MCR-f-UI-DC
100240_en_05 PHOENIX CONTACT 9
10 Functions of the Membrane
Keypad
Figure 4 Membrane keypad
Press the key briefly: The output value calcu-
lated is displayed.
By pressing the key again, you return to the cur-
rent input measured value.
Press the key briefly (< 0.sec.): Switches the
module to edit mode for frequency input sig-
nals.
Press the key for at least 2 seconds: Switches
the module to edit mode for analog input sig-
nals.
Press the keys briefly together (< 0.5 sec.):
Switches the module to extended edit mode
Press the keys briefly together: Ends edit
mode, without saving any settings that may
have been made.
Adopts the current setting in edit mode and
switches automatically to the next value.
10.1 Special Function of the Keys in Edit Mode
In edit mode for pulse input signals and for ana-
log input signals, pressing the enter key in
addition to the or key accelerates forward
or backward counting.
By releasing the key and then briefly pressing it
again, it is possible to carry out fine adjust-
ments.
11 Display on LCD
11.1 Display Within Setting Range
Frequency input for NAMUR, 2, 3 and 4-wire
sensors, incremental encoders with push-pull
and HTL output signal and dry contact. Settings
can be made in either Hz or RPM/kRPM [Dis-
play: kRM] / MRPM [Display: MRM].
Frequency input for NAMUR sensors with wire
break and short-circuit recognition. Settings
can be made in either Hz/kHz or RPM/kRPM
[Display: kRM] / MRPM [Display: MRM].
Current input 0…20 mA
Voltage input 0…10 V
ON delay of switching output.
(setting range 0…30 sec., default value = 0.00
sec.)
OFF delay of switching output.
(setting range 0…30 sec., default value = 0.00
sec.)
Setting POWER ON delay (switching output)
(setting range 0…30 sec., default value = 1.00
sec.) During this period, the switching output
does not react to events. This function is only of
effect directly after switching on the supply volt-
age.
Setting the wire-break detection time
(setting range 0.2…10.1 sec., default value =
10.1 sec.)
If no input signal is detected during this period,
"No Input" appears on the display and the out-
puts behave according to their settings
Setting the end value
(setting range 75…125%, default value =
100%)
Setting the zero point in relation to the previ-
ously set
output signal: (setting range -5…+5 mA / -
2.5…+2.5 V;
default value = 0 mA / 0 V)
Setting the division factor from 0.1 to 9999 (de-
fault value = 1.0). Slow positioning tasks require
holed coupling halves with multiple divisions
(factor > 1). Measuring the rotational speed of a
motor at the gearbox requires a small division
factor (factor < 1).
ext. Mode
Reset
Edit
Display
Zero
Input
Analog
Output
FullScale
Input
Digital
Output
High
Setpoint
Low
Setpoint