Data sheet
WDU 35/ZA BL Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 26
D-32758 Detmold
Germany
www.weidmueller.com
Technical data
Creation date March 31, 2021 1:58:03 PM CEST
Catalogue status 26.03.2021 / We reserve the right to make technical changes. 2
Dimensions and weights
Depth 62.5 mm Depth (inches) 2.461 inch
Depth including DIN rail 63 mm Height 60 mm
Height (inches) 2.362 inch Net weight 51.48 g
Weight 54 g Width 16 mm
Width (inches) 0.63 inch
Temperatures
Storage temperature
-25 °C...55 °C
Operating temperature range For operating temperature
range see EC Design
Test Certificate / IEC Ex-
Certificate of Conformity
Continuous operating temp., min. -60 °C Continuous operating temp., max. 130 °C
Material data
Material Wemid Colour blue
UL 94 flammability rating V-0
Rating data IECEx/ATEX
Certificate No. (ATEX) DEMKO14ATEX1338U Certificate No. (IECEX) IECEXULD14.0005U
Max. voltage (ATEX) 690 V Current (ATEX) 115 A
Wire cross section max. (ATEX) 35 mm² Max. voltage (IECEX) 690 V
Current (IECEX) 115 A Wire cross section max. (IECEX) 35 mm²
Operating temperature range For operating temperature
range see EC Design
Test Certificate / IEC Ex-
Certificate of Conformity
Marking EN 60079-7
Ex eb II C Gb
Ex 2014/34/EU label II 2 G D
System specifications
Version Screw connection,
for screwable cross-
connection, With assembly
peg, One end without
connector
End cover plate required
Yes
Number of potentials 1 Number of levels 1
Number of clamping points per level 2 Number of potentials per tier 1
Levels cross-connected internally No PE connection No
Rail TS 35 N-function Yes
PE function No PEN function Yes
2 clampable conductors (H05V/H07V) with equal cross-section (rated connection)
Cross-section for connected wire,
stranded, two clampable wires, max. 16 mm²
Cross-section for connected wire,
stranded, two clampable wires, min. 16 mm²
Wire connection cross section, finely
stranded with wire-end ferrules DIN
46228/1, 2 clampable wires, max. 16 mm²
Wire connection cross section, finely
stranded with wire-end ferrules DIN
46228/1, 2 clampable wires, min. 2.5 mm²
Wire connection cross section, finely
stranded, two clampable wires, min. 2.5 mm²
Wire cross-section, finely stranded, two
clampable wires, max. 16 mm²