacts
AgNi 90 / 10, AgNi 90 / 10 htv
4 x 6 A
250 Vac
1500 VA
4 x 6 A
24 V, 10 mA / 20 mV, 1 mA htv
V-0
40...+70°C
> 30 x 106 (DC coil), > 20 x 106 (AC coil)
15 / 10 ms
5 ms
22.5 x 30 x 28 mm
2500 Veff
240 V / 2 / III
B / 250
Type Qty Order no.
PT 570006 10 8074650000
PT 570012 10 8054360000
PT 570024 10 1180700000
PT 570048 10 8074670000
PT 570060 10 8074680000
PT 570110 10 8074700000
PT 570220 10 8636230000
PT 570506 10 8074710000
PT 570512 10 8074730000
PT 570524 10 1181800000
PT 570548 10 1180900000
PT 570560 10 8074760000
PT 570615 10 1180800000
PT 570730 10 1181100000
Other relays on request
DC coil
6 Vdc
12 Vdc
24 Vdc
48 Vdc
60 Vdc
115 Vdc
220 Vdc
AC coil
6 Vac
12 Vac
24 Vac
48 Vac
60 Vac
115 Vac
230 Vac
Relay coupler
K.18
K
Relay with 4 change-over contacts
With DC or AC voltage coil
Mechanical operating display
Locking test button
Cadmium-free contact material
For plugging onto Weidmüller base PXZ4
with retaining clip PT 28802
PLUGINDUSTRY
PT 5
Technical data
Order data
Max. DC load breaking capacity
DC voltage [Vdc]
DC current [A]
4 pole
3 pole
2 pole
contacts
contacts
contacts
in series
pole
resistive load
Electrical life
Operations
DC current [A]
resistive load
Coil operating range DC
Coil voltage (U/Un)
Ambient temperature [°C]
nominal voltage
Miniature power relay PT 5
SSB_K014-K019_GB 24.10.2003 12:53 Uhr Seite K.18
K
Relay coupler
MICROSERIES
1 change-over contact
Module can be used as an universal interface between con-
trol and actuator for switching small and medium loads
The pluggable cross-connection in input and output mini-
mizes the effort to wire
• Width 6.1 mm
• Relay interchangeable, also with opto-couplers
11
14
12
A2
A1
11
14
12
A2
A1
11
14
12
A2
A1
11
14
12
A2
A1
(5/12Vdc)
(24/60 Vdc)
(24/48/120 Vuc)
(230 Vac)
Output
Max. switching voltage AC/Continuous current 250V/6A
Min. switching power 12V/100mA
Response time / Release time 6.2ms/3.9ms
Contact base material AgSnO
Mechanical endurance 20x10^6 switching cycles
Max. switching frequency at rated load 0.1Hz
Rated data
Status indicator/Free wheel diode/Reverse volt. prot. LED green/Yes/available
Ambient temp., fitted w. distance -25 °C…+50 °C
Storage temperature -40 °C…+60 °C
Climate 40°C/93% rel. humidity without condensation
Approvals CE, cURus
Insulation coordinates (EN 50 178)
Standards EN 50178
Rated voltage 300 V
Impulse withstand voltage 4 kV
Creepage and clearance path input - output =>5.5mm
Overvoltage category III
Pollution severity 2
Secure separation acc. to VDE 0106 Part 101 Yes
Dimensions Screw connection Tension clamp connection
Clamping range (rating- / min. / max.) mm22.5 / 0.5 / 4 1.5 / 0.5 / 2.5
Length x width x height mm 93.0 / 6.1 / 92.0 94.0 / 6.1 / 91.0
Information
2
0
0
0
0
.
1
5
AC resistive load
S
witch o
p
erations
Switch operations
ch
o
p
era
ti
ons
acc
. t
o
D
D
eratin
g
curv
e
Ambient tem
p
erature
[C
°
]
O
ut
p
ut current
[
A
]
v
v
olta
g
e [A]
DC-load breaking capacity
DC-load
breaking
capa
curre
n
t [A]
curre t
[A]
Applications
SSB_K008-K059 21.10.2003 16:42 Uhr Seite K.20
K
Relay coupler
MICROSERIES
1 change-over contact
Ordering data
Input
Rated voltage
Rated current AC
Rated current DC
Power rating
Oper.-/drop-out volt. AC-coil
Oper.-/drop-out volt. DC-coil
Pull-in curr./release curr. AC-coil
Pull-in curr./release curr. DC-coil
Ordering data
Complete module
Screw connection Type
Order No.
Tension clamp connection Type
Order No.
Ordering data
Spare relay, pluggable
Type
Order No.
Information
5VDC 1CO
5 Vdc +/- 20 %
38.5mA
193mW
3.2V/1.6V
21.6mA/8mA
MRS 5Vdc 1CO
8556080000
MRZ 5Vdc 1CO
8556150000
APE 30005V 05Vdc-Rel1U
4061580000
12VDC 1CO
12 Vdc +/- 20 %
17mA
210mW
6.4V/2.5V
8.4mA/2.4mA
MRS 12Vdc 1CO
8556070000
MRZ 12Vdc 1CO
8556140000
APE 30012V 12Vdc-Rel1U
4061610000
24VDC 1CO
24 Vdc +/- 20 %
6.6mA
160mW
15.4V/6.5V
4mA/1.2mA
MRS 24Vdc 1CO
8533640000
MRZ 24VDC 1U
8533660000
APE 30024V 24Vdc-Rel1U
4060120000
24VUC 1CO
24 Vuc +/- 10 %
11mA
6.4mA
154mW
15.8V/7V
15.8V/7V
3.6mA/1.3mA
3.6mA/1.3mA
MRS 24Vuc 1CO
8556050000
MRZ 24Vuc 1CO
8556120000
APE 30024V 24Vdc-Rel1U
4060120000
Ordering data
Input
Rated voltage
Rated current AC
Rated current DC
Power rating
Oper.-/drop-out volt. AC-coil
Oper.-/drop-out volt. DC-coil
Pull-in curr./release curr. AC-coil
Pull-in curr./release curr. DC-coil
Ordering data
Complete module
Screw connection Type
Order No.
Tension clamp connection Type
Order No.
Ordering data
Spare relay, pluggable
Type
Order No.
Information
48VUC 1CO
48 Vuc +/- 10 %
5mA
4mA
190mW
29V/11V
29V/11V
2.2mA/1.3mA
2.2mA/1.3mA
MRS 48Vuc 1CO
8556040000
MRZ 48Vuc 1CO
8556110000
APE 30048V 48Vdc-Rel1U
4061620000
60VDC 1CO
60 Vdc +/- 20 %
3.3mA
200mW
35V/11V
1.6mA/0.6mA
MRS 60Vdc 1CO
8556060000
MRZ 60Vdc 1CO
8556130000
APE 30060V 60Vdc-Rel1U
4061630000
120VUC 1CO
120 Vuc +10 %/ -15 %
3.5mA
3.5mA
0.42VA
71V/22V
71V/22V
1.8mA/0.5mA
1.8mA/0.5mA
MRS 120Vuc 1CO
8556030000
MRZ 120Vuc 1CO
8556100000
APE 30060V 60Vdc-Rel1U
4061630000
230VAC 1CO
230 Vac +/- 10 %
7.6mA
1.75VA
103V/49V
103V/49V
5mA/2.5mA
5mA/2.5mA
MRS 230Vac 1CO
8556020000
MRZ 230Vac 1CO
8556090000
APE 30024V 24Vdc-Rel1U
4060120000
SSB_K008-K059 21.10.2003 16:42 Uhr Seite K.21
K
Relay coupler
MICROSERIES
1 change-over contact with gold-plated con-
tact
Module can be used as an universal interface between con-
trol and actuator for switching small and medium loads
The pluggable cross-connection in input and output mini-
mizes the effort to wire
• Width 6.1 mm
• Relay interchangeable, also with opto-couplers
11
14
12
A2
(24Vdc)
A1
11
14
12
A2
(120 Vuc)
A1
11
14
12
A2
(230 Vac)
A1
Output
Max. switching voltage AC/Continuous current 250V/6A
Min. switching power 12V/10mA
Response time / Release time 6.6ms/5.8ms
Contact base material AgSnO 5 #03BCm Au
Mechanical endurance 20x10^6 switching cycles
Max. switching frequency at rated load 0.1Hz
Rated data
Status indicator/Free wheel diode/Reverse volt. prot. LED green/Yes/available
Ambient temp., fitted w. distance -25 °C…+50 °C
Storage temperature -40 °C…+60 °C
Climate 40°C/93% rel. humidity without condensation
Approvals CE, cURus
Insulation coordinates (EN 50 178)
Standards EN 50178
Rated voltage 300 V
Impulse withstand voltage 4 kV
Creepage and clearance path input - output =>5.5mm
Overvoltage category III
Pollution severity 2
Secure separation acc. to VDE 0106 Part 101 Yes
Dimensions Screw connection Tension clamp connection
Clamping range (rating- / min. / max.) mm22.5 / 0.5 / 4 1.5 / 0.5 / 2.5
Length x width x height mm 93.0 / 6.1 / 92.0 94.0 / 6.1 / 91.0
Information
Ordering data
Ordering data
Complete module
Screw connection Type
Order No.
Tension clamp connection Type
Order No.
Ordering data
Spare relay, pluggable
Type
Order No.
Input
Rated voltage
Rated current AC
Rated current DC
Power rating
Oper.-/drop-out volt. AC-coil
Oper.-/drop-out volt. DC-coil
Pull-in curr./release curr. AC-coil
Pull-in curr./release curr. DC-coil
Information
24VDC 1CO 5uAU
24 Vdc +/- 20 %
6.6mA
160mW
15.4V/6.5V
4mA/1.2mA
MRS 24Vdc 1CO 5uAu
8596060000
MRZ 24Vdc 1CO 5uAu
8596080000
APE 30124V 24Vdc-Rel1U
4061590000
230VAC 1CO 5uAU
230 Vac +/- 10 %
7.6mA
1.75VA
103V/49V
103V/49V
5mA/2.5mA
5mA/2.5mA
MRS 230Vac 1CO 5uAu
8596050000
MRZ 230Vac 1CO 5uAu
8596070000
APE 30124V 24Vdc-Rel1U
4061590000
SSB_K008-K059 21.10.2003 16:42 Uhr Seite K.22
Type Qty Order no.
Marker
WS 12/6 12 x 6 mm 200 1061160000
Labels, laser mark
LM MT 300 15/6 ge 484 Labels / sheet 10 1686360000
Screwdriver
SD 0.6 x 3.5 x 100 10 9008330000
Relay coupler
K.23
K
MICROSERIES
Accessories General data – MICROSERIES
Tension clamp Screw
Clamping conductor connection connection
Solid H07V-U mm20.5 … 2.5 0.5 … 4.0
Flexible H07V-K mm20.5 … 2.5 0.5 … 2.5
“f” with ferrule acc. to DIN 46 228 / 1 mm20.5 … 1.5 0.5 … 1.5
“f” with ferrule with plastic collar mm20.5 … 1.5 0.5 … 1.5
Max. clamping range mm2 0.13 … 2.5 0.13 … 4.0
Plug gauge acc. to IEC 60-947-1 Size A 2 A 3
General technical data
Rated torque - 0,6
Continuous output current of the 2-pole cross-connector A 10 10
Continuous output current of the multi-pole cross-connector A 10 10
Stripping length mm 10 7
Protection class IP 20 IP 20
Enclosure material Wemid Wemid
Flammability class acc. to UL 94 V-0 V-0
Rated current A 6 6
Rated voltage V 250 250
Pluggable cross-connector Technical data
Type No. of poles Qty Order no.
Yellow
ZQV 4N / 2 GE 2 60 1758250000
ZQV 4N / 3 GE 3 60 1762630000
ZQV 4N / 4 GE 4 60 1762620000
ZQV 4N / 10 GE 10 20 1758260000
ZQV 4N / 41 GE 41 10 1758270000
Red
ZQV 4N / 2 RT 2 60 1793950000
ZQV 4N / 3 RT 3 60 1793980000
ZQV 4N / 4 RT 4 60 1794010000
ZQV 4N / 10 RT 10 20 1794040000
ZQV 4N / 41 RT 41 10 1794070000
Blue
ZQV 4N / 2 BL 2 60 1793960000
ZQV 4N / 3 BL 3 60 1793990000
ZQV 4N / 4 BL 4 60 1794020000
ZQV 4N / 10 BL 10 20 1794050000
ZQV 4N / 41 BL 41 10 1794080000
Black
ZQV 4N / 2 SW 2 60 1793970000
ZQV 4N / 3 SW 3 60 1794000000
ZQV 4N / 4 SW 4 60 1794030000
ZQV 4N / 10 SW 10 20 1794060000
ZQV 4N / 41 SW 41 10 1794090000
Other accessories Dimensional drawings
Tension clamp Screw connection
91 mm
94 mm
6.1 mm
92 mm
93 mm
6.1 mm
SSB_K023-K023_GB 24.10.2003 15:43 Uhr Seite K.23
K
Relay coupler
WAVESERIES
1 change-over contact
2,4 V...24 Vdc
1
0 V
2
24 Vdc
3
12
11
14
250 V / 4 A 7
8
9
1
A2
2
A1 +
3
12
11
14
250 V / 4 A 7
8
9
0 V
24 Vdc
A1 +24 Vuc
0 V
1
A3
2
A2 48 Vuc
3
12
11
14
250 V / 4 A 7
8
9
WRS 1 12,4-24 Vdc
WRS 24 Vdc
WRD 24/xxVuc
Output
Max. switching voltage AC/Continuous current 250V/5A
Min. switching power 100mA/5Vdc
Response time / Release time 7ms/6ms
Contact base material Ag alloy
Mechanical endurance 20x10^6 switching cycles
Max. switching frequency at rated load 0.1Hz
Rated data
Status indicator/Free wheel diode/Reverse volt. prot. LED green/Yes/available
Ambient temp., fitted w. distance -25 °C…+50 °C
Storage temperature -40 °C…+60 °C
Climate 40°C/93% rel. humidity without condensation
Approvals UL / CSA
Insulation coordinates (EN 50 178)
Standards EN 50178
Rated voltage 300 V
Impulse withstand voltage 6 kV (1.2/50 µ)
Creepage and clearance path input - output =>5.5mm
Overvoltage category III
Pollution severity 2
Secure separation acc. to VDE 0106 Part 101 Yes
Dimensions Screw connection Tension clamp connection
Clamping range (rating- / min. / max.) mm21.5 / 0.5 / 2.5
Length x width x height mm 72.0 / 22.5 / 92.4
Information
0
1
2
3
4
5
6
7
8
Clearance > = 10mm
Ambient temperature [°C]
020 40 60 80 100
Output current [A]
Mounted horizontally
Applications
SSB_K008-K059 25.10.2003 11:38 Uhr Seite K.24
K
Relay coupler
WAVESERIES
1 change-over contact
Ordering data
Input
Rated voltage
Rated current AC
Rated current DC
Power rating
Oper.-/drop-out volt. AC-coil
Oper.-/drop-out volt. DC-coil
Pull-in curr./release curr. AC-coil
Pull-in curr./release curr. DC-coil
Ordering data
Complete module
Screw connection Type
Order No.
Tension clamp connection Type
Order No.
Ordering data
Spare relay, pluggable
Type
Order No.
Information
2.4-24VDC 1CO
2.4…24 Vdc +/-10 %
4.6mA
200 mW
1.9 V
3.88mA
WRS1 2.4-24VDC 1U
8275320000
24VDC 1CO
24 Vdc +/- 10 %
9mA
220mW
16 V/7.5 V
5.7 mA/2.2 mA
WRS1 24VDC 1U
8275350000
24/48VUC 1CO
24 Vuc // 48 Vuc, +/- 10 %
approx. 14mA
14 mA
0.35VA(W) // 0.5VA(W)
16 V/9.5 V // 29 V/15 V
16 V/9.5 V // 29 V/15 V
9 mA/4.5 mA // 8.3mA/4.1mA
9 mA/4.5 mA // 8.3mA/4.1mA
WRS1 24/48VUC 1U
8286280000
24/60VUC 1CO
24 Vuc // 60 Vuc, +/- 10 %
approx. 11mA
approx. 10mA
0.22W / 0.34VA // 0.6W / 0.7VA
16 V/9.5 V // 31 V/20 V
15 V/8,5V // 34 V/15 V
5.6mA/2.3mA // 5.6mA/2.1mA
5.8 mA/3.9 mA // 5.6 mA/3.4 mA
WRS1 24/60VUC 1U
8418210000
Ordering data
Input
Rated voltage
Rated current AC
Rated current DC
Power rating
Oper.-/drop-out volt. AC-coil
Oper.-/drop-out volt. DC-coil
Pull-in curr./release curr. AC-coil
Pull-in curr./release curr. DC-coil
Ordering data
Complete module
Screw connection Type
Order No.
Tension clamp connection Type
Order No.
Ordering data
Spare relay, pluggable
Type
Order No.
Information
24/115VUC 1CO
24 Vuc // 115 Vuc, +/- 10 %
approx. 11mA
approx. 10mA
0.22W / 0.34VA // 1.2W / 1.3VA
15 V/12 V // 60 V/34 V
16V/8.5V // 64V/26V
5.8mA/3.9mA // 5.5mA/3mA
5.6mA/2.3mA // 5.7mA/2.2mA
WRS1 24/115VUC 1U
8418220000
24VUC/230VAC 1CO
24 Vuc // 230 Vac, +/- 10 %
approx. 15mA
14mA (24Vdc)
0.34VA / 0.32W // 3.5VA
13 V/9 V // 115 V/66 V
13 V/9 V (24Vdc)
7.5 mA/4.7 mA // 7.4 mA/4.3 mA
7.5 mA/4.7 mA
WRS1 24VUC/230VAC 1U
8418230000
SSB_K008-K059 25.10.2003 11:38 Uhr Seite K.25
K
Relay coupler
WAVESERIES
2 NO contacts
0
1
2
3
4
5
6
7
8
0 1020304050607080
Derating curve
[
[
A
Output current
clearance 10mm
>
Ambient temperature (°C)
A 1
0 V
1
A 2
2
A 3
312
11
14
10
24
13
23 7
8
9
mounted
Output
Max. switching voltage AC/Continuous current 250V/5A
Min. switching power 100mA/5Vdc
Response time / Release time 5ms/6ms
Contact base material AgSnO2
Mechanical endurance 50x10^6 switching cycles
Max. switching frequency at rated load 0.1Hz
Rated data
Status indicator/Free wheel diode/Reverse volt. prot. LED green/Yes/available
Ambient temp., fitted w. distance -25 °C…+50 °C
Storage temperature -40 °C…+60 °C
Climate 40°C/93% rel. humidity without condensation
Approvals UL / CSA
Insulation coordinates (EN 50 178)
Standards EN 50178
Rated voltage 300 V
Impulse withstand voltage 6 kV (1.2/50 µ)
Creepage and clearance path input - output =>8mm
Overvoltage category III
Pollution severity 2
Secure separation acc. to VDE 0106 Part 101 Yes
Dimensions Screw connection Tension clamp connection
Clamping range (rating- / min. / max.) mm21.5 / 0.5 / 2.5
Length x width x height mm 92.4 / 22.5 / 112.4
Information
Ordering data
Ordering data
Complete module
Screw connection Type
Order No.
Tension clamp connection Type
Order No.
Ordering data
Spare relay, pluggable
Type
Order No.
Input
Rated voltage
Rated current AC
Rated current DC
Power rating
Oper.-/drop-out volt. AC-coil
Oper.-/drop-out volt. DC-coil
Pull-in curr./release curr. AC-coil
Pull-in curr./release curr. DC-coil
Information
12/24VDC 2A
12 Vdc // 24 Vdc, +/- 10 %
approx. 20mA
0.24W // 0.5W
7.5 V /3.5 V // 14.5 V/6.1 V
10 mA/4.2 mA // 10 mA/4 mA
WRS2 12/24VDC 2A
8418240000
24/48VUC 2A
24 Vuc // 48 Vuc, +/- 10 %
approx. 11mA
approx. 8.5mA
0.17W / 0.21VA // 0.4W / 0.48VA
13.5 V /9 V // 24 V/16 V
16 V /7.8 V // 28 V/12 V
4.4 mA/2.7 mA // 4.3 mA/2.6 mA
4.3 mA/1.6 mA // 4.4 mA/1.6 mA
WRS2 24/48VUC 2A
8418250000
115VUC/230VAC 2A
115 Vuc // 230 Vac, +/- 10 %
approx. 10mA
9mA (115Vdc)
1VA / 0.9W // 2.5VA
58 V /22 V // 110 V/40 V
54 V /20 V (115Vdc)
4.8 mA/1.7 mA V // 5 mA/2 mA
4 mA/2 mA
WRS2 115VUC/230VAC 2A
8418260000
SSB_K008-K059 25.10.2003 11:38 Uhr Seite K.26
K
Relay coupler
WAVESERIES
1 NC contact / 1 NO contact
A 1
0 V
1
A 2 2
A 3 312
11
14
10
12
13
11 7
8
9
mounted
g
0
1
2
3
4
5
6
7
8
020406080100
Derating curve
[
[
A
Output current
Ambient temperature [°C]
clearance 10mm
>
Output
Max. switching voltage AC/Continuous current 250V/5A
Min. switching power 100mA/5V
Response time / Release time 7ms/5ms
Contact base material AgSnO2
Mechanical endurance 50x10^6 switching cycles
Max. switching frequency at rated load 0.1Hz
Rated data
Status indicator/Free wheel diode/Reverse volt. prot. LED green/Yes/available
Ambient temp., fitted w. distance -25 °C+50 °C
Storage temperature -40 °C+60 °C
Climate 40°C/93% rel. humidity without condensation
Approvals UL / CSA
Insulation coordinates (EN 50 178)
Standards EN 50178
Rated voltage 300 V
Impulse withstand voltage 6 kV (1.2/50 µ)
Creepage and clearance path input - output =>8mm
Overvoltage category III
Pollution severity 2
Secure separation acc. to VDE 0106 Part 101 Yes
Dimensions Screw connection Tension clamp connection
Clamping range (rating- / min. / max.) mm21.5 / 0.5 / 2.5
Length x width x height mm 92.4 / 22.5 / 112.4
Information
Ordering data
Ordering data
Complete module
Screw connection Type
Order No.
Tension clamp connection Type
Order No.
Ordering data
Spare relay, pluggable
Type
Order No.
Input
Rated voltage
Rated current AC
Rated current DC
Power rating
Oper.-/drop-out volt. AC-coil
Oper.-/drop-out volt. DC-coil
Pull-in curr./release curr. AC-coil
Pull-in curr./release curr. DC-coil
Information
12/24VDC 1A 1R
12 Vdc // 24 Vdc, +/- 10 %
approx. 20mA
0.24W // 0.5W
7.5 V /3.5 V // 14.5 V/6.1 V
10 mA/4.2 mA // 10 mA/4 mA
WRS2 12/24VDC 1A1R
8418270000
24/48VUC 1A1R
24 Vuc // 48 Vuc, +/- 10 %
approx. 11mA
approx. 8.5mA
0.17W / 0.21VA // 0.4W / 0.48VA
13.5 V /9 V // 24 V/16 V
13.5 V /9 V // 24 V/16 V
4.4 mA/2.7 mA // 4.3 mA/1.6 mA
4.3 mA/1.6 mA // 4.4 mA/1.6 mA
WRS2 24/48VUC 1A1R
8418280000
115VUC/230VAC 1A 1R
115 Vuc // 230 Vac, +/- 10 %
approx. 10mA
9mA (115Vdc)
1VA / 0.9W // 2.5VA
58 V /22 V // 110 V/40 V
54 V /20 V (115Vdc)
4.8 mA/1.7 mA // 5 mA/2 mA
4 mA/1.6 mA
WRS2 115VUC/230VAC 1A1R
8418290000
SSB_K008-K059 25.10.2003 11:38 Uhr Seite K.27
K
Relay coupler
WAVESERIES
2 change-over contacts
0
0,01
0,02
0,03
0,04
0,05
0,06
0,07
0,08
01020 30 40 50 60 70 80
[
[
A
Output current
Ambient temperature [°C]
clearance > 10 mm
mounted
214
11
12
4
6
510
212
211
114
8
9
1
3
27
112
111
Derating curve
1A1
1A3
1A2
2A1
2A3
2A2
Output
Max. switching voltage AC/Continuous current 250V/5A
Min. switching power 100mA/5Vdc
Response time / Release time 6ms/10ms
Contact base material Ag alloy
Mechanical endurance 20x10^6 switching cycles
Max. switching frequency at rated load 0.1Hz
Rated data
Status indicator/Free wheel diode/Reverse volt. prot. LED green/Yes/available
Ambient temp., fitted w. distance -25 °C+50 °C
Storage temperature -40 °C+60 °C
Climate 40°C/93% rel. humidity without condensation
Approvals UL / CSA
Insulation coordinates (EN 50 178)
Standards EN 50178
Rated voltage 300 V
Impulse withstand voltage 6 kV (1.2/50 µ)
Creepage and clearance path input - output =>5.5mm
Overvoltage category III
Pollution severity 2
Secure separation acc. to VDE 0106 Part 101 Yes
Dimensions Screw connection Tension clamp connection
Clamping range (rating- / min. / max.) mm21.5 / 0.5 / 2.5
Length x width x height mm 92.4 / 22.5 / 112.4
Information
Ordering data
Ordering data
Complete module
Screw connection Type
Order No.
Tension clamp connection Type
Order No.
Ordering data
Spare relay, pluggable
Type
Order No.
Input
Rated voltage
Rated current AC
Rated current DC
Power rating
Oper.-/drop-out volt. AC-coil
Oper.-/drop-out volt. DC-coil
Pull-in curr./release curr. AC-coil
Pull-in curr./release curr. DC-coil
Information
12/24VDC 2CO
12 Vdc // 24 Vdc, +/- 10 %
approx. 23mA
0.26W // 0.53W
8.5 V /3 V // 15 V/4.8 V
15.2 mA/5.7 mA // 15.3 mA/5.6
mA
WRS2 12/24VDC 2U
8418300000
24/48VUC 2CO
24 Vuc // 48 Vuc, +/- 10 %
approx. 15mA
14 mA
0.35VA(W) // 0.7VA(W)
16V/9.5V // 29V/15V
9 mA/4.5 mA // 8.3mA/4.1mA
9 mA/4.5 mA // 8.3mA/4.1mA
WRS2 24/48VUC 2U
8418310000
24VUC/230VAC 2CO
24 Vuc // 230 Vac, +/- 10 %
approx. 15mA
14mA (24Vdc)
0.35W // 3.45VA
13 V/9 V // 115 V/66 V
13 V/9 V (24Vdc)
7.5 mA/4.7 mA // 7.4 mA/4.3 mA
7.5 mA/4.7 mA
WRS2 24VUC/230VAC 2U
8418320000
SSB_K008-K059 25.10.2003 11:38 Uhr Seite K.28
K
Relay coupler
WAVESERIES
3 NO contacts
113
0
1
2
3
4
5
6
7
0 20406080100
>
Derating curve
114
1A1
1A2
K1
313
314
3A1
3A2
K3
213
214
2A1
2A2
K2
2
3
9
8
11
12
10
7
clearance 10mm
mounted
[
[
A
Output current
Ambient temperature [°C]
5
6
1
4
Output
Max. switching voltage AC/Continuous current 250V/4A
Min. switching power 12V/10mA
Response time / Release time 5ms/21ms
Contact base material AgSnO2
Mechanical endurance 20x10^6 switching cycles
Max. switching frequency at rated load 0.1Hz
Rated data
Status indicator/Free wheel diode/Reverse volt. prot. LED green/No/not available
Ambient temp., fitted w. distance -25 °C+50 °C
Storage temperature -40 °C+60 °C
Climate 40°C/93% rel. humidity without condensation
Approvals UL / CSA
Insulation coordinates (EN 50 178)
Standards EN 50178
Rated voltage 300 V
Impulse withstand voltage 6 kV (1.2/50 µ)
Creepage and clearance path input - output =>5.5mm
Overvoltage category III
Pollution severity 2
Secure separation acc. to VDE 0106 Part 101 Yes
Dimensions Screw connection Tension clamp connection
Clamping range (rating- / min. / max.) mm21.5 / 0.5 / 2.5
Length x width x height mm 92.4 / 22.5 / 112.4
Information
Ordering data
Ordering data
Complete module
Screw connection Type
Order No.
Tension clamp connection Type
Order No.
Ordering data
Spare relay, pluggable
Type
Order No.
Input
Rated voltage
Rated current AC
Rated current DC
Power rating
Oper.-/drop-out volt. AC-coil
Oper.-/drop-out volt. DC-coil
Pull-in curr./release curr. AC-coil
Pull-in curr./release curr. DC-coil
Information
24VUC 3A
24 Vuc +/- 10 %
10.4mA
10.5mA
0.3VA // 0.25W
12.8 V / 5 V
12.8 V / 5 V
6.6 mA / 2.1 mA
6.5 mA / 1.4 mA
WRS2 24VUC 3A
8418330000
230VAC 3A
230 Vac +/- 10 %
10.3mA
2.4VA
207V/207V/207V
9mA
WRS2 230VAC 3A
8418340000
SSB_K008-K059 25.10.2003 11:38 Uhr Seite K.29
5 VTTL 12 V– 24 V– 24 V048 V– 48 V060 V– 115 V~ 115 V– 230 V~2)240 V~
0.45 W1) 0.45 W 0.45 W 0.45 W 0.45 W 0.45 W 0.45 W 0.82 W
0.7 VA 0.6 VA 0.8 VA 0.8 VA 1.2 VA
3 mA 3 mA 2.5 mA– 2 mA 2.5 mA– 1 mA– 2 mA– 0.5 mA–
3.5 mA~ 4.5 mA~ 1 mA~ 1 mA~ 1 mA~
12 mA 10 mA 6 mA 4.3 mA
250 V 250 V 250 V 250 V 250 V 250 V 250 V 250 V 250 V 250 V 250 V
5 A 6 A 6 A 6 A 6 A 5 A 5 A 5 A 5 A 3 A 3 A
8 A
2000 VA / 100 W
250 mW / 10 mA
3 ms
8 ms 8 ms 8 ms 8 ms 12 ms 13 ms 12 ms 9 ms 12 ms 10 ms 10 ms
7 ms 7 ms 7 ms 16 ms 11 ms 12 ms 11 ms 8 ms 11 ms 9 ms 9 ms
70 Hz 70 Hz 70 Hz 30 Hz 70 Hz 20 Hz 70 Hz 30 Hz 70 Hz 30 Hz 30 Hz
AgNi, gold-flashed
>107switching cycles
> 5 x 105 switching cycles
>7 x 105switching cycles
–40 °C…+60 °C
–25 °C…+40 °C
–25 °C…+50 °C
III
2
11.2 mm NOC / NCC, 25 mm change-over contact
70 mm (74 mm BL/SL version)
56 mm / 51.5 mm
1) Rated consumption of auxiliary voltage 24 V–.
2) 230 V– on request
Relay coupler
K.30
K
RS-SERIES / RS 30
Screw connection
1 NOC
1 NCC
1 NCC, 1 NOC
or 1 change-over contact RS 30
Isolating plug with screw connection
RS 30
Input voltage 5…60 V ± 10 %; 115 V/230 V + 5 % – 15%
Nominal consumption – (W)
Nominal consumption ~ (VA)
Release current of relay (at 20°C)
Release current of relay (at 20°C)
Pick-up current
Output voltage max.
Continuous current
Derating curve
a = arranged on mounting rail in horizontal row without spacing
b = arranged on mounting rail in horizontal row with 20 mm
spacing
Continuous
current
Ambient temperature
Switch-on current
Switch-on power under ohmic load
Min. switching power/switching current
Duration of bounce
Typical switching times
–, Pick-up delay
–, Release delay
Max. switching frequency
Contact material
Service life, mechanical
–, 24 V-, 1A ohmic load
–, 230 V-. 3A, ohmic load
Storage temperature
Ambient temperature, arranged on mounting rail
–, in horizontal row without spacing
–, in horizontal row with > 20 mm spacing
Insulation coordination acc. to EN 50 178
Overvoltage category
Pollution severity
Dimensions
Mounting width
Length (at right angles to mounting rail)
Hight (with TS 32 / TS 35 x 7.5)
Constant current
Constant current
spacing > 20 mm
Switching mode on/off
< 1 min (50 / 50 %)
48 V~ / 230 V~ / 240 V~
Technical data
1 change-over contact
1 NOC
1 NCC
1 change-over contact
SSB_K030-K031_GB 10.10.2003 9:39 Uhr Seite K.30
Relay coupler
K.31
K
Screw connection
RS 30
Isolating plug with screw connection
RS 30
RS-SERIES – RS 30
Input
voltage
5 V–, TTL
12 V–
24 V–
24 Vb
48 V–
48 Vb
60 V–
115 V–
115 V~
230 V~
240 V~
Mail-line wiring diagram
Function
display
without
without
LED red
without
LED green
LED red
without
LED green
LED red
LED green
LED red
without
LED green
without
LED green
LED red
without
LED green
LED red
without
LED green
LED red
without
LED green
LED red
without
LED green
LED red
ABCDEF GG
change-over change-over change-over
NOC NOC NCC contact contact contact NOC NCC
1167760000 1167660000
1129660000
1129421001 1129521001
1101661001 1100961001 1100260000
1101611001 1100911001 1181511001 1100210000
1101621001 1100921001 1181521001 1100220000
1101761001 1100360000
1101711001
1101721001
1101811001 1100410000
1101821001 1100420000
1100560000
1101911001
1102061001
1102011001
1100620000
1155161001 1155261001
1155111001 1155211001
1155121001 1155221001
1102161001 1100760000
1102111001
1102121001
1102261001 1100860000
1102211001
1102221001
1128561001
1128511001
1128521001
Order data
A - 1 NOC DC B - 1 NOC AC/DC
C - 1 NCC DC D - 1 change-over contact DC
F - 1 change-over contact AC/DC
G - 1 NOC / 1NCC DC
E - 1 change-over contact DC
SSB_K030-K031_GB 10.10.2003 9:39 Uhr Seite K.31
K
Relay coupler
RS-SERIES - RS 31
1 change-over contact
• For high switching power
• Suitable to switch inductive loads
A 2
A 1
A 2
12 14
11
24 Vdc
A 2
A 1
A 2
12 14
11
residual tensions
Output
Max. switching voltage AC/Continuous current 250V/16A
Min. switching power 1W
Response time / Release time 9ms/10ms
Contact base material AgCdO
Mechanical endurance 3x10^7 switching cycles
Max. switching frequency at rated load 0.1Hz
Rated data
Status indicator/Free wheel diode/Reverse volt. prot. LED green/Yes/available
Ambient temp., fitted w. distance -25 °C…+40 °C
Storage temperature -40 °C…+60 °C
Climate 40°C/93% rel. humidity without condensation
Approvals CE
Insulation coordinates (EN 50 178)
Standards EN 50178
Rated voltage 250V
Impulse withstand voltage 6 kV
Creepage and clearance path input - output 3mm
Overvoltage category III
Pollution severity 2
Secure separation acc. to VDE 0106 Part 101 No
Dimensions Screw connection Tension clamp connection
Clamping range (rating- / min. / max.) mm22.5 / 0.5 / 4
Length x width x height mm 70.0 / 25.0 / 58.0
Information
0
8
16
0
A
10 20 30 40 50 60 70
Derating curv
e
Applications
SSB_K008-K059 22.10.2003 8:35 Uhr Seite K.32
K
Relay coupler
RS-SERIES - RS 31
1 change-over contact
Ordering data
Input
Rated voltage
Rated current AC
Rated current DC
Power rating
Oper.-/drop-out volt. AC-coil
Oper.-/drop-out volt. DC-coil
Pull-in curr./release curr. AC-coil
Pull-in curr./release curr. DC-coil
Ordering data
Complete module
Screw connection Type
Order No.
Tension clamp connection Type
Order No.
Ordering data
Spare relay, pluggable
Type
Order No.
Information
24VDC 1CO
24 Vdc +/- 10 %
40mA
1W
21.5V
-/11.5mA
RS 31 24VDC LD LP 1U
1128311001
48VDC 1CO
48 Vdc +/- 10 %
20mA
1W
43V
-/13.5mA
RS 31 48VDC LD 1U LP
1150761001
115V DC 1CO
115 Vdc + 5 / - 15%
8mA
1W
98V
-/5.5mA
RS 31 115VDC LD LP 1U
1150361001
115VAC 1CO
115 Vac +5 %/ -15 %
8mA
1VA
98V
-/1.5mA
RS 31 115VAC LD LP 1U
1150461001
Ordering data
Input
Rated voltage
Rated current AC
Rated current DC
Power rating
Oper.-/drop-out volt. AC-coil
Oper.-/drop-out volt. DC-coil
Pull-in curr./release curr. AC-coil
Pull-in curr./release curr. DC-coil
Ordering data
Complete module
Screw connection Type
Order No.
Tension clamp connection Type
Order No.
Ordering data
Spare relay, pluggable
Type
Order No.
Information
230VAC 1CO
230 Vac + 5 / - 15%
4.5mA
1VA
195V
-/2.2mA
RS 31 230VAC LD LP 1U
1128461001
SSB_K008-K059 22.10.2003 8:35 Uhr Seite K.33
K
Relay coupler
RS-SERIES - RS 32
2 change-over contacts, DC input
A
3
40 50 60 70
4
2
1
20 30 °C
10
A1
A2
A2
1214 22 24
11 21
Output
Max. switching voltage AC/Continuous current 250V/4A
Min. switching power 10V/100mA
Response time / Release time 13ms/10ms
Contact base material AgNi 0.15 gold flashed
Mechanical endurance >30x10^6 switching cycles
Max. switching frequency at rated load 0.1Hz
Rated data
Status indicator/Free wheel diode/Reverse volt. prot. LED red/No/available
Ambient temp., fitted w. distance -25 °C…+40 °C
Storage temperature -40 °C…+60 °C
Climate 40°C/93% rel. humidity without condensation
Approvals CE
Insulation coordinates (EN 50 178)
Standards EN 50178
Rated voltage 250V
Impulse withstand voltage 4 kV
Creepage and clearance path input - output 3mm
Overvoltage category III
Pollution severity 2
Secure separation acc. to VDE 0106 Part 101 No
Dimensions Screw connection Tension clamp connection
Clamping range (rating- / min. / max.) mm22.5 / 0.5 / 4
Length x width x height mm 70.0 / 25.0 / 68.0
Information
Ordering data
Ordering data
Complete module
Screw connection Type
Order No.
Tension clamp connection Type
Order No.
Ordering data
Spare relay, pluggable
Type
Order No.
Input
Rated voltage
Rated current AC
Rated current DC
Power rating
Oper.-/drop-out volt. AC-coil
Oper.-/drop-out volt. DC-coil
Pull-in curr./release curr. AC-coil
Pull-in curr./release curr. DC-coil
Information
12VDC 2CO
12 Vdc +/- 10 %
50mA
0.6W
11V
-/9.5mA
RS 32 12VDC LD LP 2U
9406021001
24VDC 2CO
24 Vdc +/- 10 %
25mAdc
0.6W
21.5V
-/5mA
RS 32 24VDC LD LP 2U
9406121001
48VDC 2CO
48 Vdc +/- 10 %
12mAdc
0.6W
43V
-/2mA
RS 32 48VDC LD LP 2U
9406321001
60VDC 2CO
60 Vdc +/- 10 %
10mAdc
0.6W
54V
-/1.5mA
RS 32 60VDC LD LP 2U
9406521001
SSB_K008-K059 22.10.2003 8:35 Uhr Seite K.34
K
Relay coupler
RS-SERIES - RS 32
2 change over contacts, UC input
A
3
40 50 60 70
4
2
1
20 30 °C
10
A1
A2
A2
12 14 22 24
11 21
V
Output
Max. switching voltage AC/Continuous current 250V/4A
Min. switching power 10V/100mA
Response time / Release time 13ms/10ms
Contact base material AgNi 0.15 gold flashed
Mechanical endurance >30x10^6 switching cycles
Max. switching frequency at rated load 0.1Hz
Rated data
Status indicator/Free wheel diode/Reverse volt. prot. LED red/No/not available
Ambient temp., fitted w. distance -25 °C…+40 °C
Storage temperature -40 °C…+60 °C
Climate 40°C/93% rel. humidity without condensation
Approvals CE
Insulation coordinates (EN 50 178)
Standards EN 50178
Rated voltage 250V
Impulse withstand voltage 4 kV
Creepage and clearance path input - output 3mm
Overvoltage category III
Pollution severity 2
Secure separation acc. to VDE 0106 Part 101 No
Dimensions Screw connection Tension clamp connection
Clamping range (rating- / min. / max.) mm22.5 / 0.5 / 4
Length x width x height mm 70.0 / 25.0 / 68.0
Information
Ordering data
Ordering data
Complete module
Screw connection Type
Order No.
Tension clamp connection Type
Order No.
Ordering data
Spare relay, pluggable
Type
Order No.
Input
Rated voltage
Rated current AC
Rated current DC
Power rating
Oper.-/drop-out volt. AC-coil
Oper.-/drop-out volt. DC-coil
Pull-in curr./release curr. AC-coil
Pull-in curr./release curr. DC-coil
Information
24VUC 2CO
24 Vuc +/- 10 %
28mAac
18mAdc
0.6W // 0.9VA
21.5V
-/2.5mA
-/4.5mA
RS 32 24VUC LD LP 2U
9406221001
48VUC 2CO
48 Vuc +/- 10 %
18mAac
12mAdc
0.6W // 0.9VA
43V
-/4.5mA
-/2mA
RS 32 48VUC LD LP 2U
9406421001
115VUC 2CO
115 Vuc + 5 / - 15%
5mA
5 mA
0.5W // 0.6VA
98V
-/1.5mA
-/1mA
RS 32 115VUC LD LP 2U
9406621001
230VUC 2CO
230 Vuc + 5 / - 15%
4.3mA
4.3mA
1W //1VA
195V
-/2mA
-/1.2mA
RS 32 230VUC LD LP 2U
9406721001
SSB_K008-K059 22.10.2003 8:35 Uhr Seite K.35
K
Relay coupler
RS-SERIES - RS 32
2 change over contacts, multiple voltage in-
put
A
3
40 50 60 70
4
2
1
20 30 °C
10
A1
A2
A2
12 14 22 24
11 21
Output
Max. switching voltage AC/Continuous current 250V/4A
Min. switching power 10V/100mA
Response time / Release time 13ms/10ms
Contact base material AgNi 0.15 gold flashed
Mechanical endurance >30x10^6 switching cycles
Max. switching frequency at rated load 0.1Hz
Rated data
Status indicator/Free wheel diode/Reverse volt. prot. LED red/No/not available
Ambient temp., fitted w. distance -25 °C…+40 °C
Storage temperature -40 °C…+60 °C
Climate 40°C/93% rel. humidity without condensation
Approvals CE
Insulation coordinates (EN 50 178)
Standards EN 50178
Rated voltage 250V
Impulse withstand voltage 4 kV
Creepage and clearance path input - output 3mm
Overvoltage category III
Pollution severity 2
Secure separation acc. to VDE 0106 Part 101 No
Dimensions Screw connection Tension clamp connection
Clamping range (rating- / min. / max.) mm22.5 / 0.5 / 4
Length x width x height mm 70.0 / 25.0 / 68.0
Information
Ordering data
Ordering data
Complete module
Screw connection Type
Order No.
Tension clamp connection Type
Order No.
Ordering data
Spare relay, pluggable
Type
Order No.
Input
Rated voltage
Rated current AC
Rated current DC
Power rating
Oper.-/drop-out volt. AC-coil
Oper.-/drop-out volt. DC-coil
Pull-in curr./release curr. AC-coil
Pull-in curr./release curr. DC-coil
Information
24-48VUC 2CO
24 Vuc // 48 Vuc +/- 10 %
28mA / 22mA
18mA / 20mA
0.6W // 0.9VA
21.5V/43V
-/3mA // -/4.5mA
-/5mA // -/2mA
RS 32 24-48VUC LD LP 2U
1122661001
115-230VUC 2CO
115 Vuc // 230 Vuc + 5 / - 15%
5.6mA/5.3mA
5.4mA/5mA
1W // 1VA
98V/195V
-/1.5mA // -/2mA
-/1mA // -/1.2mA
RS 32 115-230VUC LD 2U
1122761001
SSB_K008-K059 22.10.2003 8:35 Uhr Seite K.36
Relay coupler
K.38
K
24 Vdc 24 Vac/dc 48 Vdc 115 Vac/dc 230 Vac
0.45 W ––––
0.75 W 0.45 W 0.75 W
–––––
0.7 VA 0.6 VA 1.2 VA
12 mA––––
23 mA 12 mA 14 mA 5 mA
–––––
16.5 mA 6 mA 4 mA
2 mA 1.5 mA 1 mA
250 V 250 V 250 V 250 V 250 V
6 A6 A6 A6 A3 A
8 ms
10 ms / 10 ms
12 ms 8 ms / 10 ms 10 ms
7 ms
15 ms / 20 ms
11 ms 5 ms / 8 ms 10 ms
3 ms
8 A
2000 VA
250 mW/10 mA
AgNi 90/10, AgNi0,15, gold-flashed
> 30 x 106switching cycles
> 5 x 105switching cycles
> 7 x 105switching cycles
–40°C…+60°C
–25°C…+50°C
III
2
0.5…2.5 mm2
Rated data
Input voltage
Nominal consumption soldered relay
plugged relay
Nominal consumption soldered relay
plugged relay
Pull-in current soldered relay
plugged relay
Pull-in current soldered relay
plugged relay
Release current of relay (at 20°C)
Output voltage max.
Continuous current
Derating curve
a = arranged on mounting rail in horizontal row without spacing
b = arranged on mounting rail in horizontal row
with 20 mm spacing
Continuous
current
Ambient temperature
Typical switch-on times
Pick-up delay ( ac / dc)
Release delay ( ac / dc)
Duration of bounce
Switch-on current
Switch-on power under ohmic load
Min. switching power / switching current
Contact material
Service life mechanical
24 Vdc, 1A, ohmic load
230 Vac, 3A, ohmic load
Storage temperature
Ambient temperature
Insulation coordination acc. to EN 50 178
Overvoltage category
Pollution severity
Dimensions
Conductor cross-sectional area (screw connection)
RS-SERIES – with RSM multiple interface
4 relays
soldered or plugged
with one change-over contact each RSM 4 R / RSM 4 RS
8 relays
soldered or plugged
RSM 8 R / RSM 8 RS
16 relays
soldered or plugged
RSM16R/RSM16RS
Technical data
LEDs red, other colours on request
Mounting feet can also be mounted turned at an angle
of 180°
SSB_K038-K039_GB 24.10.2003 16:17 Uhr Seite K.38
Connection technology
Input Flat band connection Multiple plug with locking
acc. to DIN 41651/part 1 and 2
Output Screw connection
Input Screw connection • Plugged relay
Screw connection and multiple plug
acc. to IEC 603-1/DIN 41651
• Relay soldered
Multiple plug
acc. to IEC 603-1/DIN 41651
Output Screw connection
4 relays 8 relays 16 relays
RSM 4 R/RS RSM 8 R/RS RSM 16 R/RS
Input voltage (B = 75 mm) (B = 145 mm) (B = 285 mm)
24 Vdc, switching minus Relay soldered 1100061001 1100161001
24 Vdc, switching plus Relay pluggable 11133610011)11135610011)11137610011)
Relay soldered 1112361001 1107761001 1107861001
24 Vdc, switching minus Relay pluggable 11134610011)11136610011)11138610011)
Relay soldered 1112661001
24 Vac/dc Relay pluggable 1173461001 1173561001 1173661001
48 Vdc, switching plus Relay pluggable 1113961001 1114161001 1114361001
115 Vac/dc Relay pluggable 1114561001 1114661001 1114761001
230 Vac Relay pluggable 1114861001 1114961001 1115061001
1) approved by Germanisch Lloyd
For RSM ... R/RS, 24 V
For RSM ... R/RS, 48 V
For RSM ... R/RS, 115 V and 230 V
Relay coupler
K.39
K
1
1
1
11 14 12
2
2
2
21 24 22
3
3
3
31 34 32
4
4
4
41 44 42
8
8
81 84 82
16 19/+20/-
9/+10/-
+ -
161 164 162
RSM 16
RSM 8
RSM 4
RS-SERIES – with RSM multiple interface
Order data
Input voltage Contact material Remarks Order no.
24 Vdc AgNi 90/10 RT 314024 with clip 8630780000
AgNi 90/10 RT 314024 without clip 4058480000
48 Vdc AgNi 90/10 RT 314048 with clip 8630790000
AgNi 90/10 RT 314048 without clip 4058740000
115 Vdc AgNi 90/10 RT 314110 with clip 8630770000
AgNi 90/10 RT 314110 without clip 4058500000
Spare relays (for plugging)
DC voltage, positive-switching
joint minus potential,
plus connected up
1
1
1
2
2
2
21 24 22
3
3
3
31 34 32
4
4
4
41 44 42
8
8
81 84 82
16
161 164 162
RSM 16
RSM 8
RSM 4
11 14 12
NN
N
N
DC/AC/AC voltage DC voltage, switching minus (negative-switching)
joint plus potential,
minus connected up
1
1
1
11 14 12
2
2
2
21 24 22
3
3
3
31 34 32
4
4
4
41 44 42
8
8
81 84 82
16 19/-20/+
9/-10/+
- +
161 164 162
RSM 16
RSM 8
RSM 4
SSB_K038-K039_GB 24.10.2003 16:17 Uhr Seite K.39
K
Relay coupler
MCZ-Series
MiniConditioner MCZ R
Module can be used as an universal interface between con-
trol and actuator for switching small and medium loads
The pluggable cross-connection in input and output mini-
mizes the effort to wire
• Width 6 mm, low height
24 Vuc / 230 Vac
120 Vac
432
5
11
12 14
0 V
+ 24 V
DC-Input
432
1
5
11
12 14
0 V
24 V
43
5
11
12 14
2
1
0 V
120 V
Output
Max. switching voltage AC/Continuous current 400V/6A
Min. switching power 12V/100mA
Response time / Release time 4.5ms/10ms
Contact base material AgSnO2
Mechanical endurance 20x10^6 switching cycles
Max. switching frequency at rated load 0.1Hz
Rated data
Status indicator/Free wheel diode/Reverse volt. prot. LED green/Yes/available
Ambient temp., fitted w. distance -25 °C…+50 °C
Storage temperature -40 °C…+60 °C
Climate 40°C/93% rel. humidity without condensation
Approvals CE, UL, CSA, GL
Insulation coordinates (EN 50 178)
Standards EN 50178
Rated voltage 300 V
Impulse withstand voltage 6 kV
Creepage and clearance path input - output => 5.5mm
Overvoltage category III
Pollution severity 2
Secure separation acc. to VDE 0106 Part 101 Yes
Dimensions Screw connection Tension clamp connection
Clamping range (rating- / min. / max.) mm21.5 / 0.5 / 2.5
Length x width x height mm 91.0 / 6.0 / 63.2
Information
6
5
4
3
2
1
2
0
2
5
30
35
40
40
45
45
50
50
°
C
C
I
L
/
/A
L
/A
L
D
eratin
g
curv
e
rowed without clearances on the mountin
g
rai
l
300
2
00
1
00
2
5
/
U/
Vd
c
p
rohibite
d
a
r
ea
1
2
3
4
5
6
I
L
/Adc
L
/Adc
L
Limit dia
g
ra
m
rowed with 20 mm spacin
g
on the mountin
g
rai
l
Applications
SSB_K008-K059 22.10.2003 8:54 Uhr Seite K.40
K
Relay coupler
MCZ-Series
MiniConditioner MCZ R
Ordering data
Input
Rated voltage
Rated current AC
Rated current DC
Power rating
Oper.-/drop-out volt. AC-coil
Oper.-/drop-out volt. DC-coil
Pull-in curr./release curr. AC-coil
Pull-in curr./release curr. DC-coil
Ordering data
Complete module
Screw connection Type
Order No.
Tension clamp connection Type
Order No.
Ordering data
Spare relay, pluggable
Type
Order No.
Information
24VDC 1CO
24 Vdc +/- 20 %
6.3mA
156mW
12V19V/4V5.5V
5.7mA
MCZ R 24VDC
8365980000
24VUC 1CO
24 Vuc +/- 10 %
10.8mA
6.1mA
160mVA / 150mW
approx.17V/approx.7V
approx.19V/approx.4V
9mA/5mA
MCZ R 24VUC
8390590000
24VDC 1CO AU
24 Vdc +/- 20 %
6.3mA
156mW
12V19V/4V5.5V
5.7mA
MCZ R 24VDC
8442960000
60VDC 1CO
60 Vdc +/- 20 %
3mA
180mW
approx.38V/approx.14V
2.7mA
MCZ R 60VDC
8470380000
Ordering data
Input
Rated voltage
Rated current AC
Rated current DC
Power rating
Oper.-/drop-out volt. AC-coil
Oper.-/drop-out volt. DC-coil
Pull-in curr./release curr. AC-coil
Pull-in curr./release curr. DC-coil
Ordering data
Complete module
Screw connection Type
Order No.
Tension clamp connection Type
Order No.
Ordering data
Spare relay, pluggable
Type
Order No.
Information
110VDC 1CO
110 Vdc +/- 10 %
2.85mA
340mW
approx.68V/approx.19V
1.6mA/0.4mA
MCZ R 110VDC
8467470000
120VAC 1CO
120 Vac -15 %/ +10 %
7mA
0.85VA
approx.7V/approx.22V
4mA/1.3mA
MCZ R 120VAC
8420880000
230VAC 1CO
230 Vac +/- 10 %
9.5mA
2.1VA
approx.115V/approx.60V
5mA/2.5mA
MCZ R 230VAC
8237710000
SSB_K008-K059 22.10.2003 8:54 Uhr Seite K.41
K
Relay coupler
DK-SERIES
1 NO contact, input bottom
Input
1
A1 +
2
A2 -
Output
3
13
4
14
Output
Max. switching voltage AC/Continuous current 100V/500mA
Min. switching power 1 V / 1 mA
Response time / Release time typ.0.72.5ms/0.22ms
Contact base material RH/RU
Mechanical endurance 10^9 switching cycles
Max. switching frequency at rated load 200Hz
Rated data
Status indicator/Free wheel diode/Reverse volt. prot. LED green/Yes/available
Ambient temp., fitted w. distance -25 °C+40 °C
Storage temperature -40 °C+60 °C
Climate 40°C/93% rel. humidity without condensation
Approvals CE
Insulation coordinates (EN 50 178)
Standards EN 50178
Rated voltage 150 V
Impulse withstand voltage 1.5 kV
Creepage and clearance path input - output =>3mm
Overvoltage category III
Pollution severity 2
Secure separation acc. to VDE 0106 Part 101 No
Dimensions Screw connection Tension clamp connection
Clamping range (rating- / min. / max.) mm24 / 0.5 / 4
Length x width x height mm 77.0 / 6.0 / 62.0
Information AP DK4: 0687560000
Ordering data
Ordering data
For TS 32 Type
Order No.
For TS 35 Type
Order No.
Ordering data
Type
Order No.
Input
Rated voltage
Rated current AC
Rated current DC
Power rating
Oper.-/drop-out volt. AC-coil
Oper.-/drop-out volt. DC-coil
Pull-in curr./release curr. AC-coil
Pull-in curr./release curr. DC-coil
Information
5 VDC 1A
5 Vdc +/- 5 %
12.5mA
65mW
4.4V
11.8mA
DKR 32 5VDC 1A
8019600000
DKR 35 5VDC 1A
8019610000
12VDC 1A
12 Vdc +/- 10 %
12mA
144mW
9V
10mA
DKR 35 12VDC 1A
8171100000
24VUC 1A
12 Vuc +/- 10 %
15mA
12mA
144mW
12V
11V
6.3mA
3.8mA
DKR 32 24VUC 1A
8008110000
DKR 35 24VUC 1A
8016610000
24VDC 1A
24 Vdc +/- 20 %
9.3mA
225mW
11V
7.5mA
DKR 32 24VDC 1A
8016620000
DKR 35 24VDC 1A
8008170000
SSB_K008-K059 22.10.2003 8:54 Uhr Seite K.42
K
Relay coupler
DK-SERIES
1 NO contact, input top
Output
3
A1 +
24 V=
4
A2 -
Input
1
13
3
14
Output
Max. switching voltage AC/Continuous current 100V/500
Min. switching power 1 V / 1 mA
Response time / Release time typ.0.72.5ms/0.22ms
Contact base material RH/RU
Mechanical endurance 10^9 switching cycles
Max. switching frequency at rated load 25Hz
Rated data
Status indicator/Free wheel diode/Reverse volt. prot. LED green/Yes/available
Ambient temp., fitted w. distance -25 °C+40 °C
Storage temperature -40 °C+60 °C
Climate 40°C/93% rel. humidity without condensation
Approvals CE
Insulation coordinates (EN 50 178)
Standards EN 50178
Rated voltage 150 V
Impulse withstand voltage 1.5 kV
Creepage and clearance path input - output =>3mm
Overvoltage category III
Pollution severity 2
Secure separation acc. to VDE 0106 Part 101 No
Dimensions Screw connection Tension clamp connection
Clamping range (rating- / min. / max.) mm24 / 0.5 / 4
Length x width x height mm 77.0 / 6.0 / 62.0
Information AP DK4: 0687560000
Ordering data
Ordering data
For TS 32 Type
Order No.
For TS 35 Type
Order No.
Ordering data
Type
Order No.
Input
Rated voltage
Rated current AC
Rated current DC
Power rating
Oper.-/drop-out volt. AC-coil
Oper.-/drop-out volt. DC-coil
Pull-in curr./release curr. AC-coil
Pull-in curr./release curr. DC-coil
Information
24 VDC 1A
24 Vdc +/- 20 %
9.3mA
225mW
11V
3.75mA
DKR 35 24VDC 1A
8215620000
SSB_K008-K059 22.10.2003 8:54 Uhr Seite K.43
K
Relay coupler
DK-SERIES
1 change-over contact, input bottom
Ein/In
1
A1 +
24V=
2
A2 -
Aus/Out
3
5
4
6
14
12
11
Output
Max. switching voltage AC/Continuous current 250V/6A
Min. switching power 10 V / 100 mA
Response time / Release time 6ms/15ms ac;8ms dc
Contact base material AgSnO2
Mechanical endurance 2x10^7 switching cycles
Max. switching frequency at rated load 20
Rated data
Status indicator/Free wheel diode/Reverse volt. prot. LED green/Yes/not available
Ambient temp., fitted w. distance -40°C+60°C
Storage temperature -40 °C+60 °C
Climate 40°C/93% rel. humidity without condensation
Approvals
Insulation coordinates (EN 50 178)
Standards EN 50178
Rated voltage 300 V
Impulse withstand voltage 4 kV
Creepage and clearance path input - output =>8mm
Overvoltage category III
Pollution severity 2
Secure separation acc. to VDE 0106 Part 101 No
Dimensions Screw connection Tension clamp connection
Clamping range (rating- / min. / max.) mm24 / 0.5 / 4
Length x width x height mm 77.0 / 6.0 / 62.0
Information End plate
Ordering data
Ordering data
For TS 32 Type
Order No.
For TS 35 Type
Order No.
Ordering data
Type
Order No.
Input
Rated voltage
Rated current AC
Rated current DC
Power rating
Oper.-/drop-out volt. AC-coil
Oper.-/drop-out volt. DC-coil
Pull-in curr./release curr. AC-coil
Pull-in curr./release curr. DC-coil
Information
24VUC 1CO
24 Vuc +/- 20 %
9mA
7mA
220mVA/180mW
18V
19V
7mA
5.5mA
DKR DK5 24VUC 1U
9454910000
DKR DK5 24VUC 1U
9454910000
24VDC 1CO
24 Vdc +/- 20 %
11.5mA
384mW
19V
9mA
DKR 35 24VDC 1U
8181980000
24VUC 1CO
24 Vuc +/- 20 %
20mA
16mA
480mW /400mW
18V
18V
12.8mA
11.5mA
DKR 35 24VUC 1U
8181970000
SSB_K008-K059 22.10.2003 8:54 Uhr Seite K.44
Relay coupler
K.46
K
EG SERIES
1 NCC, 1 NOC, 1 change-over contact
Also with hard gold-plated contacts
With combination foot for TS 32, TS 32 and TS 35
(clip-in base for plug-in) change-over contacts
10 mm wide
Screw connection
A 1
A 2
Output
Max. switching voltage AC / constant current 250 V / 5 A
Min. switching power 100 mW / 10 mA
hard gold-plated contacts 40 µW
Response time/release time 8 ms / 6 ms
Contact base material AgNi 0.15 gold-flashed
hard gold-plated contacts AgNi 0.15 / 5 µ Au
Mechanical service life > 15 x 106switching cycles
Max. switching frequency at rated load 0,1 Hz
Nominal data
Status indicator/recovery diode LED green / yes
Ambient temperature arranged in horizontal row with spacing –25 °C ... +60 °C
Lagertemperatur –40 °C … +60 °C
Insulation coordination (EN 50 178)
Standards EN 50178
Rated voltage 300 V
Rated impuls voltage 8 kV
Creepage and clearance path input-output 8 mm
Overvoltage category III
Pollution severity 2
Protective separation acc. to VDE 0106 part 101 DIN VDE 0106
Main-line wiring diagram
Main-line wiring diagram
1 NOC, 1 NCC 1 change-over contact
Clamping range (nom./min/max) mm21.5 x 0.5 x 1.5 1.5 x 0.5 x 1.5
Length x width x height mm 44.0 x 10.0 x 96.0 95.0 x 10.0 x 93.0
Remarks
Constant current
Ambient temperature
a = arranged on mounting rail in horizontal row without spacing
b = arranged on mounting rail in horizontal row with 20 mm spacing
Technical data
SSB_K046-K047_GB 10.10.2003 9:44 Uhr Seite K.46
Relay coupler
K.47
K
EG SERIES
1 NOC, 1 NCC, 1 change-over contact
Order data
Input
Rated voltage
Nominal power
Switch-on current, max.
Order data
with combination foot
1 NOC Type
Order no.
1 NCC Type
Order no.
Order data, pluggable
(order clip-in base separately)
1 change-over contact Type
Order no.
1 clip-in base Type
Order no..
12 Vac/dc
12 Vac/dc, +15%, –10 %
320 mW +20% –10%
120 mA
EGR EG 7
8092310000
EGR EG 7
8092320000
RST EG 7
8216550000
RS EG 7
8193830000
24 Vdc
24 Vdc +15 % –10 %
280 mW +20% –10%
12 mA
EGR EG 7
8216520000
EGR EG 7
8216530000
RST EG 7
8216570000
RS EG 7
8193830000
24 Vac/dc
24 Vac/dc +15 % –10 %
280 mW +20% –10%
240 mA
EGR EG7
8092340000
EGR EG7
8092350000
RST EG 7
8216580000
RS EG 7
8193830000
115Vac/dc
115 Vac/dc + 15 % –10 %
330 mW +15% –10%
160 mA
EGR EG7
8092430000
EGR EG7
8092440000
RST EG 7
8216610000
RS EG 7
8193830000
Order data
Input
Rated voltage
Nominal power
Switch-on current, max.
Order data
with combination foot
1 NOC Type
Order no.
1 NCC Type
Order no.
Order data, pluggable
(order clip-in base separately)
1 change-over contact Type
Order no.
1 clip-in baseType
Order no..
Contacts
hard gold-plated
230 Vac
230 Vac +15 % –10 %
280 mW +15% –10%
185 mA
EGR EG 7
8092460000
EGR EG 7
8092470000
RST EG 7
8216620000
RS EG 7
8193830000
24 Vdc
24 Vdc +15% –10%
280 mW +20% –10%
12 mA
EGR EG 7
8147120000
EGR EG 7
8147140000
RST EG 7
8216560000
RS EG 7
8193830000
230 Vac
230 Vac +15% –10%
280 mW +15% –10%
185 mA
EGR EG 7
8178200000
RST EG 7
8216630000
RS EG 7
8193830000