4
Switch-mode power supplies
Subject to technical changes • 1/07-LIT0701
connectPower 1-phase
INSTAPOWER
Technical data
Input
Input voltage
Input current
Frequency
Starting current limit
Input fuse low fuse
Overvoltage Protection
Output
Output voltage
Output current
Max. output power
Residual ripple
Overload protection
Max. capacitance at output
Mains failure bridge-over time
Control at 10…100% load
Parallel operation
Status display
General data
Operation temperature
Storage temperature
Relative humidity
Isolation input / output
Standards
EMC standards
Approvals
Mounting position
Assembly
Dimensions
Clamping range (rating- / min. / max.) mm2
Length x width x height mm
Note
Ordering data
CP SNT 48W 12V 4A
Eingang
85…264 VAC; 110…370 VDC
500 mA @ 230 VAC
50/60 Hz
Fuse 2.5 A (T) / 250 V
Varistor
limited
Ausgang
9…15 VDC (adjustable via potentiometer)
4 A
48 W
120 mVss const. from
105%…150% max. rated output power,
automatic restart
> 75%
> 50 ms @ 230 VAC
1%
max. 3 devices (nominal voltages must
be adjusted to +/– 20 mv)
LED green
–10°C…+70°C (derating from 55°C)
–20°C…+85°C
Up to 95% at 40°C, no condensation
3 kV AC
EN 60950 (SELV), EN 50178 (PELV)
EN 61000-6-2 /-3 /-4, EN 55011,
EN 55022, EN 61000-3-2 /-3
CE / UL 508 / cURus 60950 / GS
Horizontal on TS 35 mounting rail
Mount side-by-side; clearance above/below
> 30 mm
ca. 0.2 kg
Screw connection
2.5/ 0.5 / 4
62.5 x 70 x 90.5
Type Part No.
CP SNT 48W 12V 4A 8754970000
CP SNT 48W 24V 2A
Eingang
85…264 VAC; 110…370 VDC
500 mA @ 230 VAC
50/60 Hz
Fuse 2.5 A (T) / 250 V
Varistor
limited
Ausgang
15…28 VDC (adjustable via potentiometer)
2 A
48 W
120 mVss const. from
105%…150% max. rated output power,
automatic restart
> 78%
> 50 ms @ 230 VAC
1%
max. 3 devices (nominal voltages must
be adjusted to +/– 20 mv)
LED green
–10°C…+70°C (derating from 55°C)
–20°C…+85°C
Up to 95% at 40°C, no condensation
3 kV AC
EN 60950 (SELV), EN 50178 (PELV)
EN 61000-6-2 /-3 /-4, EN 55011,
EN 55022, EN 61000-3-2 /-3
CE / UL 508 / cURus 60950 / GS
Horizontal on TS 35 mounting rail
Mount side-by-side; clearance above/below
> 30 mm
ca. 0.2 kg
Screw connection
2.5/ 0.5 / 4
62.5 x 70 x 90.5
Type Part No.
CP SNT 48W 24V 2A 8739140000
CP SNT 48W 48V 1A
85…264 VAC; 110…370 VDC
500 mA @ 230 VAC
50/60 Hz
Fuse 2.5 A (T) / 250 V
Varistor
limited
46…55 VDC (adjustable via potentiometer)
1 A
48 W
120 mVss const. from
105%…150% max. rated output power,
automatic restart
> 80%
> 50 ms @ 230 VAC
1%
max. 3 devices (nominal voltages must
be adjusted to +/– 20 mv)
LED green
–10°C…+70°C (derating from 55°C)
–20°C…+85°C
Up to 95% at 40°C, no condensation
3 kV AC
EN 60950 (SELV), EN 50178 (PELV)
EN 61000-6-2 /-3 /-4, EN 55011,
EN 55022, EN 61000-3-2 /-3
CE / UL 508 / cURus 60950 / GS
Horizontal on TS 35 mounting rail
Mount side-by-side; clearance above/below
> 30 mm
ca. 0.2 kg
Screw connection
2.5/ 0.5 / 4
62.5 x 70 x 90.5
Type Part No.
CP SNT 48W 48V 1A 8879230000