AP/UP, AP/MIL AP/UP, AP/MIL Series Magnetic Circuit Protectors Introduction | 77 Single Pole | 78 Multi-Pole | 79 Configurations | 81 Operating Characteristics | 82 Delay Curves | 83 Specifications | 84 Decision Tables | 85 AP/UP, AP/MIL Series Hydraulic Magnetic Circuit Protectors INTRODUCTION The AirpaxTM AP series are fully sealed, magnetic circuit protectors that combine power switching and accurate, reliable circuit protection with inverse time delays and trip free features. Unlike a thermal circuit protector, the AP does not change its trip current over a wide temperature span. In addition, the AP magnetic circuit protector is available in either DC, 50/60Hz or 400Hz versions and with various delays to match the protector to specific application requirements. One of the most important features of this protector is the "trip free" action, which means the circuit will not remain closed in the presence of an overload even though the handle is held in the ON position. The delay mechanism senses the fault and the contacts open. Waterproof panel integrity is provided by an "O" ring bushing seal and a silicon rubber gland within the bushing/handle assembly. 77 AP/UP, AP/MIL Series - Introduction Typical applications include communication, navigation and aircraft instrumentation, radar and power supplies. The AirpaxTM UP circuit protector, with UL recognition and CSA certification, is essentially the same as the AP in construction and operating principle. It is approved for operation at 50 volts DC to 20 amperes, 120 volts 50/60Hz to 15 amperes and 240 volts 50/60Hz to 7.5 amperes. The UP circuit protector is available in single pole units only, due to UL and CSA creepage specifications and the wide glass terminals utilized. The AirpaxTM AP-MIL protectors are produced in accordance with MIL-PRF-39019 and the pertinent specification sheets, are subjected to an exacting production and test program to maintain their Qualified Products Listing (QPL). One, two and three pole series trip units, with or without auxiliary contacts, have been accepted for this listing. Refer to specification sheets MIL-PRF-39019/1 through 6 for the application government designations. The AIRPAX cage code number is 81541. http://airpax.sensata.com/ AP/UP, AP/MIL SINGLE POLE CIRCUIT PROTECTORS .380 MAX. 1.605 MAX. [9.65] [ 40.77] .312 [7.92] .625 MAX. [15.88] 22 .875 [ 22.23] 11 RUBBER "O" RING LOCK RING ON-OFF PLATE (OPTIONAL) LOCKWASHER 3/8 -32 NEF-2B HEX NUT Mounting Detail FOR PANEL INTEGRITY, THIS HOLE MUST BE BLIND WITH .075 [1.91] MIN. DEPTH .325 [8.26 [ .125 [ 3.18 1.562 MAX. [ [39.67] .391 [ 9.93 [ Panel Mounting Detail: Tolerance for Mtg. .005 [.13] Maximum Panel Thickness: .156 [3.96] .656 MAX. [16.66] ON .625 MAX. [15.88] OFF KEYWAY .060 - .065 WIDE [1.52 - 1.65 ] .026 - .030 DEEP [.66 - .76] http://airpax.sensata.com/ AP/UP, AP/MIL Series - Single Pole 78 MULTI-POLE CIRCUIT PROTECTORS AP Multi-Pole Combinations Circuit demands and design ingenuity suggest a limitless number of special combinations, ranging from a two pole unit with one series breaker and a simple ON*OFF switch, to a more complex three pole unit having one series, one shunt and one relay configuration with auxiliary indicator circuit contacts. Please contact Airpax for specific part number. The AP12 consists of two independent series trip protectors, each available with its own rating and delay characteristics. Two Pole, AP12 Two of the basic units are combined in a sealed case to provide protection for dual circuit. A single toggle handle actuates both internal trip mechanisms. Conversely, an overload in either circuit trips both simultaneously. One frequent use of two pole protectors is to interrupt either or both sides of a power line. Likewise, three pole protectors often use three identical coils. However, any two or three pole protectors may have any coil of any delay in any desired combination. (Unless otherwise specified, we assume the two or three poles to be all alike.) This two pole unit can therefore have an unlimited number of combinations, which makes ordering by a code system impractical. Thus, if the poles differ, a descriptive drawing is recommended. Two Pole, AP12, Toggle 1.780 MAX. .380 MAX. [45.21] [9.65] NOTE A .312 [7.92] .625 MAX. [15.88] .625 [15.88] 22 .875 [22.23] 11 .625 RUBBER "O" RING [15.88] LOCK RING 1.281 MAX. [32.53] ON-OFF PLATE (OPTIONAL) LOCKWASHER .250 [6.53 (2 PLACES) .003 .076 .076 9.53 AP/UP, AP/MIL Series - Multi-Pole 9.53 .002 .051 .625 [15.88 .325 [8.26 [ OFF .375 .147 3.73 PANEL SEAL INTEGRITY, .125 [3.18 FOR THIS HOLE MUST BE BLIND WITH .075 [1.91] MIN. DEPTH [ ON KEYWAY .060 - .065 WIDE [1.52 - 1.65] .026 - .030 DEEP [.66 - .76] 79 .003 .375 [ 1.562 MAX. [39.67] .375 [9.53] [ .875 MAX. .625 [22.23] [15.88] Mounting Detail .375 [9.53 [ 6-32 THD. .188 [ 4.78 ] DEEP (2 PLACES) -32 NEF-2B HEX NUT [ 3/8 .391 [ 9.93 Panel Mounting Detail: Tolerance for Mtg. .005 [.13] Panel Thickness: .125-.156 [3.18-3.96] Note: Tolerance .031 [.79] Angles: 5 unless noted. Dimensions in brackets [ ] are millimeters. A: Threaded inserts exceed seated height of bushing by .005-.015 [.13-.38] http://airpax.sensata.com/ AP/UP, AP/MIL combination. (Unless otherwise specified, we assume the two or three poles to be all alike.) Like the two pole protectors, each pole may have different ratings and delays. All multi-pole units have provisions for a rugged three point panel mount. Use of 6-32 panel seal screws together with the bushing mount is recommended to maintain specification shock and vibration levels. Three Pole, AP112 Three circuits may be simultaneously protected. One actuating toggle handle closes all circuits and all poles trip in the presence of an overload on any circuit. Some typical combinations could be: 3 series poles; 2 series and one shunt; 2 series and one relay; or 3 series with a set of auxiliary contacts. Three Pole, AP112, Toggle 1.780 MAX. .380 MAX. [45.21] [9.65] NOTE A .312 [7.92] .625 MAX. [15.88] .875 [ 22.23] .625 [15.88] .625 [15.88] 22 11 .937 [23.80] RUBBER "O" RING 1.937 MAX. [49.20] LOCK RING ON-OFF PLATE (OPTIONAL) LOCKWASHER .003 .687 KEYWAY .060 - .065 WIDE [1.52 - 1.65] .026 - .030 DEEP [.66 - .76] http://airpax.sensata.com/ .625 [15.88 .325 [8.26 [ OFF 17.45 .003 .687 .076 17.45 .002 .051 .147 3.73 .125 [3.18 FOR PANEL SEAL INTEGRITY, THIS HOLE MUST BE BLIND WITH .075 [1.91] MIN. DEPTH [ ON .076 [ 1.562 MAX. [39.67] Mounting Detail [ .875 MAX. .625 [22.23] [15.88] .250 [6.53 (2 PLACES) .687 .687 [17.45] [17.45 [ 6-32 THD. .188 [4.78] DEEP (2 PLACES) -32 NEF-2B HEX NUT [ 3/8 .391 [9.93 Panel Mounting Detail: Tolerance for Mtg. .005 [.13] Panel Thickness: .125-.156 [3.18-3.96] AP/UP, AP/MIL Series - Multi-Pole 80 Series Trip AP1-1 Series Trip The most popular configuration for magnetic protectors is the series trip where the sensing coil and contacts are in series with the load being protected. The handle position conveniently indicates circuit status. In addition to providing conventional overcurrent protection, it's simultaneously used as a power disconnect. 2X RUBBER BOOT UP1-1 (UL Recognized Series) 1.012 25.70] ] SCHEMATIC DIAGRAM BOOT REMOVED FOR CLARITY Relay Trip (Note A) AP1- 4 (Relay) Shunt Trip AP1- 3 .130.010 3.30.25] .076.010 DIA. 1.93.25 ] ] ] .438 [11.13] .438 [11.13] Switch with Auxiliary Switch AP1-1RC (Note A) Series with Auxiliary Switch AP1-1R (Note A) C NC C NO NO NC NC NO C NO NC C AP7-1 (Screw Terminal with Terminal Block) 6 - 32 x .187 [4.75] SCREW NO. 6 LOCKWASHER SINGLE POLE 1.780 45.21] MAX. ] MULTIPOLE 1.950 49.53] MAX. DIM. FROM BACK OF PANEL. ] Voltage Trip Sometimes called "dump circuits" or "panic trip circuits," these units make it possible to open main power contacts with lower power inputs from one or more sources. This configuration is becoming increasingly more important for sensitive circuitry and denser packaging in automation systems. Available in series, shunt or relay configurations. 7 .875 22.22] ] Remote Indication, AP1-1R AP series trip circuit protectors are available with electrically isolated contacts which are rated at 1/2 ampere, 120 volts AC or 50 volts DC. These contacts provide SPDT switching action which can be used to indicate "power-on" and "power-off" conditions or to actuate lights, alarms or timing devices. 1.562 MAX. 39.67] 1.350.050 34.291.27] ] Relay Trip This permits the overload sensing coil to be placed in a circuit which is electrically isolated from the trip contacts. The coil may be actuated by sensors monitoring pressure, flow, temperature, speed, etc. Other typical applications include crowbar, interlock and emergency/rapid shutdown circuitry. Trip may be accomplished by voltage or current, which must be removed immediately upon tripping. .312 7.92] ] Shunt Trip The shunt trip is designed for controlling two separate loads with one assembly. The control is established by providing overload protection for the critical load. When the current through this load becomes excessive and reaches the trip point the protector will open and remove power from both loads simultaneously. The total current rating of both loads must not exceed the maximum contact rating. Optional Booted Terminals ] CONFIGURATIONS Note: Tolerance .031 [.79] Angles: 5 unless noted. Dimensions in brackets [ ] are millimeters. A. Main protector contacts open. 81 AP/UP, AP/MIL Series - Configurations http://airpax.sensata.com/ AP/UP, AP/MIL OPERATIONAL CHARACTERISTICS SERIES RESISTANCE NOMINAL VALUES @ +25C Inrush Pulse Tolerance The following table provides a comparison of inrush pulse tolerance with and without the inertial delay feature for each of the 50/60Hz delays. Pulse tolerance is defined as a single pulse of half sine wave peak current amplitude of 8 milli-seconds duration that will not trip the circuit protector. Current Ratings DC, 50/60Hz, 400 Hz (Amps) DC Series Resistance All Delays except 40, 50, 60 (ohms) DC Series Resistance Delays 40, 50, 60 (ohms) 0.050 470 105 0.100 145 27.0 0.250 18.0 3.80 0.500 4.30 1.00 0.750 1.60 0.400 1.00 1.15 0.230 2.00 0.298 0.060 3.00 0.130 0.033 5.00 0.052 0.012 7.50 0.025 0.007 10.0 0.016 0.006 15.0 0.006 0.005 20.0 0.005 0.004 Delay vs PEAK AMPLITUDE Delay Peak Amplitude 61, 62, 71, 72, A, B 4 Times Rated Current (60Hz) 61F, 62F, 71F, 72F 6.5 Times Rated Current (60Hz) 64, 65 10 Times Rated Current (60Hz) 64F, 65F 13 Times Rated Current (60Hz) 41, 42, AF, BF 14 Times Rated Current (400Hz) 41F, 42F 20 Times Rated Current (400Hz) 51, 52 6 Times Rated Current (60Hz) 51F, 52F, AF, BF 8 Times Rated Current (60Hz) Tolerance at 25% values based on V-A method after 1 hour stabilization at 100% rated current. Consult factory for other limits. Percentage of Rated Current vs Trip Time in Seconds at +25C (Vertical Mount) Delay 100% 125% (Note A) 200% 400% 800% 40* No Trip .035 Max .025 Max .015 Max .015 Max 41 No Trip .200 to 7 .055 to .950 .010 to .240 .005 to .080 42 No Trip 3 to 60 .500 to 9 .010 to 1.75 .005 to .100 49* No Trip .100 Max .050 Max .020 Max .015 Max 50* No Trip .035 Max .025 Max .015 Max .015 Max 51 No Trip .400 to 4 .060 to .600 .010 to .200 .005 to .035 52 No Trip 4 to 40 .600 to 6 .010 to 1.50 .005 to .050 59* No Trip .100 Max .050 Max .020 Max .015 Max 60* No Trip .035 Max .025 Max .015 Max .015 Max 61 No Trip .500 to 5 .070 to .700 .020 to .200 .008 to .080 62 No Trip 4 to 40 .800 to 8 .010 to .300 .005 to .080 64 No Trip .900 to 10 .200 to 1.70 .040 to .500 .012 to .100 65 No Trip 9 to 60 1.15 to 7 .110 to 1 .010 to .190 69* No Trip .100 Max .050 Max .020 Max .015 Max 71 (Note B) No Trip .200 to 7 .055 to .950 .010 to .240 .005 to .080 72 (Note B) No Trip 3 to 60 .500 to 9 .010 to 1.75 .005 to .100 79 (Note B) No Trip .100 Max .050 Max .020 Max .015 Max *Notes: Instantaneous delays (40, 49, 59, 60, 69, 79) are not compatible with inrush enhancement options and are not recommended for general use. A. 150% for delays 40, 50 & 60. 135% minimum trip for delays 41, 42, 49, 71, 72 & 79. B. Military time delays. 71=A, 72=B, 79=C http://airpax.sensata.com/ AP/UP, AP/MIL Series - Operating Characteristics 82 Delay curves 64 and 65 illustrate the improved inrush tolerance provided compared to standard delays. Not available in MIL configurations. All trip times and trip currents are specified with the breaker mounted in the normal vertical position at ambient temperature of 25C. For time delay test and measurement purposes, the breakers should not carry current prior to application of overload. 10000 INSTANT MAY TRIP 100 10 1 .1 .01 .001 0 500 600 700 800 900 1000 900 1000 900 1000 DELAY 64 MAY TRIP TRIP MAY TIME IN SECONDS MAY TRIP 1 1 .1 .01 .01 0 100 150 200 125 300 400 500 600 700 800 900 1000 .001 0 PERCENT OF RATED CURRENT 100 150 200 125 300 400 500 600 700 800 PERCENT OF RATED CURRENT 10000 10000 SHORT 100 1000 TIME IN SECONDS MAY MAY TRIP TRIP 100 10 10 1 1 .1 .1 .01 .01 0 100 150 200 135 DELAY 65 MAY TRIP TRIP MAY 1000 TIME IN SECONDS 400 PERCENT OF RATED CURRENT 10 .1 300 400 500 600 700 800 900 1000 PERCENT OF RATED CURRENT 83 300 100 10 .001 100 150 200 135 1000 100 TIME IN SECONDS LONG 1000 10000 1000 .001 10000 TIME IN SECONDS Typical Delay Curves The delay curves below illustrate our standard instant, short and long delays. Please consult factory for specific delay curves or refer to table on page 87. AP/UP, AP/MIL Series - Delay Curves .001 0 100 150 200 125 300 400 500 600 700 800 PERCENT OF RATED CURRENT http://airpax.sensata.com/ Lever Strength The operating lever or its seal will not be damaged by a 10 lb. force applied in any direction. AP/UP, AP/MIL Trip Free AP circuit protectors will trip open on overload, even when forcibly held ON. This prevents the operator from damaging the circuit by holding the handle in the ON position. Shock All protectors withstand 100G without tripping, even while carrying full rated current with shock applied in any plane of 6 ms duration. Test is made according to Method 213, Test Condition I or MIL-Std-202 as outlined in Paragraph 4.6.14 of MIL-PRF-39019. Delay 40, 50 and 60 breakers are tested at 80% of rated current. Trip Indication The operating handle of the breaker moves forcibly and positively to the OFF position on overload. It is not necessary to manually "reset" to full "OFF" in order to turn it on again. Ambient Operation The protector will operate at any ambient between -40 C and +100 C, when tested in accordance with the requirements of MIL-PRF-39019. Vibration All protectors withstand vibration from 10 to 55 cycles at .06 double amplitude and 55 to 2000 cycles at 10G, applied in any plane, without damage and without tripping even while operating at full rated current. Test is made in accordance with Method 204A, Test Condition C, of MIL-Std-202 as outlined in Paragraph 4.6.12 of MIL-PRF-39019. Delay 40, 50 and 60 protectors are tested at 80% of rated current. Insulation Resistance Exceeds 100 megohms at a potential of 100Vdc. Dielectric Strength The protector will withstand 1250 volts RMS, 60Hz from terminals to case and between the terminals when open. Short Circuit Capacity When tested in accordance with the procedures of UL1077, AP supplementary protectors have a short circuit capacity of 1000 amperes at 32Vdc, 120Vac, 240Vac, 60 or 400Hz. Parts are recognized to UL1077 for type UP1 only. The rated Rupture Capacity per MIL-PRF-39019 is 500 amperes, 50 volts DC, 500 amperes, 120 volts AC and 300 amperes, 240 volts AC, 60 or 400Hz. Endurance With the circuit protector operated as an ON-OFF switch, operating life exceeds 10,000 operations at a rate of 6 per minute when tested as follows: 6000 OPS @ rated current plus 4000 OPS @ no load. Case Seal The breaker is fully sealed and will not show evidence of leakage under total immersion. Meets requirements of MILPRF-39019. Ratings AP protectors are available in current ratings from 50 milliamperes to 20 amperes, 50 volts DC or 240 volts AC, maximum, 60 Hz or 400 Hz. UP protectors are UL 1077 and CSA approved as per the following table. Please consult factory for ratings other than those noted. Panel Seal The "O" ring provides, with the other illustrated hardware, a seal against a pressure differential of 15 psi applied for an hour. RATINGS Series Voltage Current TC OL Short Circuit Rating (SC, amps) CSA Phase UP 50 VDC 0.05 to 20 amps 1 1 U1, 1000 YES -- UP 240 VAC 0.05 to 7.5 amps 1 0 C1, 1000 4X fuse max YES 1 UP 120 VAC 0.05 to 15 amps 1 1 C1, 1000 4X fuse max YES 1 UP 240 VAC (400) 0.05 to 7.5 amps 1 0 C1, 1000 4X fuse max YES 1 UP 120 VAC (400) 0.05 to 15 amps 1 0 C1, 1000 4X fuse max YES 1 RECOMMENDED TORQUE SPECIFICATIONS AUXILIARY SWITCH RATING 3.0 amps @ Component Torque (in-lbs) 6-32 Mounting Inserts 6 to 8 6-32 Screw Terminals 6 to 8 Approximate Weight Per Pole 3/8-32 Mounting Bushing Nut 20 to 25 1.8 Ounces http://airpax.sensata.com/ 120 VAC 50 VDC 49 Grams AP/UP, AP/MIL Series - Specifications 84 How to Order The ordering code for AP magnetic circuit protectors may be determined by following the steps in the decision tables shown here. For example, the following is the code for a two pole AP, hook terminal, series unit, designed for operation in a DC circuit. It has a short time delay and a rating of 20 amperes. The coding given permits a descriptive part number, with limitations. In the illustrated double pole example (AP12-151-203), it is automatically assumed that both poles are identical. One great virtue of magnetic circuit protectors is their adaptability to complex circuits, thus variations from pole to pole become the rule rather than the exception. Descriptive drawings are recommended. In this event, factory assigned part numbers are utilized. To determine the ordering number for your particular AP unit, simply follow the steps shown. You may use this number to place a order or as a reference for further questions you may have. Notes: AThe UP has a wide glass terminal to meet UL and CSA creepage specifications. Except as completely non-standard there is no space for more than two terminals and the UP is therefore limited to only the single pole series circuit configuration (Third Decision Table - 1). Delays available in the UP are: 40, 50 and 60; 41, 51 and 61; 42, 52 and 62; 64, 65, 69, 71, 72 and 79. BUsers should refer to the applicable drawings of MIL-PRF-39019. Configurations vary dependent upon the revision of MIL-PRF-39019. The 6-32 threaded mounted bushings, useful for added strength, are approved under this specification. To assure that proper parts are received, consult the factory for application assistance if there is any doubt about which version is correct for the application concerned. CScrew terminals are available and are equipped with standard terminal block. Space permits their use only in the series configuration (Third Decision Table ). Standard terminals are heavy copper hooks. DScrew terminals with SPDT auxiliary switch, available only with the series circuit, may have "R" soldering terminals, flattened and pierced, or "RC" soldering terminals which are cane hooks. Screw terminals (-7, -17, -117) are available with SPDT auxiliary switch "R" type only. EThe nominal current values for 100% of rated current (see delay curves) are those listed. Other values can be readily supplied, in general, without delayed delivery. For values above or below the listed range, please consult an Airpax sales office or sales representative. F Consult factory for assigned part numbers. 85 AP/UP, AP/MIL Series - Decision Tables http://airpax.sensata.com/ AP/UP, AP/MIL 1 Example: First Decision AP12 -1 -51-203-FM Type AP Fully sealed magnetic circuit protector UP (Note A) Underwriters' Laboratories recognized circuit supplementary protector AP - MIL (Note B) /1 through /6 QPL per MIL-PRF-39019 2 Second Decision (Note C) 1 2 3 4 4 1 3 Single pole unit, mounted with 3/8 threaded bushing 17 112 -40 Screw Terminals 7 12 117 Two pole unit, bushing plus (2) 6-32 threaded inserts Three pole unit, bushing plus (2) 6-32 threaded units Third Decision Internal Configuration -0 Switch Only (Omit 4th and 5th Decisions) -1 Series -1R (Note D) Series with Auxiliary Switch with pierced pin terminals -1RC (Note D) Series with Auxiliary Switch with cane hook terminals -3 Shunt -4 5 Relay (5 amps max coil rating) Multi-pole units with mixed construction, poles numbered left to right when viewed from terminal end (Note F). http://airpax.sensata.com/ -41 Optional FM Approved (Factory Mutual Research) Add -FM to part number to indicate FM approval. FM approval is available for Single Pole, Series Trip, UP type units only. TA = -40C to +65C Units < 10A are rated CL 1, DIV 2, Group ABCD, T6 Units > 10A are rated CL 1, DIV 2, Group ABCD, T4A 6 5 Fourth Decision Hz and Delay Poles Hook Terminals 6 Fifth Decision (Note E) Nominal Amperage Rating 400Hz 150% instant trip* Code 400Hz short time delay -051 .050 -101 .100 -201 .200 -251 .250 Amperes -42 400Hz long time delay -49 400Hz 135% instant trip* -50 DC 150% instant trip* -401 .400 -51 DC short time delay -501 .500 -52 DC long time delay -601 .600 -59 DC 125% instant trip* -60 -61 -62 -751 .750 -102 1.000 50/60Hz 150% instant trip* -1251 1.250 50/60Hz short time delay -1751 1.750 50/60Hz long time delay -202 2.000 -252 2.500 -302 3.000 -64 50/60Hz high pulse, short time delay (50/60Hz only) -65 50/60Hz high pulse, long time delay (50/60Hz only) -502 5.000 -702 7.000 -69 50/60Hz 125% instant trip* -752 7.500 -802 8.000 -71 DC, 50/60Hz, 400Hz short time delay 135% trip -103 10.000 -72 DC, 50/60Hz, 400Hz long time delay 135% trip -123 12.000 -153 15.000 DC, 50/60Hz, 400Hz instant time delay 135% trip* -173 17.000 -203 20.000 -79 For addition of inertial delay, add an iFi to any delay number. Except 40, 50 & 60. Note: Standard current ratings listed. For other ratings, please consult the factory. *Instantaneous delays are not compatible with inrush enhancement options and are not recommended for general use. AP/UP, AP/MIL Series - Decision Tables 86 This document is generated from the AIRPAXTM full-line catalog #2455005000 printed in USA, January 2011 BUSINESS CENTERS Sensata Technologies 807 Woods Road Cambridge, MD 21613, USA Phone: +1 410-228-1500 Brands: AirpaxTM Sensata Technologies Holland B.V. Kolthofsingel 8 7602 EM Almelo, The Netherslands Phone: +31 546 87 95 55 Brands: KlixonTM, Sensata TechnologiesTM Sensata Technologies Inc. 529 Pleasant Street Attleboro, MA 02703, USA Phone: +1 508-236-3287 Brands: KlixonTM, Sensata TechnologiesTM Sensata Technologies China Co., Ltd. Novel Plaza, 8th Floor 128 Nanjing Road West Shaghai, 20003 People's Republic of China Phone: +86 21 23061500 Brands: KlixonTM, Sensata TechnologiesTM Sensata Technologies 4467 White Bear Lake Parkway St. Paul, MN 55110, USA Phone: +1 800-553-6418 Brands: DimensionsTM Sensata Technologies Japan Ltd. 305, Tanagashira Oyama-cho, Sunto-gun, Shizuoka-ken Japan, 410-1396 Phone: +81 550 78 1211 Brands: KlixonTM, Sensata TechnologiesTM Sensata Technologies Nihon-Airpax 6-3, Chi Yoda 5 Chome Saitama-Ken Japan, 350-0214 Phone: +81 492 83 7575 Brands: AirpaxTM Sensata Technologies Korea Ltd. 29F, Trade Tower 159-1 SamSung-Dong, KangNam-Ku, Seoul 135-729, Korea Phone: +81-2-551-2918 Brands: KlixonTM, Sensata TechnologiesTM Important Notice: Sensata Technologies (Sensata) reserves the right to make changes to or discontinue any product or service identified in this publication without notice. Sensata advises its customers to obtain the latest version of the relevant information to verify, before placing any orders, that the information being relied upon is current. Sensata assumes no responsibility for infringement of patents or rights of others based on Sensata applications assistance or product specifications since Sensata does not possess full access concerning the use or application of customers' products. Sensata also assumes no responsibility for customers' product designs. http://airpax.sensata.com/