Constant Current LED Driver Model Number AC-60CD1.4APPU Programmable, Digital, Wide-Range Ajustable Current & Dimming Class P Listed ELECTRICAL SPECIFICATIONS: Input Current Min PF (full load) Max THD (full load) Output Voltage Output Current T case Max Min. Starting Temp IP Rating Efficiency Up To Dimming Protocol Dimming Range 0.6A @ 120V 0.26A @ 277V >0.90 <20% 27 to 55V 700 to 1400mA 90C -40C 64 85% 0 to 10V 1 to 100% Output Input Power Power 19 to 60W 70W Input Voltage: 120-277V Input Frequency: 50/60Hz Side and Bottom Mount/Leads Options < 1 Sec. Start time Dim-to-1% (Default) WIRING: PHYSICAL: Hot Spot Dimensions Lead Lengths Black White 5.9" 5.9" Blue Red 5.9" 5.9" Purple Gray 5.9" 5.9" AC-60CD1.4APPU Length Width Height Mounting 12.8" 1.34" 1.06" 12.5" SAFETY: * Class P Listed * Class A sound rating * Overload Protection * Open/Short Circuit Protection * LED driver has a life expectancy of 50,000 hours at Tcase of 75C * LED driver has a life expectancy of INSTALLATION: * Max Remote installation distance is 18 ft * LED driver cases should be grounded 100,000 hours at Tcase of 65C * Warranty: 5 yrs based on max case temp of <75C; 3 yrs based on max case temp of 90C* * Input/Output Isolation * FCC Title 47 CFR Part 15 * Surge Protection (3 KV) * Hazardous Location (HL) * Dim-To-Off Programming Option o Active: Code = E2 04 01 04 o Inactive: Code = E2 04 00 04 * LED drivers shall be installed inside electrical enclosures * 18 AWG 600V/105C tinned stranded copper lead-wires are required for installation *AC Electronics/AC LED Power Designs warrants to the purchaser that each LED Driver will be free from defects in material or workmanship for a period of 5 years when operated at max case temp of up to <75C; 3 years from date of manufacture when operated at a max case temp of up to 90C when properly installed and under normal conditions of use. See aceleds.com for complete warranty policy. 3401 Avenue D, Arlington, TX 76011 * 800-375-6355 * www.aceleds.com Data is based upon tests performed by AC Electronics in a controlled environment and representative performance. Actual performance can vary depending on operating conditions. Specifications are subject to change without notice. All specifications are nominal unless otherwise noted. (c)2017 Revised 10/03/2017 RoHS COMPLIANT L E A D - F R E E AC-60CD1.4APPU Phone Instructions First you must have a Android device (phone/tablet) with NFC-V app downloaded. Open App; then place the device on top of the driver matching up sensors until it syncs up Basic format Write To Check: Read Insert the appropriate code from chart above Read Write Shows you the Block - 00 00 00 00 Successfully written will appear This is where the code you input appears IOUT/VOUT CURVE Use with NFC-V Reader App Available Free at Google App Store 60 55 50 Output Voltage [V] 45 40 35 30 25 20 15 10 5 0 0.5 0.7 0.9 1.1 Output Current [A] 1.3 1.5 CONTROL THE IOUT WITH THE PROGRAMMING WAND. DOWNLOAD SOFTWARE FROM http://www.aceleds.com/programmable.php 3401 Avenue D, Arlington, TX 76011 * 800-375-6355 * www.aceleds.com Data is based upon tests performed by AC Electronics in a controlled environment and representative performance. Actual performance can vary depending on operating conditions. Specifications are subject to change without notice. All specifications are nominal unless otherwise noted. (c)2017 Revised 10/03/2017 AC-60CD1.4APPU Performance Characteristics Life Time (kHours) Life Time v.s. Case Temperature Curve 180 160 140 120 100 80 60 40 20 0 30 32 35 40 45 50 55 60 65 70 75 80 85 90 Case Temperature Curve (C) Derating Curve 120Vac & 277Vac 120 Load (%) 100 80 60 40 20 0 -40 -20 0 20 40 60 80 100 Outside Driver Ambient Temperature (C) 3401 Avenue D, Arlington, TX 76011 * 800-375-6355 * www.aceleds.com Data is based upon tests performed by AC Electronics in a controlled environment and representative performance. Actual performance can vary depending on operating conditions. Specifications are subject to change without notice. All specifications are nominal unless otherwise noted. (c)2017 Revised 10/03/2017 AC-60CD1.4APPU Performance Characteristics Efficiency v.s. Load Efficiency (%) 90.00% 120V 277V 80.00% 70.00% 60.00% 50.00% 50.00% 60.00% 70.00% 80.00% 90.00% 100.00% Load (%) Power Factor v.s. Load 1 0.98 0.96 120V 277V PF 0.94 0.92 0.9 0.88 0.86 50.00% 60.00% 70.00% 80.00% 90.00% 100.00% Load (%) 3401 Avenue D, Arlington, TX 76011 * 800-375-6355 * www.aceleds.com Data is based upon tests performed by AC Electronics in a controlled environment and representative performance. Actual performance can vary depending on operating conditions. Specifications are subject to change without notice. All specifications are nominal unless otherwise noted. (c)2017 Revised 10/03/2017 AC-60CD1.4APPU Performance Characteristics Output Current (A) Output Current v.s. Dimming 2.4 2.2 2 1.8 1.6 1.4 1.2 1 0.8 0.6 0.4 0.2 0 0 1 2 3 4 4 6 7 8 9 10 Dimming (0-10V) Output Current (A) Output Current v.s. Resistance 2.4 2.2 2 1.8 1.6 1.4 1.2 1 0.8 0.6 0.4 0.2 0 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 Resistance (K) 3401 Avenue D, Arlington, TX 76011 * 800-375-6355 * www.aceleds.com Data is based upon tests performed by AC Electronics in a controlled environment and representative performance. Actual performance can vary depending on operating conditions. Specifications are subject to change without notice. All specifications are nominal unless otherwise noted. (c)2017 Revised 10/03/2017