H3CA H3CA
2
Part number H3CA-A H3CA-FA H3CA-8H H3CA-8
AC 24 to 240 V, 50/60 Hz 24 V, 100/110/120 V, 200/220/240 V; 50/60 Hz
DC 12 to 240 V 12 V, 24 V, 48 V, 110 V, (permissible ripple
factor: 20% max. using single-phase, full-
wave rectified power sources)
Operating voltage 90 to 110% of rated voltage
AC 3 VA 10 VA
DC 3 W 2W
Timing 8 field-selectable modes: ON-delay, Repeat ON-delay only
functions cycle, Signal Interval/OFF-delay, Signal ON-/
OFF-delay, Signal OFF-delay (I and II),
Interval and Cycle
Start, reset, gate inputs No voltage No voltage – –
Type Time limit SPDT SPDT DPDT
Instantaneous – SPDT –
Max. load 3 A, 250 VAC (p.f. = 1)
Min. load 10 mA, 5 VDC
Repeat accuracy ±0.3%, ±0.05 sec (includes variation due to voltage and temperature changes)
Setting error ±0.5%, ±0.05 sec
Resetting system Power-OFF, external and self-reset Power-OFF
Resetting time 0.5 sec max. 0.1 sec max.
Indicators Time Remaining (LCD bar graph), Output Status (LCD message)
Materials Plastic case
Mounting Panel, track, surface
Connections 11-pin round socket Terminal screws 8-pin round socket
Weight 110 g (3.9 oz) 190 g (6.7 oz) 110 g (3.9 oz)
Approvals UL/CSA/SEV
Operating ambient temperature -10° to 55°C (14° to 131°F)
Humidity 35 to 85% RH
Vibration Mechanical durability 10 to 55 Hz; 0.75 mm (0.03 in) double amplitude
Malfunction durability 10 to 55 Hz; 0.5 mm (0.02 in) double amplitude
Shock Mechanical durability 100 G
Malfunction durability 10 G
Variation due to voltage change See "Repeat Accuracy"
Variation due to temperature change See "Repeat Accuracy"
Insulation resistance 100 MΩ min. at 500 VDC
Dielectric strength 2,000 VAC, 50/60 Hz for 1 minute between current-carrying and non-current-carrying parts
and between contact and control circuit
1,000 VAC, 50/60 Hz for 1 minute between non-continuous contacts
Service life Mechanical 10 million operations minimum (under no load, at 1,800 operations/hour)
Electrical 100,000 operations minimum at maximum ratings
Specifications
Time unit
selector
Time setting switches
Operation
mode
selector*
Mode Operation
A ON-delay
B Repeat cycle
C Signal Interval/OFF-delay
D Signal OFF-delay I
G Signal ON-delay/OFF-delay
H Signal OFF-delay II
E Interval
F Cycle
Time unit Timing range
0.1 s 0.1 to 99.9 seconds
s 1 to 999 seconds
0.1 m 0.1 to 99.9 minutes
m 1 to 999 minutes
0.1 h 0.1 to 99.9 hours
h 1 to 999 hours
10 h 10 to 9990 hours
Supply
voltage
Power
consumption
Control
output
■ RANGE AND OPERATION MODE SELECTION
Note: *Operation mode selector not included with ON-delay only models.