Film Capacitors – Power Factor Correction
PhaseCap Compact capacitors
Series/Type: MKK525-D-25-02
Ordering code: B256735252A020
Date: January 2012
Version: 2
¤ EPCOS AG 2012. Reproduction, publication and dissemination of this publication, enclosures hereto and the information
contained therein without EPCOS' prior express consent is prohibited.
Content of header bars 1 and 2 of data sheet will be automatically entered in headers and footers! Please fill in the
table and then change the color to "white". This ensures that the table disappears (invisible) for the customer PDF.
Don't change formatting when entering or pasting text in the table and don't add any cell or line in and to it!
Identification/Classification 1
(header 1 + top left bar): Film Capacitors – Power Factor Correction
Identification/Classification 2
(header 2 + bottom left header bar): PhaseCap Compact capacitors
Ordering code: (top right header bar) B256735252A020
Series/Type: (top right header bar) MKK525-D-25-02
Preliminary data (optional):
(if necessary)
Department: FILM PFC PM
Date: January 2012
Version: 2
Film Capacitors – Power Factor Correction B256735252A020
PhaseCap Compact capacitors MKK525-D-25-02
FILM PFC PM January 2012
Please read Cautions and warnings and Page 2 of 10
Important notes at the end of this document.
Construction
Dielectric: Polypropylene film
Non-PCB, semi-dry biodegradable resin
Concentric winding
Wave cut
Extruded round aluminium can with stud
Provided with ceramic discharge module
Overpressure disconnector
Features
Three-phase, delta connected
Self-healing technology
Naturally air cooled (or forced air cooling)
Indoor mounting
Typical applications
For Power Factor Correction
Terminals
Optimized capacitor safety terminals
Mounting
Threaded stud at bottom of can
(max. torque for M12 = 10 Nm)
Film Capacitors – Power Factor Correction B256735252A020
PhaseCap Compact capacitors MKK525-D-25-02
FILM PFC PM January 2012
Please read Cautions and warnings and Page 3 of 10
Important notes at the end of this document.
Technical data and specifications
* Without discharge resistor ** valid for -40/C
Maximum ratings
Vmax (up to 8 h daily) 580 V AC rms / 820 V peak
Vmax (up to 1 min) 680 V AC rms / 962 V peak
Imax Up to 1.5 • IR (A) including combined effects of ha rmonics,
overvoltages and capacitance tolerance*
IS 400 • IR (A)
VTC imp 8000 Vpk (Standard 1.2/50 μs impulse )
*Care must be taken to ensure that the maxi mum permissible voltages and operating temperatures are not exceeded
Test data
VTT 1150 V AC / 50 Hz for 10 s
VTC 3000 V AC / 50 Hz for 10 s
Characteristics MKK525-D-25-02
Rated capacitance CN 3 • 96.3 μF
Tolerance –5 / +10%
Connection D (Delta)
Rated voltage VN 525 V AC rms
Rated frequency fN 50 Hz 60 Hz
Output 25.0 kvar 30.0 kvar **
Rated current IR 28 A 33 A
tan 0 (dielectric) ~0.2 W / kvar
WN 80 Ws
RS 2.75 mΩ
Ris • C 30000 s
*tan  (50 Hz)  0.45 W / kvar
Design data
Dimensions (d x h) 136 x 200 mm
Weight approx 3.2 kg
Impregnation Non PCB, semi-dry biodegradable resin
Fixing Threaded bolt M12
Max. torque (Al can stud) 10 Nm
Mounting position Any mounting position possible.
See “Maintenance and Installation Manu al” for further details.
Film Capacitors – Power Factor Correction B256735252A020
PhaseCap Compact capacitors MKK525-D-25-02
FILM PFC PM January 2012
Please read Cautions and warnings and Page 4 of 10
Important notes at the end of this document.
Max . allow able pow er loss at specific ambient Temp.
B25673A5252A020
0
5
10
15
20
25
30
15 35 55 75 95
Θ
amb
P max
Max. allowable current (rms) at specific ambient Temp.
B25673A5252A020
0
10
20
30
40
50
15 35 55 75 95
Θ
amb
I max
Max . allow able ambient Temp. at specific power loss
B25673A5252A020
15
30
45
60
75
90
0 5 10 15 20 25 30
Θ
amb
P max
Max . allow able ambient Temp. at specific current (rms)
B25673A5252A020
15
30
45
60
75
90
0 5 10 15 20 25 30 35 40 45
Θ
amb
I max
Climatic category –40/60
Θ min –40 ºC
Θ max 60 ºC
Storage temperature –40 ºC….+85 ºC
hotspot Max. 85 ºC
P max at
Θ
ambient
11.3 W 55 ºC
7.5 W 65 ºC
3.8 W 75 ºC
Maximum power loss at
Θ
ambient
0.0 W 85 ºC
Humidity av. rel. < 95%
Degree of protection IP 20
Maximum altitude 4,000 m
Film Capacitors – Power Factor Correction B256735252A020
PhaseCap Compact capacitors MKK525-D-25-02
FILM PFC PM January 2012
Please read Cautions and warnings and Page 5 of 10
Important notes at the end of this document.
Mean life expectancy
tLD Up to 200 000 hours (temperatu re class –40/C) ;HS 70°C
Up to 150 000 hours (temperature class –40/60) ;HS 70°C
Max. 10000 switchings per year
Terminals
Protection degree Isolated terminals, IP20
Max. torque 2.0 Nm
Terminal cross section 25 mm2
Maximum terminal current 80 A
Creepage distance (min) 12.7 mm
Clearance (min) 9.6 mm
Safety
Mechanical safety Overpre ssure disconnector
Max. short circuit current (AFC: 10 kA)
Discharge resistor time  60 s to 75 V or less
Reference standards
IEC 60831–1/2, UL 810-5th edition
Film Capacitors – Power Factor Correction B256735252A020
PhaseCap Compact capacitors MKK525-D-25-02
FILM PFC PM January 2012
Please read Cautions and warnings and Page 6 of 10
Important notes at the end of this document.
Label design
Dimensional drawing
Film Capacitors – Power Factor Correction B256735252A020
PhaseCap Compact capacitors MKK525-D-25-02
FILM PFC PM January 2012
Please read Cautions and warnings and Page 7 of 10
Important notes at the end of this document.
Cautions and warnings
In case of dents of more than 1 mm depth or any other mechanical damage, capacitors must not
be used at all.
This applies also in cases of oil leakages.
To ensure the full functionality of the overpressure disconnector, elastic elements must not be
hindered and a minimum space of 12 mm has to be kept above each capacitor.
Do not handle the capacitor before it is discharged.
Resonance cases must be avoided by appropriate application design in any case.
Handle capacitors carefully, because they may still be charged even after disconnection due to
faulty discharging devices.
Protect the capacitor properly against over current and short circuit.
Failure to follow cautions may result, worst case, in premature failures, bursting and fire.
Discharging
Capacitors must be discharged to a maximum of 10% of rated voltage before they are switched in
again. This prevents an electric impulse discharge in the application, influences the capacitor’s
service life and protects against electric shock. The capacitor must be discharged to 75 V or less
within 3 minutes. There must be not any switch, fuse or any other disconnecting device in the circuit
between the power capacitor and the discharging device. PhaseCap Compact-capacitors either have
a pre-mounted ceramic discharge module inserted from above into the middle section of the terminal,
or for high voltages/high loads a plastic discharge module mounted at one side of the terminal;
alternatively discharge reactors are available from EPCOS. Discharge and short circuit capacitor
before handling!
Service life expectancy
Electrical components do not have an unlimited service life expectancy; this applies to self-healing
capacitors too. The maximum service life expectancy may vary depending on the application the
capacitor is used in.
Safety
Electrical or mechanical misapplication of capacitors may be hazardous. Personal injury or property
damage may result from bursting of the capacitor or from expulsion of oil or melted material due to
mechanical disruption of the capacitor.
Ensure good, effective grounding for capacitor enclosures.
Provide means of disconnecting and insulating a faulty component/bank.
The terminals of capacitors, connected bus bars and cables as well as other devices may also be
energized.
Follow good engineering practice.
Thermal load/over-temperature
After installation of the capacitor it is necessary to verify that maximum hot-spot temperature is not
exceeded at extreme service conditions.
Film Capacitors – Power Factor Correction B256735252A020
PhaseCap Compact capacitors MKK525-D-25-02
FILM PFC PM January 2012
Please read Cautions and warnings and Page 8 of 10
Important notes at the end of this document.
Overpressure disconnector
To ensure full functionality of an overpressure disconnector, the following must be observed:
1. The elastic elements must not be hindered, i.e.
Connecting lines must be flexible leads (cables).
There must be sufficient space (min. 12 mm) for expansion above the connections. This will
enable a longitudinal extension of the can to secure the overpressure disconnector work.
Folding beads must not be retained by clamps.
2. The maximum allowed fault current of 10000 A in accordance with UL 810 standard must be
assured by the application.
3. Stress parameters of the capacitor must be within the IEC60831 specification.
Overcurrent and short circuit protection
Use HRC fuses or MCCBs for short circuit protection. Short circuit protection and connecting
cables should be selected so that 1.5 times the rated capacitor current can be permanently
handled.
HRC fuses do not protect a capacitor against overload – they are only for short circuit protection.
The HRC fuse rating should be 1.6 to 1.8 times rated capacitor current.
Do not use HRC fuses to switch capacitors (risk of arcing).
Use thermal magnetic over current relays for overload protection.
Resonance cases
Resonance cases must be avoided by appropriate application design in any case. Maximum total
RMS capacitor current (incl. fundamental harmonic current) specified in technical data must not be
exceeded.
Re-switching vs. phase-opposition
In case of voltage interruption, a sufficient discharge time has to be ensured to avoid phase-
opposition and resulting high inrush currents.
Vibration resistance
The resistance to vibration of capacitors corresponds to IEC 68, part 2–6.
Max. test conditions:
Test duration 6 h*
Frequency range 1 10 ... 55 Hz*
Displacement amplitude 0.75 mm*
*corresponding to max. 98.1 m/s or 10 g
Film Capacitors – Power Factor Correction B256735252A020
PhaseCap Compact capacitors MKK525-D-25-02
FILM PFC PM January 2012
Please read Cautions and warnings and Page 9 of 10
Important notes at the end of this document.
These figures apply to the capacitor alone. Because the fixing and the terminals may influence the
vibration properties, it is necessary to check stability when a capacitor is built in and exposed to
vibration. Irrespective of this, you are advised not to locate capacitors where vibration amplitude
reaches the maximum in strongly vibrating equipment.
Mechanical protection
The capacitor has to be installed in a way that mechanical damages and dents in the aluminum can
are avoided.
Grounding
The threaded bottom stud of the capacitor has to be used for grounding. In case grounding is done
via metal chassis that the capacitor is mounted to, the layer of varnish beneath the washer and nut
should be removed. The maximum tightening torque is 10 Nm.
Maintenance
Check tightness of the connections/terminals periodically.
Take current reading twice a year and compare with nominal current. Use a harmonic analyser or
true effective RMS-meter.
In case of current above the nominal current check your application for modifications.
If a significant increase in the amount of non-linear loads has been detected, then a consultant
has to be called in for a harmonic study.
In case of the presence of harmonics installation of a de-tuned capacitor bank (reactors) must be
considered.
Check the discharge resistors/reactors and in case of doubt, check their function:
(1) Power the capacitor up and down.
(2) After  90 seconds the voltage between the terminals must decline to less than 75 V.
Check the temperature of capacitors directly after operation for a longer period, but make sure
that the capacitors have been switched off. In case of excessive temperature of individual
capacitors, it is recommended to replace these capacitors, as this should be an indication for loss
factor increase, which is a sign for reaching end of life.
Storage and operating conditions
Do not use or store capacitors in corrosive atmosphere, especially where chloride gas, sulfide gas,
acid, alkali, salt or the like are present. In dusty environments regular maintenance and cleaning
especially of the terminals is required to avoid conductive path between phases and/or phases
and ground.
Note
For detailed information about PFC capacitors and cautions, refer to the latest version of EPCOS PFC
Product Profile.
Important notes
Page 10 of 10
The following applies to all products named in this publication:
1. Some parts of this publication contain statements about the suitability of our products for
certain areas of application. These statements are based on our knowledge of typical
requirements that are often placed on our products in the areas of application concerned. We
nevertheless expressly point out that such statements cannot be regarded as binding
statements about the suitability of our products for a particular customer application. As a
rule, EPCOS is either unfamiliar with individual customer applications or less familiar with them
than the customers themselves. For these reasons, it is always ultimately incumbent on the
customer to check and decide whether an EPCOS product with the properties described in the
product specification is suitable for use in a particular customer application.
2. We also point out that in individual cases, a malfunction of electronic components or failure
before the end of their usual service life cannot be completely ruled out in the current state
of the art, even if they are operated as specified. In customer applications requiring a very high
level of operational safety and especially in customer applications in which the malfunction or
failure of an electronic component could endanger human life or health (e.g. in accident
prevention or life-saving systems), it must therefore be ensured by means of suitable design of the
customer application or other action taken by the customer (e.g. installation of protective circuitry
or redundancy) that no injury or damage is sustained by third parties in the event of malfunction or
failure of an electronic component.
3. The warnings, cautions and product-specific notes must be observed.
4. In order to satisfy certain technical requirements, some of the products described in this
publication may contain substances subject to restrictions in certain jurisdictions (e.g.
because they are classed as hazardous). Useful information on this will be found in our Mate rial
Data Sheets on the Internet (www.epcos.com/material). Should you have any more detailed
questions, please contact our sales offices.
5. We constantly strive to improve our products. Consequently, the products described in this
publication may change from time to time. The same is true of the corresponding product
specifications. Please check therefore to what extent product descriptions and specifications
contained in this publication are still applicable before or when you place an order.
We also reserve the right to discontinue production and delivery of products. Consequently,
we cannot guarantee that all products named in this publication will always be available.
The aforementioned does not apply in the case of individual agreements deviating from the
foregoing for customer-specific products.
6. Unless otherwise agreed in individual contracts, all orders are subject to the current version of
the “General Terms of Delivery for Products and Services in the Electrical Industry”
published by the German Electrical and Electronics Industry Association (ZVEI).
7. The trade names EPCOS, BAOKE, Alu-X, CeraDiode, CSMP, CSSP, CTVS, DeltaCap, DigiSiMic,
DSSP, MiniBlue, MiniCell, MKK, MLSC, MotorCap, PCC, PhaseCap, PhaseCube, PhaseMod,
PhiCap, SIFERRIT, SIFI, SIKOREL, SilverCap, SIMDAD, SiMic, SIMID, SineFormer, SIOV,
SIP5D, SIP5K, ThermoFuse, WindCap are trademarks registered or pending in Europe and in
other countries. Further information will be found on the Internet at www.epcos.com/trademarks.