For the Latest Information
On the Internet: www.sti.com
OMRON SCIENTIFIC TECHNOLOGIES, INC.
USA Tel. 1/888/510-4357 Canada Tel. 1/866/986-6766
H11
H
Mini Contactor Relays 4-Pole
• AC and DC operated
• 4-, 6- and 8-pole versions in different configurations
• Mirrored contacts
• Screw fixing and snap fitting (35 mm DIN rail)
• Rated current = 10A (Ith)
• Suitable for electronic devices (DIN 19240)
• Finger proof (VBG 4)
Accessories
• 2- and 4-pole additional auxiliary contacts in different
configurations
Mini Contactor with Mirrored Contacts
J7KNA-AR J7KNA
Specifications
Electrical
Operating Coil
Supply Power: 24 VDC, 110 VAC or 230 VAC
Inrush: 25 VA for AC versions
3 W for DC versions
Power Usage: 4.5 VA for AC versions
2.5 W for DC versions
Rated Carry Current: 10 A @ 40C
Switching Capability Inductive
Loads (AC-15, DC-13)
AC: Break 120 V - 6 A, 240 V - 3 A (continuous 10 A)
DC: 24 V - 3 A
Max. Switching Frequency: 10,000 per hour
Min. Switching Current: 5 mA
Max. Drop-Out Time*: 8-25 ms for AC versions
8-25 ms for DC versions
Mechanical
Mechanical Life: 1 x 107 operations min.
Mounting: 35 mm DIN rail or 4 screw holes for panel mounting
Wire Size: Screw terminals accept two 14 AWG solid or stranded wires
Weight: AC versions: 160 g (5 oz.)
DC versions: 190 g (6 oz.)
Vibration: 5 to 300 Hz
Environmental
Vibration Resistance: 2 g with control relay open; 4 g with control relay closed
Operating Temperature: -40 to 60°C (-40 to 140·F)
Approvals: IEC947-5-1, VDE 0660, EN60947-5-1, UL508
*The Drop-Out Time is the time it takes for the N/O contacts to open after the coil voltage is turned OFF.
Specifications are subject to change without notice.
Approved Standards
Standard Guide No. (US,C)
UL NKCR, NKCR7
ICE 947-5-1
VDE 0660
EN 60947-5-1