Description Part number
Sockets H3CA-A timer Bottom surface or track mounting, top screw terminals P2CF-11
Back mounting, for use with Y92F-30 mounting adapter, bottom screw terminals P3GA-11
H3CA-8, Bottom surface or track mounting, top screw terminals P2CF-08
H3CA-8H timers Back mounting, for use with Y92F-30 mounting adapter, bottom screw terminals P3G-08
Panel mounting Fits behind panel, ideal for side by side installation. Use P3G-❑❑ sockets. Y92F-30
adapters Installs through panel front; timer face fits bezel, rear of timer clips to adapter. Y92F-70
Use P3G-❑❑ sockets. Fits 65-66 mm (2.56 - 2.59 in) x 52-53 (2.04 x 2.09 in)
panel cutout. Charcoal gray face plate measures 88 H x 58 W mm (3.46 x 2.28 in).
Installs through panel front; timer face fits bezel, rear of timer clips to adapter. Y92F-71
Use P3G-❑❑ sockets. Fits 55 x 45 mm (2.17 x 1.77 in) panel cutout. Charcoal gray
face plate measures 58 H x 50 W mm (2.28 x 1.97 in).
Protective cover Hard plastic cover; not for use with Y92F-70 or Y92F-71 panel adapters. Y92A-48B
Soft plastic cover; not for use with Y92F-70 or Y92F-71 panel adapters. Y92A-48D
Mounting track DIN rail, 50 cm (1.64 ft) length PFP-50N
DIN rail, 1 m (3.28 ft) length PFP-100N
End plate PFP-M
Spacer PFP-S
Timing function 8 field-selectable functions ON-delay only
Time limit SPDT SPDT SPDT DPDT
Instantaneous SPDT
Terminal form 11-pin round socket Front mounted 8-pin round socket
screw terminals
Part number H3CA-A H3CA-FA H3CA-8H H3CA-8
AC 24 to 240 V, 50/60 Hz or Specify 24 V, 100/110/120 V, or 200/220/240 V; 50/60 Hz
DC 12 to 240 V Specify 12 V, 24 V, 48 V or 110 V
1/16 DIN, Digital-Set Timer with
0.1 Second to 9,990 Hours Range
8 field-selectable operation modes
Universal AC/DC supply voltage
timers available
Operations include ON-delay, Repeat
cycle, Signal Interval/OFF-delay,
Signal-OFF delay (I and II), Interval, Cycle
and Signal ON-delay/OFF-delay
Selectable no-voltage start, reset, gate
and check inputs expand capabilities
Time remaining LCD bar graph and LCD
output status indicator
Panel mounting adapters, sockets, and
accessories may be ordered separately
TIMERS
Contact
type
ACCESSORIES
Add the supply voltage to the part number when you order ON-delay only timers H3CA-8 and H3CA-8H. For example,
H3CA-8H-AC/100/110/120.
Supply
voltages
Solid-State Timer H3CA
Ordering Information
H3CA 1
H3CA H3CA
2
Part number H3CA-A H3CA-FA H3CA-8H H3CA-8
AC 24 to 240 V, 50/60 Hz 24 V, 100/110/120 V, 200/220/240 V; 50/60 Hz
DC 12 to 240 V 12 V, 24 V, 48 V, 110 V, (permissible ripple
factor: 20% max. using single-phase, full-
wave rectified power sources)
Operating voltage 90 to 110% of rated voltage
AC 3 VA 10 VA
DC 3 W 2W
Timing 8 field-selectable modes: ON-delay, Repeat ON-delay only
functions cycle, Signal Interval/OFF-delay, Signal ON-/
OFF-delay, Signal OFF-delay (I and II),
Interval and Cycle
Start, reset, gate inputs No voltage No voltage
Type Time limit SPDT SPDT DPDT
Instantaneous SPDT
Max. load 3 A, 250 VAC (p.f. = 1)
Min. load 10 mA, 5 VDC
Repeat accuracy ±0.3%, ±0.05 sec (includes variation due to voltage and temperature changes)
Setting error ±0.5%, ±0.05 sec
Resetting system Power-OFF, external and self-reset Power-OFF
Resetting time 0.5 sec max. 0.1 sec max.
Indicators Time Remaining (LCD bar graph), Output Status (LCD message)
Materials Plastic case
Mounting Panel, track, surface
Connections 11-pin round socket Terminal screws 8-pin round socket
Weight 110 g (3.9 oz) 190 g (6.7 oz) 110 g (3.9 oz)
Approvals UL/CSA/SEV
Operating ambient temperature -10° to 55°C (14° to 131°F)
Humidity 35 to 85% RH
Vibration Mechanical durability 10 to 55 Hz; 0.75 mm (0.03 in) double amplitude
Malfunction durability 10 to 55 Hz; 0.5 mm (0.02 in) double amplitude
Shock Mechanical durability 100 G
Malfunction durability 10 G
Variation due to voltage change See "Repeat Accuracy"
Variation due to temperature change See "Repeat Accuracy"
Insulation resistance 100 M min. at 500 VDC
Dielectric strength 2,000 VAC, 50/60 Hz for 1 minute between current-carrying and non-current-carrying parts
and between contact and control circuit
1,000 VAC, 50/60 Hz for 1 minute between non-continuous contacts
Service life Mechanical 10 million operations minimum (under no load, at 1,800 operations/hour)
Electrical 100,000 operations minimum at maximum ratings
Specifications
Time unit
selector
Time setting switches
Operation
mode
selector*
Mode Operation
A ON-delay
B Repeat cycle
C Signal Interval/OFF-delay
D Signal OFF-delay I
G Signal ON-delay/OFF-delay
H Signal OFF-delay II
E Interval
F Cycle
Time unit Timing range
0.1 s 0.1 to 99.9 seconds
s 1 to 999 seconds
0.1 m 0.1 to 99.9 minutes
m 1 to 999 minutes
0.1 h 0.1 to 99.9 hours
h 1 to 999 hours
10 h 10 to 9990 hours
Supply
voltage
Power
consumption
Control
output
RANGE AND OPERATION MODE SELECTION
Note: *Operation mode selector not included with ON-delay only models.
H3CA H3CA
3
ELECTRICAL SERVICE LIFE
10,000
5,000
7,000
3,000
1,000
700
500
300
100
70
50 250 VAC p.f. = 0.4 250 VAC p.f.= 1
24 VDC p.f.= 1
24 VDC L/R = 7 ms
0 1 2 3
Load current
In the schematic diagrams, each thick line indicates the external wiring necessary for the selected operation.
The start terminals are connected. Timing starts when power is
applied. The output is energized when the accumulated time
equals the set time. The output remains energized until power is
disconnected or a reset input is applied.
(AC/DC)
Power 2 - 10
(A1-A2)
Start 3 - 6
(X-C1)
Reset 3 - 7
(X-B1)
Control 9 - 11
output NO (15-18)
Time-out
indicator
Remaining
time indicator
t = set time Rt = reset time t-a = less than set time
Signal Start
(AC/DC)
Start signal
Reset signal
Start 3 - 6
(X-C1)
Control 9 - 11
output NO (15-18)
Time-out
indicator
Remaining
time indicator
Power 2 - 10
(A1-A2)
Reset 3 - 7
(X-B1)
t = set time t-a = less than set time
Timing Charts
Power is applied continuously. Timing starts at the leading edge
of the start input. The output is energized when the accumu-
lated time equals the set time. Subsequent start signals during
or after timing will not be accepted. The output relay will remain
energized until a reset input is applied or power is interrupted.
Engineering Data
Power
Power
Electrical operations (thousands)
H3CA-A, H3CA-FA
Mode A ON-Delay
Power-ON Start/Power-OFF Reset
H3CA H3CA
4
In the schematic diagrams, each thick line indicates the external wiring necessary for the selected operation.
Mode B Repeat Cycle
Signal Start
Power is continuously applied. The OFF/ON cycle is initiated at
the leading edge of the start input. The output relay will be OFF
for the set time and then ON for the set time. This cycle will be
repeated until a reset input is applied or power is disconnected.
(AC/DC)
Start signal
Reset signal
Start 3 - 6
(X-C1)
Control 9 - 11
output NO (15-18)
Time-out
indicator
Remaining
time indicator
Power 2 - 10
(A1-A2)
Reset 3 - 7
(X-B1)
t = set time t-a = less than set time
(AC/DC)
Power-ON Start/Power-OFF Reset
The start terminals are connected. Timing starts when power is
applied. The output relay will be OFF for the set time and then ON
for the set time. This cycle will be repeated until a reset input is
applied or power is disconnected. Start 3 - 6
(X-C1)
Control 9 - 11
output NO (15-18)
Time-out
indicator
Remaining
time indicator
Power 2 - 10
(A1-A2)
Reset 3 - 7
(X-B1)
t = set time t-a = less than set time
Mode C Signal Interval/OFF-Delay
Power is continuously applied. Timing begins on both the leading
and trailing edges of the start input. The output relay is energized
during timing. Once the timer has timed out from the trailing edge,
it resets and is ready for subsequent start inputs.
(AC/DC)
Start signal
Start 3 - 6
(X-C1)
Control 9 - 11
output NO (15-18)
Time-out
indicator
Remaining
time indicator
Power 2 - 10
(A1-A2)
Reset 3 - 7
(X-B1)
t = set time t-a = less than set time
Power
Power
Power
H3CA H3CA
5
In the schematic diagrams, each thick line indicates the external wiring necessary for the selected operation.
Mode D Signal OFF-Delay (I)
Power is continuously applied. The output relay is energized at
the leading edge of the start input. Timing starts at the trailing
edge of the start input. The output relay is de-energized when the
accumulated time equals the set time.
(AC/DC)
Start signal
Start 3 - 6
(X-C1)
Control 9 - 11
output NO (15-18)
Time-out
indicator
Remaining
time indicator
Power 2 - 10
(A1-A2)
Reset 3 - 7
(X-B1)
t = set time t-a = less than set time
Mode E Interval
Signal Start
Power is applied continuously. Timing starts at the leading edge of
the start input. The output relay is only energized during timing.
The timer is reset when power is disconnected or a reset input is
applied.
(AC/DC)
Start signal
Reset signal
Start 3 - 6
(X-C1)
Control 9 - 11
output NO (15-18)
Time-out
indicator
Remaining
time indicator
Power 2 - 10
(A1-A2)
Reset 3 - 7
(X-B1)
t = set time t-a = less than set time
Power-ON Start/Power-OFF reset
The start terminals are connected. Timing starts when power is
applied. The output relay is only energized during timing. The
timer is reset when power is disconnected or a reset input is
applied.
(AC/DC)
Start 3 - 6
(X-C1)
Control 9 - 11
output NO (15-18)
Time-out
indicator
Remaining
time indicator
Power 2 - 10
(A1-A2)
Reset 3 - 7
(X-B1)
t = set time t-a = less than set time
Power
Power
Power
H3CA H3CA
6
In the schematic diagrams, each thick line indicates the external wiring necessary for the selected operation.
Mode F Cycle One-Shot
Power-ON Short/Power-OFF Reset
The start terminals are connected. Timing starts when power is
applied. The output relay will be OFF for the set time and then
ON for the set time. The timer is reset when power is discon-
nected or a reset input is applied.
(AC/DC)
Start 3 - 6
(X-C1)
Control 9 - 11
output NO (15-18)
Time-out
indicator
Remaining
time indicator
Power 2 - 10
(A1-A2)
Reset 3 - 7
(X-B1)
t = set time t-a = less than set time
Signal Start
Power is applied continuously. The OFF/ON cycle is initiated at
the leading edge of the start input. The output relay will be OFF
for the set time and then ON for the set time. The timer is reset
when power is disconnected or a reset input is applied.
(AC/DC)
Start signal
Reset signal
Start 3 - 6
(X-C1)
Control 9 - 11
output NO (15-18)
Time-out
indicator
Remaining
time indicator
Power 2 - 10
(A1-A2)
Reset 3 - 7
(X-B1)
t = set time t-a = less than set time
Mode G Signal ON-delay/OFF-delay
Power is continuously applied. Timing begins on both the leading
and trailing edges of the start input. The output relay is energized
when the accumulated time from the leading edge equals the set
time. It is also energized for the set amount of time from the
trailing edge of the start input.
(AC/DC)
Start signal
Start 3 - 6
(X-C1)
Control 9 - 11
output NO (15-18)
Time-out
indicator
Remaining
time indicator
Power 2 - 10
(A1-A2)
Reset 3 - 7
(X-B1)
t = set time t-a = less than set time
Power
Power
Power
H3CA H3CA
7
In the schematic diagrams, each thick line indicates the external wiring necessary for the selected operation.
Mode H Signal OFF-Delay (II)
Power is continuously applied. Timing starts at the trailing edge of
the start input. The output relay is energized during timing.
Power
(AC/DC)
Start 3 - 6
(X-C1)
Control 9 - 11
output NO (15-18)
Time-out
indicator
Remaining
time indicator
Power 2 - 10
(A1-A2)
Reset 3 - 7
(X-B1)
t = set time t-a = less than set time
H3CA-8
50
Power
circuit
Timed
contact Timed
contact
Time-limit
contact NC (1 - 4)
Power (7 - 2)
Time-limit
contact NC (8 - 5)
Time-limit
contact NO (8 - 6)
Remaining
time indicator
Time-out
indicator
t = set time Rt = reset time
Time-limit
contact NO (1 - 3)
H3CA-8H
Power
circuit
Timed
contact
Time-limit
contact NC (8 - 5)
Power (7 - 2)
Instantaneous
contact NC (1 - 4)
Instantaneous
contact NO (1 - 3)
Remaining
time indicator
Time-out
indicator
Time-limit
contact NO (8 - 6)
t = set time Rt = reset time
Dimensions
50
(1.97)
45
(1.77)
(1.77)
45 (1.97)
48
(1.89)
48
(1.89)
75.4
(2.97)
44.8
(1.76)
5 6 0.7
78
63.7
89 (3.50)
13.6
11
Panel cutout
Note: Recommended panel
thickness is 1 to 3.2 mm.
Panel cutout conforms to
DIN 43700.
Instantaneous
contact
Start signal
Unit: mm (inch)
TIMERS
H3CA-A
H3CA H3CA
8
H3CA-FA
75
(2.95)
5
7.5
8.5 8.5 7.5
35
35
(1.38)
L
60
(2.36)
Note: When mounting two or more
timers next to one another,
allow 10 mm (0.39 in) between
timers (dimension L).
H3CA-8, H3CA-8H
96 91
58
Panel cutout
50
(1.97)
45
(1.77)
(1.77)
45 (1.97)
50
48
(1.89)
48
(1.89)
5 6
11 78 0.7 13.6
44.8
(1.76)
75.4
(2.97)
Mounting holes
89 (3.50)
63.7
SOCKETS
Eleven
M3.5 x 7.5
sems
Two
4.5 dia.
mounting
holes
7.8
4
34.5
31.2
(1.23)
max. (Top view)
Mounting holes
Two 4.5 dia. socket
mounting holes
Terminal arrangement
40±0.2
50
(1.97)
max.
11-Pin Sockets for H3CA-A
P2CF-11 Bottom surface or track mounting socket
(2.91)
74 max.
(1.57)
P3GA-11 Back Mounting Socket
In the schematic diagrams, each thick line indicates the external wiring necessary for the selected operation.
Note: Recommended panel
thickness is 1 to 3.2 mm.
Panel cutout conforms to
DIN 43700.
Terminal arrangement
101
(3.98)
58
45
(1.77)
(1.007)
35.4
(1.39)
H3CA H3CA
9
70 (2.75)
max.
50
(1.97)
max.
Two
4.5 dia.
mounting
holes
Eight
M3.5 x 7.5
sems 34.5
35.4 (1.39)
Terminal arrangement
(Top view)
Mounting holes
Two 4.5 dia. or two M4
socket mounting holes
40±0.2
7.8
8-Pin Sockets for H3CA-8, H3CA-8H
Y92F-30 Mounting Adapter
Adapter installs behind the panel. It is ideal for side by side installation. Use P3GA-11 or P3G-08 sockets.
For H3CA, H3CA-8, H3CA-8H
PANEL MOUNTING ADAPTERS
Terminal arrangement
(Bottom view)
P3G-08 Back mounting socket
20 max.
(0.79)
P2CF-08 Bottom surface or track mounting
Y92F-70 Mounting Adapter
Charcoal gray panel adapter installs through panel front. Timer fits bezel, rear of timer clips to adapter.
Use P3GA-11 or P3G-08 sockets.
Socket
Mounting panel
0.5 R
max.
Two 4.5 diameter mounting
holes for panel adapter
Note: recommended panel
thickness is 1 to 3.2 mm..
11 91.4
(3.59)
45
58
(2.28)
Panel cutout
15
48
(1.89) 91.4
(3.59)
Mounting panel
Y92F-30 Socket
45
(1.77)
45
(1.77)
Note: Recommended
panel thickness
is 1 to 3.2 mm.
Panel cutout
0.5 R
max.
11
(1.77)
(1.77)
58
(2.28)
(0.69)
45
±0.15
88
(3.46)
H3CA H3CA
10
Y92F-71 Mounting Adapter
Charcoal gray panel adapter installs through panel front. Timer face fits bezel, rear of timer clips to adapter. Use P3GA-11 or P3G-08.
56
(2.2)
45
43
50 11 91.4
(3.59)
Mounting
panel
Note: Recommended panel
thickness is 1 to 3.2 mm.
45
(1.77)
Panel cutout
0.5 R max.
Socket
PROTECTIVE COVERS
Y92A-48B Hard Plastic Cover Y92A-48D Soft Plastic Cover Hard plastic cover Y92A-48B and soft
plastic cover Y92A-48D snap onto the
front of the timer to protect against dust
and water. The Y92A-48B hard plastic
cover prevents accidental resetting.
Y92A-48D soft plastic cover fits snugly
over the front and allows settings to be
changed. These covers are intended for
use in areas where unusual service
conditions do not exist.
50.5
(1.99)
50.5
(1.99) 16 (0.63 in)
overall
depth
MOUNTING TRACK AND ACCESSORIES
PFP-100N/PFP-50N DIN Rail PFP-M End Plate PFP-S Spacer
Part Input terminal numbers (no-voltage only) Power supply terminal numbers Output terminal numbers
number Gate Start Reset Check COM AC (common), DC- AC (hot), DC+ Type COM NC NO
H3CA-A 5 6 7 4 3 2 10 Timed contact 11 8 9
H3CA-FA D1 C1 B1 E1 X A2 A1 Timed contact 15 16 18
H3CA-8H – – – – – 2 7 Instantaneous 1 4 3
Timed contact 8 5 6
H3CA-8 – – – – – 2 7 Timed contact 1 4 3
Timed contact 8 5 6
Connections
55
(2.16)
58
(2.28) 68
(2.68)
H3CA H3CA
11
CONTACT SIGNAL INPUTS
Input Signal Requirements
Resistance 1 K max.
Residual voltage 1 V max. when the contact makes
Contact material Gold-plated contacts recommended
H3CA-A
• Start input contact between terminals 3 and 6.
• Reset input contact between terminals 3 and 7.
• Gate input contact between terminals 3 and 5.
• Check input contact between terminals 3 and 4.
H3CA-FA
• Start input contact between terminals X and C1.
• Reset input contact between terminals X and B1.
• Gate input contact between terminals X and D1.
• Check input contact between terminals X and E1.
H3CA-A
H3CA-FA
Reset
input Start
input Gate
input
Check
input
+
Power
SOLID-STATE SIGNAL INPUTS
Input Signal Requirements
Input type Open collector transistor
Voltage when collector is OFF 20 V min.
Saturated voltage when transistor is ON 1 V max.
Collector current 50 mA max.
Input current between collector and base 0.5 µA max.
Resistance when transistor is ON 1 K max.
Residual voltage when transistor is ON 1 V max.
Resistance when transistor is OFF 200 K min.
H3CA-A and H3CA-FA
Solid-state input terminal connections are the same as those
for contact signal inputs.
Solid-State Inputs (Not Open Collector Type)
Proximity and photoelectric sensors often have
NPN or PNP type solid-state output circuits and
rated supply voltages ranging from 6 to 30 VDC.
These signals are applied to the timer according to
the diagram below.
Solid-state circuit (proximity
sensor, proximity sensor, etc.)
(Connect Reset input between
terminals 3 and 7, and Gate
input between terminals 3 and 5.)
+5 V
0.1 mA
Start input
(Timer starts
at Low level
of this
signal.)
CUMULATIVE TIMING
Using the Gate Input with ON-Delay
When the gate signal is closed, timing is temporarily
stopped. When the gate signal opens, timing resumes
at the point of interruption. The gate input terminal
permits the timer to sum up times t1 and t2 as shown
in the timing chart.
t1 + t2 = set time
Power 2 - 10
(A1-A2)
Start 3 - 6
(X-C1)
Gate 3 - 5
(X-D1)
Reset 3 - 7
(X-B1)
Control 9 - 11
output NO (15-18)
Interruption
H3CA H3CA
12
CHECK INPUT
ON-Delay Operation
When a no-voltage input signal is applied to the timer during
the lapse of a set time, the remaining set time will become 0
and the timer will enter the next control state. Also, while the
Check Signal is applied, the elapsed time measurement of the
set time is not performed. The Check input is especially useful
where ON-delay override may be desirable.
t - a = less than set time
Reset 3 - 7
(X-B1)
Power 2 - 10
(A1-A2)
Start 3 - 6
(X-C1)
Control 9 - 11
output NO (15-18)
Check 3 - 4
(X-E1)
Reset 3 - 7
(X-B1)
Power 2 - 10
(A1-A2)
Start 3 - 6
(X-C1)
Control 9 - 11
output NO (15-18)
Check 3 - 4
(X-E1)
t + set time t - a = less than set time
Repeat Cycle Operation
The Check input signal in Repeat cycle mode allows
the timer to be used like a binary flip-flop or alternating
relay. Set an unattainable time, such as 999 hours.
Apply the no-voltage Check input to shift output status
from ON to OFF, or vice-versa. Jumper terminals 3 and 6
(X and C1) to short the start function. The Check input
then controls the output relay like a flip-flop or alternating
relay. This may be used to alternate wear on main and
secondary equipment such as pumps.
t-a
Installation
PROPER INPUT CONNECTIONS (H3CA-A, H3CA-FA)
The neutral or common of the power supply is connected
to terminal 2 (A2) of the timer. Terminal 10 (A1) should be
connected to the "hot" or positive of the power supply. Do
not apply voltage to Check, Gate, Start and Reset inputs.
These are no-voltage type inputs.
......
Power
supply
AC or DC
Input contact Load
2 (A2)
10 (A1)
8
9
11
4, 5, 6, 7
C, G, S, R
H3CA-A
(H3CA-FA)
PROPER OUTPUT CONNECTIONS
Design your control circuit using the output relay contacts to
switch the load. Never switch a load with the contact that
is being used as an input signal. The timer's circuitry may
be damaged.
PARALLEL CONNECTIONS
Parallel connection of two or more Omron Timers is possible
as shown by the diagram to the right.
This will allow the simultaneous start or restart of multiple
timers using a single switch for the Start Input and a single
switch for the Reset Input.
It is possible to wire only up to 4 timers in this manner. Wiring
more than 4 results in poor performance due to excessive
voltage drop.
Reset
Start
Com
Com
H3CA-A
Timer
H3CA-A
Timer
10
11
9
1
2
3
45678
10
11
9
1
2
3
45678
H3CA H3CA
13
Operation
SELECTING TIME RANGE
Time unit
selector
Time setting switches
Operation
mode
selector*
Time unit Timing range
0.1 s 0.1 to 99.9 seconds
s 1 to 999 seconds
0.1 m 0.1 to 99.9 minutes
m 1 to 999 minutes
0.1 h 0.1 to 99.9 hours
h 1 to 999 hours
10 h 10 to 9990 hours
Use the rightmost pushwheel switch to select the
time range. Use the three center pushwheel
switches to select the time setting between 000
and 999. For ranges with 0.1 time units, the
decimal point is assumed to be between middle
and right digits.
SELECTING OPERATION MODES (H3CA-A, H3CA-FA)
Mode Operation
A ON-delay
B Repeat cycle
C Signal Interval/OFF-delay
D Signal OFF-delay I
G Signal ON-delay/OFF-delay
H Signal OFF-delay II
E Interval
F Cycle
The operation mode is selected by the
leftmost pushwheel switch.
CAUTIONS
Do not change the time unit or time range while the timer is
in operation. Otherwise, the timer may malfunction or be
damaged. Be sure to turn off the power supply to the timer
before changing any of the selections.
Mounting
PANEL MOUNTING
Using Y92F-30 Adapter
Insert the timer through the panel cutout. Push the
Y92F-30 adapter from the rear of the timer as far forward
toward the panel as possible. Wire the P3G-❑❑ socket,
then push it onto the rear of the timer. Then, tighten the two
retaining screws. To release the adapter, lift the tab at the
rear of the adapter.
Several timers may be mounted
close together using Y92F-30 adapter as
shown here. When mounting two or more
timers in a vertical line, arrange the
adapters so that their molded tabs are
positioned on the right and left sides.
When mounting two or more timers in a
horizontal line, arrange the adapters so
that their molded tabs are positioned on
the top and bottom sides.
Panel cutout for side-by-side
mounting of two timers
Molded
tab Molded
tab
Note: *Operation mode selector not included with ON-delay timers.
H3CA H3CA
14
Removal
Installation
Mounting tabs
Panel
Retaining clips
for timer
TRACK MOUNTING
Using Y92F-70 and Y92F-71 Adapters
Install the H3CA timer, face first, into the back
side of the Y92F-70 or Y92F-71 adapter so the
bezel fits snugly. Be sure the retaining clips at the
back of the adapter fit into the slots on either side
of the timer. Compress the top and bottom tabs
of the adapter then push the adapter through the
front side of the panel cutout. Be sure the tabs
extend after installation for a
secure fit.
To remove the timer from the adapter, unclip the
two retaining clips at the back of the adapter. To
remove the adapter and timer from the panel as a
unit, compress the tabs behind the panel and
push the unit out the front of the panel.
Mounting tabs
Mounting
First hook part "A" on the rear of the
timer onto an edge of the track. Then,
press the timer in direction "B" until the
latch on the bottom rear of the timer
locks securely.
Removal
Pull the latch "C" with a flat-blade
screwdriver and remove the timer
from the mounting track.
P2CF-❑❑ Socket
For H3CA-A, H3CA-8 and H3CA-8H
H3CA-FA with Built-In Track Adapter
Mounting
The P2CF-❑❑ socket has two hooks
that secure the timer to the socket.
Be sure to allow at least 20 mm
(0.79 in) clearance above and below
the socket to gain access and to
release the hooks for servicing and
maintenance. Insert timer into the
socket. Latch hooks. Then clip rear
of the socket to the track. Push the
bottom onto the track until the latch
hooks securely.
Removal
Pull the latch on the socket with a flat-blade
screwdriver and remove the timer and socket
as one unit.
NOTE: ALL DIMENSIONS ARE IN MILLIMETERS. To convert millimeters into inches divide by 25.4.
OMRON ELECTRONICS, INC. OMRON CANADA, INC.
One East Commerce Drive 885 Milner Avenue
Schaumburg, IL 60173 Scarborough, Ontario M1B 5V8
1-800-55-OMRON 416-286-6465
Cat. No. GC TI8 11/97 Specifications subject to change without notice. Printed in the U.S.A.