2CDC 251 014 V0012
Data sheet
Three-phase monitoring relay
CM-PFS
The CM-PFS is a three-phase monitoring relay
that is used to monitor three phase mains for
incorrect phase sequence and phase failure.
All devices are available with two different terminal
versions. You can choose between the proven
screw connection technology (double-chamber
cage connection terminals) and the completely
tool-free Easy Connect Technology (Push-in
terminals).
Characteristics
Monitoring of three-phase mains for phase sequence and failure
Suitable for railway applications
Powered by the measuring circuit
Closed-circuit principle
Screw connection technology or
Easy Connect Technology available
Housing material for highest fire protection classification UL 94 V-0
Tool-free mounting on DIN rail as well as demounting
2 c/o (SPDT) contacts
22.5 mm (0.89 in) width
2 LEDs for the indication of operational states
Various certifications and approvals (see overview, document no. 2CDC112246D0201)
Order data
Three-phase monitoring relay
Type Rated control supply voltage = measuring voltage Connection technology Order code
CM-PFS.P 3 x 200-500 V AC
Push-in terminals
1SVR740824R9300
CM-PFS.S 3 x 200-500 V AC
Screw type terminals
1SVR730824R9300
Accessories
Type Description Order code
ADP.01 Adapter for screw mounting 1SVR430029R0100
MAR.01 Marker label 1SVR366017R0100
COV.11 Sealable transparent cover 1SVR730005R0100
2 - Three-phase monitoring relay CM-PFS | Data sheet
Connection technology
Maintenance free Easy Connect Technology with
push-in terminals
Type designation CM-xxS.yyP
Approved screw connection technology with
double-chamber cage connection terminals
Type designation CM-xxS.yyS
Push-in terminals
Tool-free connection of rigid and flexible wires with
wire end ferrule
Easy connection of flexible wires without wire end
ferrule by opening the terminals
No retightening necessary
One operation lever for opening both connection
terminals
For triggering the lever and disconnecting of wires
you can use the same tool (Screwdriver according to
DIN ISO 2380-1 Form A 0.8 x 4 mm (0.0315 x 0.157
in), DIN ISO 8764-1 PZ1 ø 4.5 mm (0.177 in))
Constant spring force on terminal point independent
of the applied wire type, wire size or ambient
conditions (e. g. vibrations or temperature changes)
Opening for testing the electrical contacting
Gas-tight
Double-chamber cage connection terminals
Terminal spaces for different wire sizes:
fine-strand with/without wire end ferrule
One screw for opening and closing of both cages
Pozidrive screws for pan- or crosshead screwdrivers
according to DIN ISO 2380-1 Form A 0.8 x 4 mm
(0.0315 x 0.157 in), DIN ISO 8764-1 PZ1 ø 4.5 mm
(0.177 in)
Both the Easy Connect Technology with push-in terminals and screw connection technology with double-chamber cage
connection terminals have the same connection geometry as well as terminal position.
2CDC 253 025 F0011
2CDC 253 026 F0011
Data sheet | Three-phase monitoring relay CM-PFS - 3
Functions
Operating controls
2CDC 251 014 V0012
1 Indication of operational states
R: yellow LED – status indication of the output
relays
F: red LED – fault message
Application
The CM-PFS is used to monitor three-phase mains for incorrect phase sequence and phase failure.
Operating mode
The three-phase main to be monitored is connected to terminals L1, L2, L3 in accordance to the wiring diagram.
The device operates according to the closed-circuit principle g – incorrect phase sequence or phase failure: relays de-
energize.
The signalling of status indication is made by means of the front-face LEDs.
Function diagram
Phase sequence and phase failure monitoring
If all phases are present with the correct phase sequence, the output relays energize after the start-up delay ts is complete.
If a phase failure or a phase sequence error occurs, the output relays de-energize instantaneously.
The LED R is on when output relays are energized.
In case of motors which continue running with only two phases, the CM-PFS detects phase failure if the reverse fed voltage
is less than 60% of the originally applied voltage.
21-22
21-24
L1, L2, L3
11-12
11-14
L1, L2, L3 L1, L2, L3 L1, L2, L3 L1, L2, L3L1, L3, L2 L1, L2 L1
L3 L2, L3ts
F: red LED
R: yellow LED
Measured value
ts = start-up delay fixed 500 ms
2CDC 252 003 F0212
1
4 - Three-phase monitoring relay CM-PFS | Data sheet
Electrical connection
L1
L2
242821252226
1418
L3
L3 1115
1216 1418 2226 2428
2125L2L1
1216 1115
1SVC 110 000 F0118
L1, L2, L3
Control supply voltage = measuring
voltage
1115-1216/1418 Output contacts –
2125-2226/2428 closed-circuit principle
Connection diagram
Technical data
Data at Ta = 25 °C and rated values, unless otherwise indicated
Input circuits
Supply circuit = measuring circuit L1, L2, L3
Rated control supply voltage Us = measuring voltage
3 x 200-500 V AC
Rated control supply voltage Us tolerance -15...+10 %
Rated frequency 50/60 Hz
Frequency range 45-65 Hz
Typical current / power consumption 400 V AC 16 mA / 11 VA
Measuring circuit L1, L2, L3
Monitoring functions phase failure
phase sequence
Measuring range 3 x 200-500 V AC
Threshold value for phase failure Umin 0.6 x Un
Hysteresis related to the threshold value -
Response time 500 ms
Timing circuit
Start-up delay tSfixed 500 ms
User interface
Indication of operational states
Relay status R1, R2 R: yellow LED V Output relay energized
Fault message F: red LED V Phase failure
W Phase sequence error
Data sheet | Three-phase monitoring relay CM-PFS - 5
Output circuits
Kind of output 11(15)-12(16)/14(18) relay, 1st c/o (SPDT) contact
21(25)-22(26)/24(28) relay, 2nd c/o (SPDT) contact
1 x 2 c/o (SPDT) contacts
Operating principle closed-circuit principle 1)
Contact material AgNi alloy, Cd free
Rated operational voltage Ue250 V AC
Minimum switching voltage / Minimum switching current 24 V / 10 mA
Maximum switching voltage / Maximum switching current see "Load limit curves" on page 7
Rated operational voltage Ue and
rated operational current Ie
AC-12 (resistive) at 230 V
4 A
AC-15 (inductive) at 230 V
3 A
DC-12 (resistive) at 24 V
4 A
DC-13 (inductive) at 24 V
2 A
AC rating
(UL 508)
utilization category
(Control Circuit Rating Code)
B 300 pilot duty;
general purpose 250 V, 4 A, cos phi 0.75
max. rated operational voltage 300 V AC
max. continuous thermal current at B 300 5 A
max. making/breaking apparent power at B 300 3600/360 VA
Mechanical lifetime 30 x 106 switching cycles
Electrical lifetime AC-12, 230 V, 4 A 0.1 x 106 switching cycles
Maximum fuse rating to achieve
short-circuit protection
n/c contact 6 A fast-acting
n/o contact 10 A fast-acting
Conventional thermal current Ith 4 A
1) Closed-circuit principle: output relays de-energize if the measured value exeeds/drops below the threshold.
General data
MTBF on request
Duty cycle 100 %
Dimensions see "Dimensional drawings"
Weight Screw connection
technology
Easy Connect Technology
(push-in)
net 0.128 kg (0.282 lb) 0.120 kg (0.265 lb)
Mounting DIN rail (IEC/EN 60715), snap-on mounting without any tool
Mounting position any
Minimum distance to other units vertical/ horizontal
≥ 10 mm (0.39 in) in case of continuous measuring voltage > 440 V
Degree of protection housing / terminal IP50 / IP20
Electrical connection
Screw connection
technology
Easy Connect
Technology (push-in)
Connnecting capacity fine-strand with(out) wire end ferrule 1 x 0.5-2.5 mm²
(1 x 18-14 AWG)
2 x 0.5-1.5 mm²
(2 x 18-16 AWG)
2 x 0.5-1.5 mm²
(2 x 18-16 AWG)
rigid 1 x 0.5-4 mm²
(1 x 20-12 AWG)
2 x 0.5-2.5 mm²
(2 x 20-14 AWG)
2 x 0.5-1.5 mm²
(2 x 20-16 AWG)
Stripping length 8 mm (0.32 in)
Tightening torque 0.6 - 0.8 Nm
(7.08 lb.in)
-
Recommended screw driver DIN ISO 2380-1: Form A /
0.8x4.0 mm
DIN ISO 8764-1: PZ 1 /
Ø 4.5 mm
-
6 - Three-phase monitoring relay CM-PFS | Data sheet
Environmental data
Ambient temperature ranges operation -25...+60 °C
storage -40...+85 °C
transport -40...+85 °C
Climatic class IEC/EN 60721-3-3 3K3
Damp heat, cyclic IEC/EN 60068-2-30 6 x 24 cycle, 55 °C, 95 % RH
Vibration, sinusoidal Class 2
Shock Class 2
Isolation data
Rated insulation voltage Uiinput circuit / output circuit 600 V
output circuit 1 / output circuit 2 300 V
Rated impulse withstand voltage Uimp input circuit / output circuit 6 kV
output circuit 1 / output circuit 2 4 kV
Basic insulation input circuit / output circuit 600 V AC
Protective separation
(IEC/EN 61140, EN 50178)
input circuit / output circuit n/a
Pollution degree 3
Overvoltage category III
Standards / Directives
Standards IEC/EN 60947-5-1, IEC/EN 60255-27, EN 50178
Low Voltage Directive 2014/35/EU
EMC directive 2014/30/EU
RoHS directive 2011/65/EU
Railway application standards
EN 50155, IEC 60571
“Railway applications – Electronic equipment
used on rolling stock”
temperature class T3
supply voltage category S1, S2, C1*), C2*)
IEC/EN 61373
“Railway applications – Rolling stock equipment – Shock and vibration tests”
Category 1, Class B
EN 45545-2 Railway applications – Fire protection on railway vehicles – part 2:
Requirements for fire behavior of materials
HL3
and components ISO 4589-2 LOI 32.3 %
NF X-70-100-1 C.I.T. (T12) 0.45
EN ISO 5659-2 Ds max (T10.03) 104
NF F 16-101: Rolling stock. Fire behaviour. Materials choosing
NF F 16-102: Railway rolling stock. Fire behaviour. Materials choosing,
application for electric equipment
I2 / F2
DIN 5510-2 Preventive fire protection in railway vehicles. Part 2: Fire behaviour
and fire side effects of materials and parts
fullfilled
*) only applicable for devices with DC supply
Data sheet | Three-phase monitoring relay CM-PFS - 7
Electromagnetic compatibility
Interference immunity to IEC/EN 61000-6-2
electrostatic discharge IEC/EN 61000-4-2 Level 3, 6 kV / 8 kV
radiated, radio-frequency, electromagnetic
field
IEC/EN 61000-4-3 Level 3, 10 V/m (1 GHz) / 3 V/m (2 GHz) / 1 V/m (2.7 GHz)
electrical fast transient/burst IEC/EN 61000-4-4 Level 3, 2 KV / 5 kHz
surge IEC/EN 61000-4-5 Level 3, 2 kV L-L
conducted disturbances, induced by radio-
frequency fields
IEC/EN 61000-4-6 Level 3, 10 V
voltage dips, short interruptions and
voltage variations
IEC/EN 61000-4-11 Class 3
harmonics and interharmonics IEC/EN 61000-4-13 Class 3
Interference emission IEC/EN 61000-6-3
high-frequency radiated IEC/CISPR 22, EN 55022 Class B
high-frequency conducted IEC/CISPR 22, EN 55022 Class B
Technical diagrams
Load limit curves
300
200
100
80
60
50
40
30
20
10
1246
10
IA
V
V
0.1 0.2 0.5
resistive load
2CDC 252 194 F0205
AC load (resistive)
300
200
100
80
60
50
40
30
20
10
1 2 4 6 10
IA
V
V
0.1 0.2 0.5
resistive load
2CDC 252 193 F0205
DC load (resistive)
cos ϕ
F
0.5
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
1.0
0.6
0.7
0.8
0.9
1.0
2CDC 252 192 F0205
Derating factor F for inductive AC load
Switching current [A]
Switching cycles
250 V
resistive load
2CDC 252 148 F0206
Contact lifetime
8 - Three-phase monitoring relay CM-PFS | Data sheet
Dimensions
in mm and
inches
113.4 4.47”
22.5 0.89”
85.6 3.37”
103.7 4.08”
105.9 4.17”
2CDC 252 009 F0011
Accessories
22.5 0.89”
68 2.68”
110.5 4.31”
8 0.32”
4.8 0.19”
front to back
2CDC 252 010 F0011
6.5
62.5
60
10 11.5
20
0.256”
2.461”
2.362”
70 2.756”
0.394”
0.787”
0.453”
2CDC 252 008 F0010
20
3A11
8
.315”
.787”
2CDC 252 186 F0005
ADP.01 - Adapter for screw mounting MAR.01 - Marker label COV.11 - Sealable transparent cover
Further documentation
Document title Document type Document number
Electronic relays and controls Catalog 2CDC 110 004 C02xx
CM-PAS, CM-PFS, CM-PSS, CM-PVS Instruction manual 1SVC 630 510 M0000
You can find the documentation on the internet at www.abb.com/lowvoltage
-> Automation, control and protection -> Electronicrelaysandcontrols -> Measuring and monitoring relays.
CAD system files
You can find the CAD files for CAD systems at http://abb-control-products.partcommunity.com
-> Low Voltage Products & Systems -> Control Products -> Electronic Relays and Controls.
ABB STOTZ-KONTAKT GmbH
P. O. Box 10 16 80
69006 Heidelberg, Germany
Phone: +49 (0) 6221 7 01-0
Fax: +49 (0) 6221 7 01-13 25
E-mail: info.desto@de.abb.com
You can find the address of your
local sales organisation on the
ABB home page
http://www.abb.com/contacts
-> Low Voltage Products
Contact us
Note:
We reserve the right to make technical changes
or modify the contents of this document without
prior notice. With regard to purchase orders, the
agreed particulars shall prevail. ABB AG does
not accept any responsibility whatsoever for
potential errors or possible lack of information in
this document.
We reserve all rights in this document and in
the subject matter and illustrations contained
therein. Any reproduction, disclosure to third
parties or utilization of its contents – in whole
or in parts – is forbidden without prior written
consent of ABB AG.
Copyright© 2017 ABB
All rights reserved