s
Copyright © Siemens AG 2008
Siemens Aktiengesellschaft A5E01648459-01
SIMATIC
Product Information
07/2008
For the programming manual from PROFIBUS DP to PROFINET IO, Edition 10/2006,
A5E00298268-03
This product information contains important information on new and revised diagnostics
data records. The Product Information is part of the supplied product and the statements made
therein are binding in case of doubt.
기기는 업무용(A) 전자파 적합기기로서 판매자 또는 사용자는 점을 주의하시기 바라며 가정 외의 지역에서 사용하는 것을 목적으로 합니다.
Product Information
2 A5E01648459-01
For chapter 5 "Data records for PROFINET IO"
Overview of relevant data records for PROFINET IO
The following information is an addendum to the manual, section
5.1.2
.
Data records on the status of PROFINET interfaces
Data record number Content and meaning Size in bytes
W#16#802A The data record supplies the latest port settings. 0 - 4176
W#16#802B /
W#16#802F
The data record supplies the configured port settings. 0 - 4176
W#16#802D The data record supplies the configured settings for the
synchronization.
0 - 4176
W#16#8060 The data record supplies the latest settings of the optical port. 0 - 4176
W#16#8061 /
W#16#8061
The data record supplies the configured settings of the optical port. 0 - 4176
W#16#8070 The data record supplies the configured settings of the PROFINET
interface.
0 - 4176
W#16#8080 The data record supplies the latest settings of the PROFINET
interface.
0 - 4176
W#16#F831 The data record supplies the collective data record for the configured
settings of the PROFINET interface and its ports (settings of the IRT
parameters only).
0 - 4176
W#16#F841 The data record supplies the collective data record for latest settings
of the PROFINET interface and its ports.
0 - 4176
W#16#F842 The data record supplies the collective data record for the configured
settings of the PROFINET interface and its ports.
0 - 4176
Product Information
A5E01648459-01
3
Additional information
Detailed information on data records are available in the PROFINET specification "Application
Layer services for decentralized periphery and distributed automation" and "Application Layer
protocol for decentralized periphery and distributed automation" in version V2.2 on the Internet
pages of the PROFIBUS user organization under www.profinet.com.
Blocks of diagnostics and configuration data records
The following information is an addendum to the manual, section
5.5.9
, table 5-23.
Coding of ExtChannelErrorType for ChannelErrorType "Incorrect neighborhood"
Value (hexadecimal) Meaning
W#16#0000 Reserved
W#16#0001 W#16#7FFF Manufacturer-specific
W#16#8000 Incorrect neighbor device
W#16#8001 Incorrect neighbor port
W#16#8002 Neighbor does not support RealTime Class 3 or
is not configured
W#16#8003 Error due to incorrect interface setting full
duplex and half duplex
W#16#8004 Incorrect or missing media redundancy
configuration
W#16#8005 No neighbor present
W#16#8006 Neighbor does not support smooth media
redundancy
W#16#8007 Error due to difference in determining cable
length
W#16#8008 Same Sync domain name used in several
instances / several Sync masters exist
W#16#8009 W#16#8FFF Reserved
W#16#9000 W#16#9FFF Reserved for profiles
W#16#A000 W#16#FFFF Reserved
Product Information
4 A5E01648459-01
Coding of ExtChannelErrorType for ChannelErrorType "Synchronization error" and "Error time
basis"; table 5-25 in manual
Value (hexadecimal) Meaning
W#16#0000 Reserved
W#16#0001 W#16#7FFF Manufacturer-specific
W#16#8000 Sync slave no longer synchronized
W#16#8001/ W#16#8002 Reserved
W#16#8003 Synchronization error
W#16#8004 W#16#8FFF Reserved
W#16#9000 W#16#9FFF Reserved for profiles
W#16#A000 W#16#FFFF Reserved
Product Information
A5E01648459-01
5
User Structure Identifier
The following information is an addendum to the manual, section
5.5.16
, table 5-42 in the
manual.
Coding of USI (UserStructureIdentifier)
Value (hexadecimal) Meaning Description
W#16#0000 - W#16#7FFF Manufacturer-specific In connection with Alarm Type
diagnostics incoming/going
manufacturer-specific
Diagnostics in AlarmNotification
and Diagnosis Data.
In connection with other Alarm
Types, the use is manufacturer-
specific.
W#16#8000 ChannelDiagnosis Use in connection with
ChannelDiagnosis in
AlarmNotification and Diagnosis
Data.
W#16#8001 Multiple Only in connection with data
that correspond to the structure
of "(BlockHeader, Data*)*."
BlockType still corresponds with
the used AlarmType.
W#16#8002 ExtChannelDiagnosisData Use only in connection with
ChannelDiagnosisWithAddInfo
in AlarmNotification and
Diagnosis Data.
W#16#8003 Qualified Graduated extended channel
diagnostics
W#16#8004 - W#16#80FF Reserved
W#16#8100 Maintenance Maintenance
W#16#8101 - W#16#81FF Reserved
W#16#8200 Reserved
W#16#8201 iParameter
- W#16#8202 - W#16#8FFF Reserved
W#16#9000 - W#16#9FFF Reserved for profiles Reserved for profiles
W#16#A000 - W#16#FFFF Reserved
Product Information
6 A5E01648459-01