D1U2-W-400-12-HA4C
54mm 1U Front End AC-DC Power Supply Converter
D1U2-W-400-12-HA4C.A04 Page 1 of 6
www.murata-ps.com
www.murata-ps.com/support
For full details go to
www.murata-ps.com/rohs
 
ORDERING GUIDE
Part Number Power Output
High Line AC
Power Output
Low Line AC
Main
Output
Standby
Output Airfl ow
D1U2-W-400-12-HA4C 400W 400W 12V 5V Back to front
INPUT CHARACTERISTICS
Parameter Conditions Min. Nom. Max. Units
Voltage Operating Range 90 115/230 264 Vac
Frequency 47 50/60 63 Hz
Turn-on Voltage Ramp up 85 Vac
Turn-off Voltage Ramp down 85
Maximum current at Vin=100Vac 400W 5 Arms
Inrush Current Cold start between 0 to 200msec 30 Apk
Power Factor At 230Vac, full load 0.99
Effi ciency (100Vac) including fan load
35% load 80
%50% load 85
100% load 85
OUTPUT VOLTAGE CHARACTERISTICS
Output
Voltage Parameter Conditions Min. Typ. Max. Units
12V
Voltage Set Point 12.0 Vdc
Line and Load Regulation 11.8 12.2
Ripple Voltage & Noise120MHz Bandwidth 120 mV p-p
Output Current (230Vac) 0 33.3 A
Load Capacitance 0 15,000 µF
5VSB
Voltage Set Point 5.0 Vdc
Line and Load Regulation 4.85 5.15
Ripple Voltage & Noise120MHz Bandwidth 50 mV p-p
Output Current 0 3 A
Load Capacitance 0 500 µF
1 Ripple and noise are measured with 0.1 µF of ceramic capacitance and 10 µF of tantalum capacitance on each of the
power supply outputs. A short coaxial cable with 50 scope termination is used.
FEATURES
400W output power
12V main output
5V standby output of 15W
1U height: 2.15"x13.67"x1.58"
8.6 Watts per cubic inch density
Effi ciency 85% at full load, 100Vac and 50°C
N+1 redundancy capable,
including hot plugging (up to 4 in parallel)
Active current sharing on 12V main output,
ORing FET
Overvoltage, overcurrent,
overtemperature protection
Internal cooling fan (variable speed)
PSMI and SMbus / I2C interface with bicolor
LED status indicators
RoHS compliant
PRODUCT OVERVIEW
The D1U2-W-400-12-HA4C is a 400 watt, power factor corrected front end supply with a 12V main output and a 5V
(15W) standby. It features active current sharing and up to 4 supplies maybe operated in parallel. The supply may be hot
plugged, it recovers from overtemperature faults, and has status LEDs on the front panel in addition to logic and PSMI
status signals. The supply comes in a low profi le 1U package and has >8W/cubic inch power density, making it ideal for
delivering reliable, effi cient power to servers, workstations, storage systems and other 12V distributed power systems.
CB
Test Certi cate
and Test Report
www.murata-ps.com
/
en
/
3d
/
acdc.htm
l
www.murata-ps.com
/
en
/
3d
/
acdc.htm
l
www.murata-
p
s.com/en/3d/acdc.htm
l
www.murata-ps.com
/
en
/
3d
/
acdc.htm
l
www.murata-
p
s.com/en/3d/acdc.htm
l
www.murata-ps.com
/
en
/
3d
/
acdc.htm
l
Available now at
www.murata-ps.com/en/3d/acdc.html
D1U2-W-400-12-HA4C
54mm 1U Front End AC-DC Power Supply Converter
D1U2-W-400-12-HA4C.A04 Page 2 of 6
www.murata-ps.com/support
OUTPUT CHARACTERISTICS
Parameter Conditions Min. Typ. Max. Units
Output Rise Monotonicity No voltage excursion
Startup Time AC ramp up 1.5 2.0 s
Transient Response 12V, 30-70% load step, 1A/s di/dt 3
%
5VSB, 30-70% load step, 0.1A/s di/dt 3
Current sharing accuracy (up to 4 in parallel) At 100% load ±10
Hot Swap Transients All outputs within regulation
Holdup Time 20 ms
ENVIRONMENTAL CHARACTERISTICS
Parameter Conditions Min. Typ. Max. Units
Storage Temperature Range -40 70 °C
Operating Temperature Range 050
Operating Humidity Noncondensing 5 90 %
Storage Humidity 595
Altitude (without derating at 55°C) 3,000 m
Shock 30G non operating
Operational Vibration 0.5G, 5 – 500 Hz
MTBF Per Telcordia SR332M1C1 @25°C 300K hrs
Safety Approvals
CSA/UL 60950-1-07-2nd Ed.
IEC 60950-1:2005 (2nd Edition) w Am. 1:2009
EN 60950-1:2006 +A11:2009 +A1:2010
CE Marking per LVD DIRECTIVE 2006/95/EC
Input Fuse Power Supply has internal 10A/250V fast blow fuse on the AC line input
Switching Frequency 90KHz for Boost PFC Converter
200KHz for Main Output Converter
Weight 2.28lbs (1.034kg)
PROTECTION CHARACTERISTICS
Output
Voltage Parameter Conditions Min. Typ. Max. Units
Overtemperature (intake) Autorestart 65 70 75 °C
12V Overvoltage Latching 14.0 14.5 V
Overcurrent Hiccup 115 130 %
5VSB Overvoltage Latching 5.7 5.9 V
Overcurrent Autorecovery 4.4 6.0 A
ISOLATION CHARACTERISTICS
Parameter Conditions Min. Typ. Max. Units
Insulation Safety Rating / Test Voltage Input to Output - Reinforced 3000 Vrms
Input to Chassis - Basic 1500 Vrms
Isolation Output to Chassis 500 Vrms
CONTROL SIGNALS
Condition LED Status
Standby - ON; Main output - OFF; AC PRESENT Blinking green
Standby - ON; Main output - ON Solid green
Main/standby output overcurrent, undervoltage, overvoltage warning Blinking yellow
FAN_FAULT; overtemperature; main/standby output overcurrent, undervoltage, overvoltage fault Yellow
D1U2-W-400-12-HA4C
54mm 1U Front End AC-DC Power Supply Converter
D1U2-W-400-12-HA4C.A04 Page 3 of 6
www.murata-ps.com/support
EMISSIONS AND IMMUNITY
Characteristic Standard Compliance
Input Current Harmonics IEC/EN 61000-3-2 Complies
Voltage Fluctuation and Flicker IEC/EN 61000-3-3 Complies
Conducted Emissions FCC 47 CFR Part 15/CISPR 22/EN55022 Class B
ESD Immunity IEC/EN 61000-4-2 Level 3 criteria A
Radiated Field Immunity IEC/EN 61000-4-3 Level 3 criteria B
Electrical Fast Transients/Burst Immunity IEC/EN 61000-4-4 Level 3 criteria A
Surge Immunity IEC/EN 61000-4-5 Level 3 criteria A
Radiated Field Conducted Immunity IEC/EN 61000-4-6 Level 3 criteria A
Magnetic Field Immunity IEC/EN 61000-4-8 3 A/m criteria B
Voltage dips, interruptions IEC/EN 61000-4-11
230Vin, 100% load, Phase 0°, Dip 100% Duration 10ms (A)
230Vin, 50% load, Phase 0°, Dip 100% Duration 20ms (VSB:A, V1:A)
230Vin, 100% load, Phase 0°, Dip 100% Duration > 20ms (VSB, V1:B)
DC OUTPUT CONNECTOR AND SIGNALS
The DC Output Connector is a TYCO MINIPAK HDL Connector TYCO P/N: 1926734-1. Mating pin sequencing shall be 12V_RTN fi rst, 12V second, signals third and PSKILL_L signal
last. PSKILL_L is the last to mate and fi rst to break and is used as a power supply output enable for the 12V rail.
Mating Part: TYCO P/N 1-1926739-8
Power Supply Output Connector Isometric and Front Views
Front Connector View Looking at Blades and Pins (view looking in at rear of power supply)
D1U2-W-400-12-HA4C
54mm 1U Front End AC-DC Power Supply Converter
D1U2-W-400-12-HA4C.A04 Page 4 of 6
www.murata-ps.com/support
DC OUTPUT CONNECTOR AND SIGNALS (continued)
POWER SUPPLY OUTPUT CONNECTOR POWER BLADE AND SIGNAL PIN ALLOCATION
Power Blade Number Signal Function Signal Direction Blade Sequencing
P1, P2, P3, P4 RTN 12V Return Output Level 3 UPM PWR
P5, P6, P7, P8 12V 12V Output Output Level 2 UPM PWR
A1 SMB_ALERT_L I2C Serial Bus Interrupt Output Level 2 Signal
A2 PSON_L Power Supply ON Input
A3 PSKILL_L Power Supply Enable Input Level 1 Signal
A4, A5 5VSB 5V Standby Voltage Output Level 2 Signal
B1 SMB_SCL I2C Serial Bus Clock Bi-directional
Level 2 SignalB2, B3 RTN Ground Output
B4, B5 5VSB 5V Standby Voltage
C1 SMB_SDA I2C Serial Bus Data / Address Bi-directional Level 2 Signal
C2, C3, C4, C5 RTN Ground Output
D1 SMB_A1 I2C Serial Bus Address Bit A1 Input
Level 2 Signal
D2 RTN Ground Output
D3 12LS 12V Current Share Line Bi-directional
D4 12V_RS- 12V Remote Sense Negative Input
D5 12V_RS+ 12V Remote Sense Positive
E1 SMB_A0 I2C Serial Bus Address Bit A0 Input
Level 2 Signal
E2 RTN Ground
Output
E3 PWOK_H Power OK Status Bit
E4 FF1_H Fan Fail #1 Status Output
E5 FF2_H Fan Fail #2 Status Output
View into mating face of 25S8P MINIPAK HDL Plug
Signal contacts: choice of Level 1 (L1) or Level 2 (L2)
Power contacts: choice of Level 2 (L2) or Level 3 (L3)
Column:
Row:
e
d
c
b
a
1234512345678
D1U2-W-400-12-HA4C
54mm 1U Front End AC-DC Power Supply Converter
D1U2-W-400-12-HA4C.A04 Page 5 of 6
www.murata-ps.com/support
WIRING DIAGRAM
CURRENT SHARING NOTES
12V Output: Current sharing is achieved using the active current share method. (See wiring diagram section for connection details.) The total combined load must be below
400W at startup. Startup of parallel power supplies is not internally synchronized. It is recommended that the paralleled power supplies be turned on at the same time (with their
PSON_L signals). Current sharing can be achieved with or without remote sense connected to the common load.
5VSB Output: 5VSB outputs can be tied together for redundancy but total combined output power must not exceed 15W. The 5VSB output has internal ORing MOSFET for
additional redundancy / internal short protection.
Up to four units can be paralleled together. Outputs of AC input units (D1U2-W-400) and DC input units (D1U2-D-400) can be paralleled together. Please consult your Murata sales
representative if operation with more than four units in parallel is needed.
DC out return
+Remote Sense
-Remote Sense
+DC outD5
P5-P8
P1-P4
D4
- Dotted lines show optional remote sense connections.
Optional remote sense lines can be attached to a load that is a distance
away from the power supply to improve regulation at the load.
D1U2 12V load
A2
B2, B3, C2-C5, D2, E2, E5
A4, A5, B4, B5
Close switch (or FET, BJT, or wire)
to turn on +DC out
+5V logic circuitry
5VSB
PSON_L
RTN
A3 PSKILL_L
D1U2
D5
P5-P8
P1-P4
D4
A4, A5, B4, B5
A2
B2, B3, C2-C5, D2, E2, E5
A3
PSON_L
PSKILL_L
D3 12LS D3
RTN
+DC out
DC out return
-Remote Sense
12LS
5VSB
+Remote Sense
D1U2-W-400-12-HA4C
54mm 1U Front End AC-DC Power Supply Converter
D1U2-W-400-12-HA4C.A04 Page 6 of 6
www.murata-ps.com/support
Murata Power Solutions, Inc. makes no representation that the use of its products in the circuits described herein, or the use of other
technical information contained herein, will not infringe upon existing or future patent rights. The descriptions contained herein do not imply
the granting of licenses to make, use, or sell equipment constructed in accordance therewith. Specifi cations are subject to change without
notice. © 2013 Murata Power Solutions, Inc.
Murata Power Solutions, Inc.
11 Cabot Boulevard, Mansfi eld, MA 02048-1151 U.S.A.
ISO 9001 and 14001 REGISTERED
This product is subject to the following operating requirements
and the Life and Safety Critical Application Sales Policy:
Refer to: http://www.murata-ps.com/requirements/
MECHANICAL DIMENSIONS
Dimensions: 2.15" x 13.67" x 1.58" [54.5mm x 347.2mm x 40.2mm]
OPTIONAL ACCESSORIES
Description Part Number
12V D1U2 Output Connector Card D1U2-12-CONC
APPLICATION NOTES
Document Number Description
TBD D1U2 Output Connector Card
TBD D1U2 Communication Protocol
AC input connector: IEC 320-C14
9.41
±0.35
0.370
±0.014
8.15
±0.35
0.321
±0.014
MATTING SURFACE
OF SIGNAL PINS FIELD
40.20
±0.50
1.583
±0.020
[1]
39.00
±0.50
1.535
±0.020
[1]
26.16
±1.00
1.030
±0.039
[1]
66.55
±0.50
2.620
±0.020
[1]
347.20
±0.50
13.669
±0.020
[1]
380.20
REF
14.969
33.00
REF
1.299
54.50
±0.50
2.146
±0.020
[1]
340.40
±0.50
13.402
±0.020
[1]
MATTING SURFACE
OF SIGNAL PINS FIELD
Airfl ow Back to Front
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Murata:
D1U2-W-400-12-HA4C