Form No.
Page 1 of 2
BIF Doc #720018
Bussmann®
Square Body – Flush End Contact
690V (IEC) 25-400A
Electrical Characteristics Ordering Information Curves
00BTN/60
Rated I2t (A2S) 00B/60 Type T Carton
Current Clearing Watts Visual Indicator Carton Weight
Size RMS-Amps Pre-arc at 660V Loss Indicator for Micro Qty. (kg) BIF #
25 19 130 6 170M2708 170M2758
32 28.5 195 7 170M2709 170M2759
40 50 360 9 170M2710 170M2760
50 95 640 10 170M2711 170M2761
63 170 1200 12 170M2712 170M2762
80 310 2100 15 170M2713 170M2763
00 100 620 4150 20 170M2714 170M2764
125 1000 6950 25 170M2715 170M2765 5 1.35 17056312
160 1900 13000 30 170M2716 170M2766
200 3400 23000 35 170M2717 170M2767
250 6250 42000 45 170M2718 170M2768
315 10000 68500 55 170M2719 170M2769
350 13500 91500 60 170M2720 170M2770
400 18000 125000 70 170M2721 170M2771
nInterrupting rating 200kA (Estimated 300kA) RMS Symmetrical. 1 kg = 2.2 lbs. 1 lb = 0.45 kg
nWatts loss provided at rated current.
nMicroswitch indicator ordered separately.
7-11-01 SB01191
Form No.
Page 2 of 2
BIF Doc #720018
Bussmann®
The only controlled copy of this BIF document is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled.
This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right,
without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without
notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
Square Body – Flush End Contact
690V (IEC) 25-400A
Total Clearing I2t
The total clearing I2t at rated voltage and
at power factor of 15% are given in the
electrical characteristics. For other volt-
ages, the clearing I2t is found by multi-
plying by correction factor, K, given as
a function of applied working voltage,
Eg, (RMS).
Arc Voltage
This curve gives the peak arc voltage,
UL, which may appear across the fuse
during its operation as a function of the
applied working voltage, Eg, (RMS) at a
power factor of 15%.
Power Losses
Watts loss at rated current is given in
the electrical characteristics. The curve
allows the calculation of the power
losses at load currents lower than the
rated current. The correction factor, Kp,
is given as a function of the RMS load
current, Ib, in % of the rated current .
Electrical Characteristics
54 Max
64
30
48
62
M8
6
Indicator
Dimensions
Flush End Contact: Type 00B/60, 00BTN/60
Dimension in mm.
1mm = 0.0394∑ 1∑ = 25.4mm
UL
1.4
1.2
103
6
8
7
9
5
4
3Eg
200 300 400 500 600 690
UL
1.4
1.2
103
6
8
7
9
5
4
3Eg
200 300 400 500 600 690
Kp
30 40 50 60 70 80 90 100%
Ib
1.0
0.8
0.4
0.5
0.6
0.3
0.2
0.1
7-11-01 SB01191