https://www.phoenixcontact.com/us/products/2800675
09/10/2014Page2/6
Lightning/surge arrester type 1/2-VAL-MS-T1/T2 175/12.5/1+1-2800675
Technical data
Ambient conditions
Ambient temperature (operation) -40 °C ... 80 °C
General
IEC power supply system TT
TN-C
TN-S
Housing material PBT / PA
Inflammability class according to UL 94 V0
Color black
Standards for air and creepage distances DIN EN 60664-1
EN 61643-11
Mounting type DIN rail: 35 mm
Type DIN rail module, two-section, divisible
Number of positions 2
Surge protection fault message Optical
Direction of action 1L-N & N-PE
Protective circuit
IEC test classification I / II
T1 / T2
EN type T1 / T2
Nominal voltage UN120 V AC
Maximum continuous operating voltage UC175 V AC
Maximum continuous operating voltage UC (L-N) 175 V AC
Maximum continuous operating voltage UC (N-PE) 264 V AC
UT (TOV-proof) 208 V AC (5 s / L-N)
1200 V AC (200 ms / N-PE)
Nominal frequency fN50 Hz (60 Hz)
Rated load current IL80 A (with serial 16mm² through wiring)
Residual current IPE ≤ 5 µA (per phase)
Standby power consumption PC≤ 140 mVA
Max. discharge current Imax (8/20) µs maximum (L-N) 50 kA
Max. discharge current Imax (8/20) µs maximum (N-PE) 50 kA
Nominal discharge current In (8/20) µs (L-N) 12.5 kA
Nominal discharge current In (8/20) µs (N-PE) 50 kA
Impulse discharge current (10/350)µs charge 25 As
Impulse discharge current (10/350)˽µs, specific energy 625 kJ/Ω
Impulse discharge current (10/350)˽µs, peak value limp 50 kA (N-PE)