3 ( 3.35 )
6 ( 6.7 )
10 ( 11.2 )
20 ( 22.4 )
Current ratings
@40°C (25°C)
[ A ]
FN2320Y-3-06
FN2320Y-6-06
FN2320Y-10-06
FN2320Y-20-06
Filter
Fast-on H2
Fast-on K2
Fast-on K2
Fast-on L1
Conn. / Housing
125
275
285
600
Weight
[ g ]
Additional specifications
Inductance Capacitance Resistance
L L1 Cx Cy R
[ mH ] [ µH ] [ µF ] [ nF ] [ M]
1.1 30 0.33 5.5 1
1.9 70 0.33 5.5 1
1.3 40 0.33 5.5 1
1.0 30 0.33 5.5 1
Electrical schematics
FN2320Y-3-06 / FN2320Y-6-06 / FN2320Y-10-06 FN2320Y-20-06
2xL1 2xL
P
N
Cx
2 x Cy
R
Cx
P
N
E
LINE
LOAD
LINE
LOAD
2x1kOhm
2xL
P
P
Cx RCx
N
2 x Cy
N
E
2xL1
0.94
Maximum leakage
@ 230VAC/50Hz
[ mA ]
2000 1100
Filter type
-25°C - +100°C
Temperature
range
250 50/60
Maximum
operating voltage
[ VAC ] [ Hz ]
Hipot test voltage
PNE PN
[ VAC ] [ VDC ]
Operating
frequency
[ Hz ]
DC to 60All types
FN 2320
Current ratings from 3 to 20A
Broadband attenuation characteristics
UL-rated materials
Nennströme von 3 bis 20A
Breitbandige Dämpfungseigenschaften
UL konformes Material
Courants de service de 3 à 20A
Atténuation large bande
Matériaux UL
Single-phase chassis-mounting filter
Filter selection table Approvals
156
* Measurements share this common
tolerance unless otherwise stated.
FN2320Y
105
98.5 ±1
38.6 ±1
71
46.6
29.3
50.5 84.5 ±1
79
61 95
51
4.4
6
1.2
121.6
74
85
54
40.3
64
75
5.3
6.3
0.7
87
3A 6A 10A 20A
±0.5
±0.5
±0.5
±0.5
±0.5
±0.3
±0.1
±0.1
±0.1
±0.1
±1
Tol.*
[ mm ]
A
B
C
D
E
F
G
M
N
O
P
All dimensions in mm; 1 inch = 25.4mm.
Mechanical data
-3A -6A, -10A -20A
P
D
C
O
M
B
F
A
N
FN 2320 insertion loss
Per CISPR 17; A = 50/50sym, B = 50/50asym, C = 0.1/100sym, D = 100/0.1sym
3 amp types 6 amp types
dB
70
60
50
40
30
20
10
0
-10
-20
10 k 100 k 1M 10 M
A
B
C/D
dB
70
60
50
40
30
20
10
0
-10
-20
10 k 100 k 1M 10 M
A
B
D
C
10 amp types
dB
70
60
50
40
30
20
10
0
-10
-20
10 k 100 k 1M 10 M
A
B
C
D
20 amp types
dB
70
60
50
40
30
20
10
0
-10
-20
10 k 100 k 1M 10 M
A
B
D
C
P
D
C
O
N
M
B
F
A
P
B
C
O
A
F
D
N
M
G
E
Housing H2 Housing K2 Housing L1
157