E3X-DA E3X-DA
15
Use the attached saddle to secure the end cap of the protective
spiral tube. To secure the protective spiral tube at a position other
than the end cap, apply tape to the tube so that the portion
becomes thicker in diameter.
Saddle
End cap
Tube
E39-F10 Fiber Connector
Mount the fiber connector as shown in the following illustrations
Splice
Retention clip
Retention clip
Fiber
Each fiber unit should be as close as possible before they are
connected.
Sensing distance will be reduced by approximately 25% when
fibers are connected.
Only 2.2-mm-dia. fibers can be connected.
Precautions
AVOID DAMAGE TO THE E3X-DA
•Voltage must not exceed the rated voltage of the E3X-DA.
•When supplying power to the E3X-DA, make sure that the
polarity of the power is correct.
•Do not short-circuit the load connected to the E3X-DA.
•Do not impose 100 VAC or more on models that operate
with DC.
•Do not use the E3X-DA in environments where flammable or
explosive gas exists.
•Do not disassemble, repair or modify the E3X-DA.
•The E3X-DA has an enclosure rating of IP50; do not immerse
in water.
•Load must be connected to the E3X-DA.
INSTALLATION
Power Reset Time
•The E3X-DA is ready to sense objects 100 ms after the unit
is turned on.
•If power is supplied to the E3X-DA and the load
independently, make sure to turn ON the E3X-DA first.
•When the E3X-DA is turned ON or OFF, the operation indica-
tor will be illuminated for an instant, but no control output will
be turned ON.
Power Supply
•Do not connect the E3X-DA to a full-wave or half-wave
rectified power supply.
•When a standard switching power supply is used, the frame
ground (FG) and the ground (G) terminal must be grounded.
Otherwise, the E3X-DA may experience noise problem.
WIRING
Cable
•The cable can be extended up to 100 m provided the wire
thickness is at least 0.3 mm2.
•Do not pull cables with pulling force exceeding 50N.
Avoid Damage or Malfunction Due to Induction Noise
•Never run the E3X-DA cables in the same conduit with power
lines or high tension cables.
Mutual Interference Protection Function
•Perform two-point teaching if two or three fiber units are
closely mounted. Only apply power to the unit that is in
teaching operation or block the emitters of the fiber units that
are not in teaching mode.
FURTHER INFORMATION
Correcting an EEPROM Error
•An EEPROM error may result if power failure or static noise
occurs. In this case, repeat the whole teaching procedure.