Lower Current Three Phase RFI Filters
Specifications
Maximum leakage current, each line-to-ground:
3, 6, 10A 20A
@ 120 VAC 60 Hz: 2.0 mA 3.5mA
@ 250 VAC 50 Hz: 3.0 mA 5.5mA
Hipot rating (one minute):
line-to-ground 1500 VAC
line-to-line 1450 VDC
Operating frequency: 50/60 Hz
Rated voltage (max.):
phase-to-phase 440 VAC
phase-to-neutral/ground 250 VAC
Rated current:
03AYO1 3A
06AYO1 6A
10AYO1 10A
20AYO1 20A
Minimum insertion loss in dB:
Line-to-ground in 50 ohm circuit
Current Frequency-MHz
Rating .15 .5 1 5 10 30
03A 12 23 29 33 38 35
06A 7 23 30 40 50 30
10A –– 5 16 28 15
20A – 7 11 32 23 12
Line-to-line in 50 ohm circuit
Current Frequency-MHz
Rating .15 .5 1 5 10 30
03A – 12 20 50 35 30
06A 10 18 24 31 28 28
10A 10 18 24 42 28 22
20A 10 18 24 42 38 23
18
Catalog 1654001 Dimensions are in inches and Dimensions are shown for USA Cust. Svc.: 1-800-468-2023 www.corcom.com
Revised 05-07 millimeters unless otherwise reference purposes only. CORCOM Prods: 1-847-680-7400 www.tycoelectronics.com
specified. Values in italics Specifications subject Germany: 49-89-6089-0
are metric equivalents. to change.
AYO Series
AYO Series
CORCOM Product Guide
UL Recognized
CSA Certified
VDE Approved
The AYO series filters are designed for 3-phase, four wire,
WYE applications providing filtering in each of the three
lines plus neutral.
These lower current RFI filters provide filtering to industrial
3-phase applications.
Electrical Schematic
AYO1
Resistor location for reference only.Resistor location for reference only.