Transformer terminal block, connection method:Screw connection, length:27.6 mm, width:13 mm, height:19
mm, color:orange, mounting type:DIN rail,Coil snap-in device
Key Commercial Data
Packing unit 1 pc
Minimum order quantity 50 pc
GTIN
GTIN 4017918060541
Weight per Piece (excluding packing) 6.250 g
Custom tariff number 85369010
Country of origin Greece
Technical data
General
Note
For transformers on ships, saltwater-proof DIN rails must be used
according to the regulations of Germanic Lloyd. This requirement is fulfilled
by all rail designs.
When selecting the type of connection on safety transformers in acc. with
IEC 742/EN 60742/DIN VDE 0551-1, please observe:
- When safety transformers are used as self-contained devices, only
screw connections are permitted for the external connections.
- When installing safety transformers, the specifications of the respective
devices must be observed.
Number of connections 2
Color orange
Insulating material PA
https://www.phoenixcontact.com/us/products/2702115
08/25/2020Page2/5
Transformer terminal block-TRK 4 OG-2702115
Technical data
General
Flammability rating according to UL 94 V2
Rated surge voltage 8 kV
Rated insulation voltage 800 V
Degree of pollution 3
Overvoltage category III
Connection in acc. with standard IEC/ EN
Nominal current IN16 A
Nominal voltage UNvoltage data only possible in conjunction with transformer
Number of positions 1
Dimensions
Width 13 mm
Length 27.6 mm
Height 19 mm
Connection data
Conductor cross section solid min. 0.75 mm²
Conductor cross section solid max. 4 mm²
Conductor cross section flexible min. 1 mm²
Conductor cross section flexible max. 4 mm²
Conductor cross section AWG min. 18
Conductor cross section AWG max. 12
Conductor cross section flexible, with ferrule without plastic sleeve min. 0.75 mm²
Conductor cross section flexible, with ferrule without plastic sleeve max. 2.5 mm²
Conductor cross section flexible, with ferrule with plastic sleeve min. 0.75 mm²
Conductor cross section flexible, with ferrule with plastic sleeve max. 2.5 mm²
2 conductors with same cross section, solid min. 0.75 mm²
2 conductors with same cross section, solid max. 4 mm²
2 conductors with same cross section, stranded min. 1 mm²
2 conductors with same cross section, stranded max. 4 mm²
Two conductors with the same cross section stranded, with ferrule and
without plastic sleeve, minimum 0.75 mm²
Two conductors with the same cross section stranded, with ferrule and
without plastic sleeve, maximum 2.5 mm²
Two conductors with the same cross section, flexible, with TWIN ferrules,
with plastic sleeve, minimum 0.5 mm²
Two conductors with the same cross section, flexible, with TWIN ferrules,
with plastic sleeve, maximum 1.5 mm²
Connection method Screw connection
Stripping length 11 mm
https://www.phoenixcontact.com/us/products/2702115
08/25/2020Page3/5
Transformer terminal block-TRK 4 OG-2702115
Technical data
Connection data
11 mm
Internal cylindrical gage A3
Screw thread M4
Tightening torque, min 1.5 Nm
Tightening torque max 1.8 Nm
Standards and Regulations
Connection in acc. with standard CSA
IEC/ EN
Flammability rating according to UL 94 V2
Environmental Product Compliance
China RoHS Environmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values
Classifications
eCl@ss
eCl@ss 10.0.1 27141110
eCl@ss 4.0 27141100
eCl@ss 4.1 27141100
eCl@ss 5.0 27141100
eCl@ss 5.1 27141100
eCl@ss 6.0 27141100
eCl@ss 7.0 27141110
eCl@ss 8.0 27141110
eCl@ss 9.0 27141110
ETIM
ETIM 2.0 EC001283
ETIM 3.0 EC001283
ETIM 4.0 EC001283
ETIM 5.0 EC000398
ETIM 6.0 EC000398
ETIM 7.0 EC000398
UNSPSC
UNSPSC 6.01 30211811
UNSPSC 7.0901 39121410
https://www.phoenixcontact.com/us/products/2702115
08/25/2020Page4/5
Transformer terminal block-TRK 4 OG-2702115
Classifications
UNSPSC
UNSPSC 11 39121410
UNSPSC 12.01 39121410
UNSPSC 13.2 39121410
UNSPSC 18.0 39121410
UNSPSC 19.0 39121410
UNSPSC 20.0 39121410
UNSPSC 21.0 39121410
Approvals
Approvals
Approvals
IMQ / CSA / UL Recognized / cUL Recognized / EAC / cULus Recognized
Ex Approvals
Approval details
IMQ http://www.imq.it/en/banca_dati/prodotti.html CA02.01301
Nominal voltage UN 750 V
mm²/AWG/kcmil 4
CSA http://www.csagroup.org/services-industries/product-listing/ 13631
B C
Nominal voltage UN 600 V 600 V
Nominal current IN 25 A 25 A
mm²/AWG/kcmil 18-12 18-12
UL Recognized http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 60425
B C
Nominal voltage UN 600 V 600 V
https://www.phoenixcontact.com/us/products/2702115
08/25/2020Page5/5
Transformer terminal block-TRK 4 OG-2702115
Approvals
B C
Nominal current IN 30 A 30 A
mm²/AWG/kcmil 16-10 16-10
cUL Recognized http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 60425
B C
Nominal voltage UN 600 V 600 V
Nominal current IN 30 A 30 A
mm²/AWG/kcmil 16-10 16-10