Product catalogue | Functional Electronics | Surge protection | Instrumentation and control | 3-, 2- or 1- stage protection
with tension spring connection | MCZ OVP 48 V UC
- 2 -
Interference voltage
Technical data
Limiting frequency (-3 dB) at load resistance 500 kHz 240 Ω
Rated voltage (AC/DC) 48 V
Rated voltage (DC), max. 70 V
Rated voltage (AC) 48 V
Volume resistance 2.5 Ω
Rated voltage, max. 53 V AC
Rated current 0.5 A
Rated voltage 48 V
Rated voltage (DC) 48 V
Max. continuous voltage, Uc (AC) 53 V
Operating current, Imax 0.5 A
Specification class to IEC 61643-21 D1
Lightning test current I imp (10/350 µs) 1 kA
Discharge current, max. (8/20 µs) 5 kA
Sparkover time ≤ 100 ps
Fuse, max. 0.5 A
Dimensions
Clamping range, max. 1.5 mm²
Clamping range, min. 0.5 mm²
Clamping range, nom. 1.5 mm²
Length 91 mm
Height 63.5 mm
Width 6 mm
Approvals
Approvals institutes
Classifications
ETIM 2.0 EC000943
ETIM 3.0 EC000943
eClass 4.1 27-14-11-27
eClass 5.0 27-14-11-27
eClass 5.1 27-14-11-27
Similar products
Order No. Part designation Version
8449000000 MCZ OVP CL 48VUC 0,5A Surge protection for instrumentation and control, {Reference
(AttributeDefinition) not found: pattr2500833906422}, Rated voltage:
48 V