HEAVYCON male insert, for 690 V(III/3), with 16 N/O contacts and 2 switching contacts, screw connection
The illustration shows a combination
of versions HC-HV -10-EBUC, -10-
EBUS, -10-ESTC and -10-ESTS
Key commercial data
Packing unit 1 pc
GTIN
Weight per Piece (excluding packing) 117.0 GRM
Custom tariff number 85366990
Country of origin Germany
Technical data
General
Note For HEAVYCON-ADVANCE housing of B24 type and HEAVYCON
housing of HV10 type The switching contacts are 2 mm lagging.
Connection method Screw connection
Tightening torque 0.5 Nm
Pollution degree 3
Surge voltage category III
Constructional and testing regulations DIN VDE 0627/86
DIN VDE 0110/02.79
DIN VDE 0110-1/04.97
IEC 60664-1, DIN IEC 60512
IEC 60352
https://www.phoenixcontact.com/us/products/1773433
2/4/14Page2/5
Contact insert-HC-HV 16-ESTS-1773433
Technical data
General
Number of positions 16+2+PE
Insertion/withdrawal cycles ≥ 500
Design HV16
Connection in acc. with standard IEC / EN
Conductor cross section 0.5 mm² ... 2.5 mm²
Connection cross section AWG 20 ... 14
Stripping length of the individual wire 7 mm (N/O contacts; with ferrule inserts use inserts of 10 mm length.)
7 mm (control contacts)
Assembly instructions When using a ferrule, the wire protection in the terminal point must be
removed and a 10 mm long ferrule must be used.
Ambient conditions
Ambient temperature (operation) -40 °C ... 125 °C (including heating up of contacts)
Material data
Inflammability class according to UL 94 V0
Contact material Copper alloy
Contact surface material Ag
Contact carrier material PA
Electrical characteristics
Rated voltage (III/3) Power 400 V (Conductor-PE)
(250 V control contacts)
Power 690 V (Conductor-Conductor)
Rated surge voltage 6 kV (N/O contacts)
4 kV (control contacts)
Rated current 16 A
Classifications
eCl@ss
eCl@ss 4.0 27140816
eCl@ss 4.1 27140816
eCl@ss 5.0 27143424
eCl@ss 5.1 27143424
eCl@ss 6.0 27143424
eCl@ss 7.0 27440209
eCl@ss 8.0 27440209
https://www.phoenixcontact.com/us/products/1773433
2/4/14Page3/5
Contact insert-HC-HV 16-ESTS-1773433
Classifications
ETIM
ETIM 2.0 EC000438
ETIM 3.0 EC000438
ETIM 4.0 EC000438
ETIM 5.0 EC000438
UNSPSC
UNSPSC 6.01 30211923
UNSPSC 7.0901 39121522
UNSPSC 11 39121522
UNSPSC 12.01 39121522
UNSPSC 13.2 39121522
Approvals
Approvals
Approvals
GOST
Ex Approvals
Approvals submitted
Approval details
GOST
Drawings
https://www.phoenixcontact.com/us/products/1773433
2/4/14Page4/5
Contact insert-HC-HV 16-ESTS-1773433
Schematic diagram
View termination side