Publication No: US-CYC-SG-003 - June 2008
1973 TO 2008
SELECTION GUIDE
Powered by more than 100 years
of expertise, EnerSys® is the
world’s largest industrial battery
manufacturer, operating 21
facilities worldwide. Along with
manufacturing and distributing a
wide range of reserve power and
motive power batteries, chargers,
power equipment, and battery
accessories, EnerSys provides
unmatched aftermarket and
customer support to its customers
in over 100 countries worldwide.
Wherever the world
needs stored energy,
EnerSys® is there.
2
EnerSys® Value-Added Services
In addition to our manufacturing capability, EnerSys®
is proud to provide its customers with the following
services:
Customized manufacturing design
Battery recycling
Online technical information
Charging support
Product testing
On-site technical seminars
Battery samples
Application engineering
Technical documentation
Charger evaluation to determine
compatibility with CYCLON® batteries
Applications
Batteries from the EnerSys “pure lead” family are
used in a wide variety of standby and portable/cyclic
applications including those in:
Telecommunications
Electronics
Uninterruptible power supplies
Defense installations
Aviation (may require FAA or other appropriate
agency certification/approval for installation in
aircraft)
Computer back-up
Electric vehicles
Medical equipment
Solar power
Lawn and garden equipment
Extreme temperature environments
(-65°C to +80°C or -85°F to +176°F) for single cells
The EnerSys® plant in Warrensburg, Missouri covers
32,000 square feet and is situated on 33 acres.
83
TABLE OF CONTENTS
Company background
EnerSys® .................................................................................................................... 2
Services and applications ......................................................................................... 2
Features and benefits ............................................................................................... 5
Technical information
Capacity as a function of temperature ..................................................................... 7
State of charge .......................................................................................................... 7
Storage time as a function of temperature ............................................................... 7
Charging recommendations ...................................................................................... 7
CYCLON® Battery Single Cells
CYCLON® product family .......................................................................................... 8
CYCLON® battery alternate configurations .............................................................. 9
CYCLON® battery standard descriptions ................................................................. 9
CYCLON® battery Single Cell performance specifications .................................... 10
CYCLON® battery Single Cell standard assemblies .............................................. 11
CYCLON® battery BC Single Cell performance specifications .............................. 12
CYCLON® battery Single Cell mechanical specifications ...................................... 13
CYCLON® battery BC Single Cell mechanical specifications ................................ 13
CYCLON® battery Single Cell constant current (CC)
and constant power (CP) discharge graphs ........................................................... 14
CYCLON® Battery Monobloc
4V/6V Monobloc performance specifications ........................................................ 15
4V/6V Monobloc standard assemblies ................................................................... 16
4V/6V Monobloc mechanical specifications ........................................................... 17
4V/6V Monobloc constant current (CC)
and constant power (CP) discharge graphs ........................................................... 18
Quick reference list
Standard product listing .......................................................................................... 19
CYCLON
®
BATTERY SELECTION GUIDE
4Publication No: US-CYC-SG-003 - June 2008
www.enersys.com
Resealable safety valve
A 50-PSI vent lets gases escape, then automatically reseals, so there’s no
risk of excessive gas accumulation within the battery, or “dry out” failure
from repeated recharges.
Pure lead plates
Made from 99.99% pure lead, CYCLON® battery plates are extremely thin,
so they offer more surface area than conventional batteries –
and far more power.
AGM plate separator
High-purity acid is absorbed right into the Absorbed Glass Mat (AGM)
plate separators, so the CYCLON battery provides leak-proof operation
in any position.
Steel can enclosure
The CYCLON battery’s metal outer jacket offers extreme shock, vibration,
temperature, and flammability protection.
Powerful design
One-piece plastic cover
Direct thru-the-wall
intercell connections
One-piece plastic case
Features and Benefits
Sealed pure-lead cells were invented by the Gates
Corporation in 1973. The purity of the materials used is key
to supporting the CYCLON® battery's performance benefits.
A longer service life, meaning fewer replacements and the
cost associated with it, combined with higher reliability and
fewer system failures, result in a lower long-term cost of
ownership to the end user or equipment owner.
What are the advantages of EnerSys® technology?
1. Power density - Per unit weight, the power provided by
pure lead products offers the greatest high-rate power
density for your energy dollar. CYCLON battery's greater
volumetric power allows engineers to consider more
energy-supporting features or design smaller,
lighter packages.
At high-rate and pulse discharges, EnerSys® CYCLON
batteries offer the best performance value when
compared with competitive product in applications
at less than 100 minutes of discharge.
2. Cycle life - Compared to competitive lead products
(offering up to 200 full cycles), pure lead batteries provide
50% to 200% greater full cycle capability. CYCLON
batteries will deliver up to 300 cycles (100% DOD, C/5).
And, because CYCLON batteries incorporate a high
vent-pressure design, EnerSys products experience
no “dry out” failure mode from repeated recharges.
3. Float life - Conventional sealed-lead batteries vary
greatly in specified standby life: from three to six years
at 20°C, C/20. CYCLON battery Single Cells, however,
offer a ten-year design life at 25°C, C/5, to 80% of rated
capacity. At 20°C, CYCLON battery Single Cells offer a
fifteen-year design life.
4. High stable voltage delivery - The high stable voltage
delivery of a pure lead battery results from its low internal
resistance. The flat discharge voltage profile of our
batteries, similar to nickel cadmium, combined with our
products' low internal resistance, means our batteries are
able to discharge and recharge their power more quickly
and efficiently and offer greater application flexibility. The
pure lead construction also gives more watts-per-unit
weight at high discharge rates.
5. Safety - Since CYCLON battery Single Cells and
Monoblocs emit minimal to no gassing under normal
charging conditions they are safe for installation in
offices, aircraft cabins, hospitals or any other environment
occupied by human beings. Underwriters Laboratories
(UL) recognizes all CYCLON cells and batteries as
components.
6. Widest temperature range - Due to the products' strong
construction and high vent pressures, these cells will
maintain their performance and physical parameters in
extreme conditions. At high temperatures, the chemical
reaction in a battery that causes aging is accelerated.
Pure lead technology resists that chemical reaction more
effectively than alloyed lead, thus allowing a battery to
have a longer service life. At high temperatures, when
conventional lead batteries experience internal moisture
loss from venting and case side wall distention, the
CYCLON Single Cell battery, with its steel can (jacket)
and 50psi vent, does not experience these life-robbing
conditions. CYCLON batteries have twice the delivered
capacity of conventional sealed-lead batteries at
temperatures below -2C, offering unparalleled
low-temperature performance.
Our batteries have thinner plates, and therefore greater
plate surface area than conventional sealed-lead, thick
plate batteries. As a result our batteries can reach a high
state of charge in fast-charging applications in one-fourth
the time of conventional, sealed-lead, thick-plate batteries.
This is 50% to 100% overall better performance for your
energy dollar.
7. Rugged construction - Due to their strong external
packaging and internal pure lead composition, EnerSys
products can withstand not only extreme temperatures
but also harsh usage.
CYCLON battery Single Cells are available housed
in cases constructed of UL 94V-0 rated material. The
CYCLON battery Single Cell itself is in a metal jacket
giving added flammability protection. CYCLON batteries
are shock and vibration resistant, designed to offer higher
tolerance levels to meet demanding applications, including
those in commercial and outdoor applications. The
company's focus on battery-case integrity and high vent
pressure, coupled with pure lead's low grid-corrosion rate,
means CYCLON battery cells and Monoblocs provide the
longest service life possible.
5
Publication No: US-CYC-SG-003 - June 2008
www.enersys.com
CYCLON® Battery Single Cell/Monobloc comparison chart
Single Cells 3 atm Metal outer case & -65°C to +80°C 2 volt cells
venting pressure spiral construction
Monobloc 0.5 atm Plastic outer case & -40°C to +40°C 4 & 6 volt units
venting pressure spiral construction
Design Construction Operating range Voltages
6Publication No: US-CYC-SG-003 - June 2008
www.enersys.com
Each plastic Monobloc consists of Single Cell elements,
internally connected to provide a 4 or 6 volt unit.
Monoblocs or Single Cells can be connected in series
or parallel to achieve the required voltage or capacity.
Monoblocs and Single Cells are supplied with spade
terminals making electrical connections quick and easy.
Additionally, EnerSys® products offer the highest vent
pressure in the market. As a result, our batteries are
more resistant to venting and dryout from continuous
overcharge in standby applications.
8. Fastest recharge - EnerSys pure lead chemistry
allows our batteries and cells to offer the highest
recharge efficiency of any sealed-lead battery on the
market. With pure lead, you can achieve a 95%
state of recharge in less than one hour - without loss
of capacity or electrolyte using conventional
constant-voltage charging techniques.
Flexible charging options are possible with CYCLON®
battery Single Cells and Monoblocs, as no current limit is
required when using a constant voltage charger.
9. Orientation/placement/transport - Due to the products'
mechanical design, CYCLON batteries can be mounted
and operated in any position, an attractive feature for less
accessible areas.
CYCLON battery Single Cells offer UL 94V-0 flame-
retardant packaging, thus allowing the mounting of
systems in sensitive areas and human environments.
Plus, the unique and flexible 2-volt CYCLON battery
Single Cell allows you to design your system using
an almost infinite number of packaging/design
configurations.
Effective September 30, 1995, CYCLON battery Single
Cells and Monoblocs were classified as “nonspillable
batteries”, and are excepted from the Department of
Transportation's comprehensive packaging requirements
if the following conditions are satisfied: (1) The battery
is protected against short circuits and is securely
packaged and (2) The battery and outer packaging
must be plainly and durably marked “NONSPILLABLE”
or “NONSPILLABLE BATTERY”. CYCLON battery
shipments from the EnerSys plant in Warrensburg,
Missouri will be properly labeled in accordance with
applicable regulations. Packaging changes performed
at other locations may require additional labeling, since
in addition to the battery itself containing the required
marking, the outer packaging of the battery must also
contain the required marking: “NONSPILLABLE” or
“NONSPILLABLE BATTERY”.
CYCLON battery Single Cells and Monoblocs have been
tested and determined to be in compliance with the
vibration and pressure differential tests contained in 49
CFR § 173.159(d).
Because CYCLON battery Single Cells and Monoblocs
are classified as “Nonspillable” and meet the conditions
above, [from § 173.159(d)] they do not have an assigned
UN number nor do they require additional DOT hazard
labeling.
The regulation change effective September 1995, was
to clarify and distinguish to shippers and transporters,
all batteries that have been tested and determined to
be in compliance with the DOT Hazardous Material
Regulations, the International Civil Aeronautics
Organization (ICAO), and the International Air Transport
Association (IATA) Packaging Instruction 806 and Special
Provision A67, and therefore excepted from all other
requirements of these regulations and classified as a
“nonspillable battery”.
10. Shelf life - Pure lead batteries have an extremely low
self-discharge rate, thus providing extended storage
capability while maintaining high state-of-charge levels
for dependable operation.
CYCLON battery Single Cells and Monoblocs have
a shelf life more than two times that of conventional
lead batteries. To assure maximum reliability, EnerSys
recommends that all stored cells/batteries be recharged
(boost charged) once every 24 months or when the open
circuit voltage drops to 2.00 volts per cell, whichever
occurs earlier. Inventory should be checked more
frequently if storage temperature regularly exceeds 25°C.
The pure lead advantage
0.01
0.1
1
10
-40 -30 -20 -10 0 10 20 30 40 50
Discharge time, hours
Temperature, ºC
15 MIN RATE C RATE C/5 RATE
7
Publication No: US-CYC-SG-003 - June 2008
www.enersys.com
1.90
1.93
1.96
1.99
2.02
2.05
2.08
2.11
2.14
2.17
10 20 30 40 50 60 70 80 90 100
OCV, V
State of Charge, %
Capacity as a function of temperature for CYCLON® Battery Single Cells &
Monoblocs (use graph up to 40°C for Monoblocs)
State of charge for CYCLON® Battery Single Cells & Monoblocs
Storage time as a function of temperature for CYCLON® Battery Single Cells
& Monoblocs (fully charged cell)
Charging recommendations:
Broadly speaking, a battery may be
recharged using either a constant
voltage (CV) charger or a constant
current (CC) charger, or a modification
of either or both of these.
The exact regime chosen generally
depends upon the time and economic
constraints imposed by the system.
Constant current charging is widely
used in cyclic applications where a
recharge must be accomplished in a
relatively short time period. Constant
voltage charging, where a single
voltage level is applied across the
battery terminals, is the most suitable
method to recharge CYCLON®
batteries. Depending on the CV
charger's current limit, it is possible
to recharge these batteries from a
100% discharged condition to better
than 95% state of charge in less than
one hour, using only the cyclic charge
voltage.
Constant voltage charging
Constant voltage (CV) charging
should be within the following ranges:
Fast Chargers, Per cell:
2.45 to 2.50 volts @ 25°C
12 volts:
14.70 to 15.0 volts @ 25°C
(for a maximum of 16-20 hours)
Float Chargers, Per cell:
2.27 to 2.35 volts @ 25°C
12 volts:
13.62 to 14.10 volts @ 25°C
To avoid thermal runaway in warmer
temperatures, and to improve charge
acceptance in colder temperatures,
the charger voltage should be
compensated by approximately
3 millivolts per cell per degree
Centigrade variance from 25°C.
This is a negative coefficient, with
the voltage being lowered as the
temperature increases, and vice versa.
8Publication No: US-CYC-SG-003 - June 2008
www.enersys.com
There is no need to limit the inrush current to the battery
during constant voltage charging. The low internal
resistance of EnerSys® CYCLON® battery Single Cells and
Monoblocs allows for large inrush current without damage.
Since not all of the charge returned is accepted to replenish
the electro-chemical potential, a good rule of thumb to use
is that the charge returned should be 105% to 110% of the
capacity delivered on the previous discharge.
Most current waveforms are not pure DC nor are they pure
sine waves. Therefore, consult the EnerSys Application
Support Department for assistance when evaluating the
charger current waveforms for your specific application.
A three-step 6-8 hour charge profile optimized for CYCLON
cells and batteries is available on request from the Technical
Support Department of EnerSys.
Internal Nominal
res. of fully short circuit Height with
Products Capacity Part charged cell current for Diameter Height terminals Weight Tabs
Number mΩ @ 25°C charged cell in. mm in. mm in. mm oz. gm in. mm
D cell 2.5Ah 0810-0004 5.0 400A 1.35 34.3 2.41 61.2 2.68 68.1 6.28 178.0 .187x.025 4.75x0.64
DT cell 4.5Ah 0860-0004 5.0 400A 1.35 34.3 3.78 96.0 4.05 102.9 9.68 274.4 .187x.025 4.75x0.64
X cell 5.0Ah 0800-0004 3.5 570A 1.75 44.5 2.87 72.9 3.21 81.5 12.77 362.0 .250x.025 6.35x0.64
E cell 8.0Ah 0850-0004 3.0 665A 1.75 44.5 3.94 100.1 4.28 108.7 17.28 489.9 .250x.025 6.35x0.64
J cell 12.0Ah 0840-0004 2.5 800A 2.04 51.8 4.85 123.2 5.34 135.6 29.60 839.2 .312x.032 7.92x0.81
BC cell 25Ah 0820-0004 1.5 1335A 2.57 65.3 6.25 158.8 6.82 173.2 58.88 1669.2 M6 (-) and
M8 (+) terminals
DIMENSIONS
Internal res. Nominal
of fully charged short circuit Height with
Products Capacity Part Monobloc current for Diameter Height terminals Weight Tabs
Number mΩ @ 25°C charged cell in. mm in. mm in. mm oz. gm in. mm
D cell 2.5Ah 0819-0010 10.0 400A 3.13 79.5 1.81 46.0 2.75 69.9 .80 .36 .187x.025 4.75x0.64
X cell 5.0Ah 0809-0010 7.0 570A 3.80 96.5 2.12 53.8 3.02 76.7 1.62 .74 .250x.025 6.35x0.64
E cell 8.0Ah 0859-0010 6.0 665A 3.81 96.8 2.13 54.1 4.00 101.6 2.11 .96 .250x0.25 6.35x0.64
DIMENSIONS
CYCLON® Battery Product Family (All capacities at 10 hr. rate 25°C to 1.67Vpc)
CYCLON® Battery 2V Single Cell:
CYCLON® Battery 4V Monoblocs:
Internal res. Nominal
of fully charged short circuit
Products Capacity Part Monobloc current for Length Width Height Weight Tabs
Number mΩ @ 25°C charged cell in. mm in. mm in. mm lb. kg in. mm
D cell 2.5Ah 0819-0012 15.0 400A 4.48 113.8 1.81 46.0 2.75 69.9 1.15 .52 .187x.025 4.75x0.64
X cell 5.0Ah 0809-0012 10.0 570A 5.48 139.2 2.12 53.8 3.02 76.7 2.16 .98 .250x0.25 6.35x0.64
E cell 8.0Ah 0859-0012 8.0 665A 5.48 139.2 2.13 54.1 4.00 101.6 3.15 1.43 .250x0.25 6.35x0.64
DIMENSIONS
CYCLON® Battery 6V Monoblocs:
CYCLON® battery standard descriptions
CYCLON battery cells are ideal for small ampere-hour
applications up to 25Ah. The sealed-lead construction
uses a starved-electrolyte system and a patented
grid-alloy providing numerous advantages.
Standard batteries are offered based on combinations of
the previously described CYCLON battery cells and are
available in 6 and 12 volt configurations with capacities
ranging from 2.5Ah to 25Ah.
Battery Packages
Rigid plastic cases or shrink wrap packaging are available.
Rigid Plastic
Cases are available for most designs in either flame-
retardant ABS material, meeting UL 94V-0 flammability
rating, or Styrene (available only in 2X3 D and X battery
configurations). Some cases have mounting holes. Rigid
plastic cases are recommended for applications in which
the battery must withstand vibration, movement or extreme
weather conditions.
Shrink Wrap
Shrink wrap packaging is less expensive and smaller in
size and weight. A plastic extrusion insulates the battery
top and keeps the cells in line. A heavy duty shrink sleeve
holds the cells firmly in place. Shrink wrap packaging
is recommended for applications in which the battery
remains stationary.
Battery Terminations for Single Cell and Monoblocs
Tab/Stud
Tab Adapters (D, DT, X, and E)
Available to convert .187" tabs to .250" tabs, 0.032" thick,
and vice versa.
BC Quick Disconnect Terminals
AMP series 250 Faston terminals are available for BC
batteries.
Connection Terminations
A wide variety of terminations are offered. For
recommendations or to specify; contact your EnerSys®
Territory Manager or battery assembler.
Fusible Links
Specify your requirement.
9
Publication No: US-CYC-SG-003 - June 2008
www.enersys.com
CYCLON® Battery Single Cell
Alternative battery configurations
Standard battery configurations are rectangular in
overall shape. A sample of other possible configurations
are illustrated below. These can be held together with
tape (offering the lowest cost and minimum electrical
and mechanical protection) or by shrink wrapping. The
CYCLON® battery Single Cell can be custom configured
in virtually an infinite number of designs.
Rectangular Rhomboid
Nested Trapezoid
Tubular Flat Pack
D .187” x .025”
DT .187” x .025”
X .250” x .025”
E .250” x .025
J .312” x .032”
BC 6mm post (negative)
8mm post (positive)
Cell size Dimensions
High integrity
terminal seal
Metal can
enclosure
Plastic internal
container
Lead grids
Resealable
Safety vent
Positive and
negative plates
Highly retentive
separator
10 Publication No: US-CYC-SG-003 - June 2008
www.enersys.com
Lead Wires
Stranded copper wire with insulation meeting UL1015
specifications (Red +, Black -). Standard leads extend 9 inches
outside the battery pack. Ends are stripped and dipped in wax,
which must be removed before use.
Standard wire gauges are:
D batteries 18AWG, UL1015
DT batteries 16AWG, UL1015
X batteries 16AWG, UL1015
E batteries 14AWG, UL1015
J batteries 14AWG, UL1015
BC batteries 12AWG, UL1015
Varying lead lengths and gauges are also available;
please specify to your EnerSys® Territory Manager or
battery assembler.
Intercell Connections
Standard
D, DT, X and E batteries—welded tin-plated steel connector
J batteries—soldered, stranded wire
BC batteries—solid copper
For vibration-prone applications
D, DT, X, E and J batteries—soldered, stranded wire
BC batteries—braided copper straps
Products 5 min 10 min 15 min 30 min 60 min 90 min 5 hr 8 hr 10 hr 20 hr
D cell (2.5Ah) 14.8 8.1 5.9 3.4 1.9 1.4 .48 .32 .26 .13
DT cell (4.5Ah) 25.2 15.0 11.2 6.6 3.7 2.6 .85 .55 .45 .24
X cell (5.0Ah) 27.3 17.8 13.2 7.0 3.9 2.8 .96 .61 .50 .26
E cell (8.0Ah) 41.7 26.4 19.0 11.0 6.2 4.4 1.6 1.0 .81 .42
J cell (12.0Ah) 51.7 38.1 29.4 18.0 9.2 6.5 2.3 1.5 1.20 .66
DURATION
Constant current discharge/amps to 1.67Vpc @ 25°C
Products 5 min 10 min 15 min 30 min 60 min 90 min 5 hr 8 hr 10 hr 20 hr
D cell (2.5Ah) 26.4 16.1 11.6 6.7 3.8 2.7 .94 .61 .50 .25
DT cell (4.5Ah) 45.0 28.1 21.0 12.5 7.1 5.1 1.7 1.1 .90 .46
X cell (5.0Ah) 45.4 31.9 23.9 13.9 7.8 5.6 1.9 1.2 1.0 .51
E cell (8.0Ah) 77.8 51.0 35.5 21.1 12.4 8.9 3.1 2.0 1.6 .85
J cell (12.0Ah) 90.4 68.4 53.4 31.6 18.3 13.2 4.7 3.0 2.3 1.3
DURATION
Constant power discharge/watts per cell to 1.67Vpc @ 25°C
Products Cyclic Float Storage & Charge C/5 Cycle life Float life at
discharge 100% DOD 25°C (20°C)
D, DT, X, E & J cell CV 2.45-2.50 CV 2.27-2.35 -65°C to +80°C -40°C to -80°C 300 10 years
CC* CC* (15 years)
CHARGING PER CELL TEMPERATURE RANGE LIFE EXPECTANCY
Charging/Temperature/Life:
Maximum recommended storage time before recharge - 24 months @ 25°C or 2.0Vpc, whichever is earlier
Atmospheric pressure range - Vacuum to 8 atmospheres
*Users planning to use CC should consult the EnerSys® Application Support Department.
UL Recognized Component. Meets UL 1989
Caution: Batteries contain toxic materials (Pb and H2SO4) • Avoid short circuit • Do not charge in gas-tight container
Sealed-lead rechargeable battery must be recycled or disposed of properly. Contact EnerSys® Customer Service for details.
CYCLON® Battery Single Cell performance specifications
11
Publication No: US-CYC-SG-003 - June 2008
www.enersys.com
CYCLON® Battery Single Cell standard assemblies
CYCLON® Battery 6 Volt 1x3 Shrink Wrap
CYCLON® Battery 6 Volt 1x3 ABS Case
CYCLON® Battery 12 Volt 2x3 ABS and Styrene Cases
CYCLON® Battery 12 Volt 2x3 Shrink Wrap
CYCLON® Battery 12 Volt 1x6 ABS Case
0810-0102 2.5Ah D Dbl. Slot 4.05 102.9 1.48 37.6 2.66 67.6 1.23 .56 No
0810-0103 2.5Ah D 4.05 102.9 1.48 37.6 2.66 67.6 1.25 .57 Yes
0860-0102 4.5Ah DT Dbl. Slot 4.05 102.9 1.48 37.6 4.03 102.4 2.07 .94 No
0860-0103 4.5Ah DT 4.05 102.9 1.48 37.6 4.03 102.4 2.09 .95 Yes
0800-0102 5.0Ah X Dbl. Slot 5.25 133.4 1.87 47.5 3.12 79.2 2.48 1.13 No
0800-0103 5.0Ah X 5.25 133.4 1.87 47.5 3.12 79.2 2.52 1.14 Yes
0850-0102 8.0Ah E Dbl. Slot 5.25 133.4 1.87 47.5 4.19 106.4 3.49 1.58 No
0850-0103 8.0Ah E 5.25 133.4 1.87 47.5 4.19 106.4 3.53 1.60 Yes
0810-0011 2.5Ah D Dbl. Slot 4.23 107.4 1.55 39.4 2.75 69.9 1.33 .60 No
0810-0077 2.5Ah D Sing. Slot 4.23 107.4 1.55 39.4 2.75 69.9 1.37 .62 Yes
0800-0011 5.0Ah X Dbl. Slot 5.44 138.2 1.96 49.8 3.16 80.3 2.71 1.23 No
0800-0071 5.0Ah X Sing. Slot 5.44 138.2 1.96 49.8 3.16 80.3 2.74 1.24 Yes
0810-0008 2.5Ah D Dbl. Slot 4.23 107.4 2.88 73.2 2.72 69.1 2.68 1.22 No
0810-0067* 2.5Ah D (Styrene) 4.23 107.4 2.97 75.4 2.73 69.3 2.63 1.19 Yes
0800-0008 5.0Ah X Dbl. Slot 5.44 138.2 3.70 94.0 3.14 79.8 5.34 2.42 No
0800-0047* 5.0Ah X (Styrene) 5.44 138.2 3.70 94.0 3.19 81.0 5.22 2.37 Yes
0810-0114 2.5Ah D Dbl. Slot 4.05 102.9 2.82 71.6 2.67 67.8 2.48 1.13 No
0810-0115 2.5Ah D 4.05 102.9 2.82 71.6 2.67 67.8 2.50 1.14 Yes
0860-0114 4.5Ah DT Dbl. Slot 4.05 102.9 2.82 71.6 4.03 102.4 3.88 1.76 No
0860-0115 4.5Ah DT 4.05 102.9 2.82 71.6 4.03 102.4 3.91 1.77 Yes
0800-0114 5.0Ah X Dbl. Slot 5.25 133.4 3.68 93.5 3.13 79.5 4.93 2.24 No
0800-0115 5.0Ah X 5.25 133.4 3.68 93.5 3.13 79.5 4.97 2.26 Yes
0850-0114 8.0Ah E Dbl. Slot 5.25 133.4 3.68 93.5 4.19 106.4 6.73 3.05 No
0850-0115 8.0Ah E 5.25 133.4 3.68 93.5 4.19 106.4 6.77 3.07 Yes
0810-0016 2.5Ah D Dbl. Slot 8.25 209.6 1.55 39.4 2.74 69.6 2.74 1.24 No
0810-0075 2.5Ah D Sing. Slot 8.25 209.6 1.55 39.4 2.74 69.6 2.76 1.25 Yes
0800-0016 5.0Ah X Dbl. Slot 10.66 270.8 1.96 49.8 3.15 80.0 5.20 2.36 No
0800-0072 5.0Ah X Sing. Slot 10.66 270.8 1.96 49.8 3.15 80.0 5.24 2.38 Yes
0810-0108 2.5Ah D Dbl. Slot 8.08 205.2 1.48 37.6 2.66 67.6 2.49 1.13 No
0810-0109 2.5Ah D 8.08 205.2 1.48 37.6 2.66 67.6 2.52 1.14 Yes
0860-0108 4.5Ah DT Dbl. Slot 8.08 205.2 1.48 37.6 4.03 102.4 3.88 1.76 No
0860-0109 4.5Ah DT 8.08 205.2 1.48 37.6 4.03 102.4 3.91 1.77 Yes
0800-0108 5.0Ah X Dbl. Slot 10.48 266.2 1.87 47.5 3.12 79.2 4.99 2.27 No
0800-0109 5.0Ah X 10.48 266.2 1.87 47.5 3.12 79.2 5.03 2.28 Yes
0850-0108 8.0Ah E Dbl. Slot 10.48 266.2 1.87 47.5 4.19 106.4 6.73 3.05 No
0850-0109 8.0Ah E 10.48 266.2 1.87 47.5 4.19 106.4 6.77 3.07 Yes
CYCLON® Battery 12 Volt 1x6 Shrink Wrap
Product Length Width Height Weight Leads
Number Description in. mm in. mm in. mm lbs. kg
Product Length Width Height Weight Leads
Number Description in. mm in. mm in. mm lbs. kg
Product Length Width Height Weight Leads
Number Description in. mm in. mm in. mm lbs. kg
Product Length Width Height Weight Leads
Number Description in. mm in. mm in. mm lbs. kg
Product Length Width Height Weight Leads
Number Description in. mm in. mm in. mm lbs. kg
Product Length Width Height Weight Leads
Number Description in. mm in. mm in. mm lbs. kg
All dimensions, excluding weight, are maximum
*Due to special assembly, consult the EnerSys® Customer Service Department for availability.
12 Publication No: US-CYC-SG-003 - June 2008
www.enersys.com
Products 5 min 10 min 15 min 30 min 60 min 90 min 5 hr 8 hr 10 hr 20 hr
BC cell (2.5Ah) 118.3 72.8 54.3 32.2 19.3 14.0 4.85 3.14 2.55 1.33
DURATION
Constant current discharge/amps to 1.67Vpc @ 25°C
Products 5 min 10 min 15 min 30 min 60 min 90 min 5 hr 8 hr 10 hr 20 hr
BC cell (2.5Ah) 197.3 142.4 105.5 63.5 36.8 25.6 9.20 6.04 4.95 2.60
DURATION
Constant current discharge/watts per cell to 1.67Vpc @ 25°C
Products Cyclic Float Storage & Charge C/5 Cycle life Float life at
discharge 100% DOD 25°C (20°C)
BC cell (2.5Ah) CV 2.45-2.50 CV 2.27-2.35 -65°C to +80°C -40°C to -80°C 300 10 years
CC* CC* (15 years)
CHARGING PER CELL TEMPERATURE RANGE LIFE EXPECTANCY
Charging/Temperature/Life:
Maximum recommended storage time before recharge - 24 months @ 25°C or 2.0Vpc, whichever is earlier
Atmospheric pressure range - Vacuum to 8 atmospheres
Mounting - Terminal torque must not exceed 35 in-lbs. (3.95 Nm)
*Users planning to use CC should consult the EnerSys® Application Support Department
UL Recognized Component. Meets UL 1989
Caution: Batteries contain toxic materials (Pb and H2SO4) • Avoid short circuit • Do not charge in gas-tight container
Sealed-lead rechargeable battery must be recycled or disposed of properly. Contact EnerSys® Customer Service for details.
CYCLON® Battery 12 Volt 2x3 25.0Ah Case
0820-2018
BC Double Slot, 8.05 204.5 5.45 138.4 7.25 184.2 22.86 10.4 Yes
Copper Straps
0820-0020 BC Double Slot, 8.05 204.5 5.45 138.4 7.25 184.2 22.86 10.4 No
Copper Straps
Product Length Width Height Weight Leads
Number Description in. mm in. mm in. mm lbs. kg
All dimensions, excluding weight, are maximum
CYCLON® Battery BC Single Cell performance specifications
13
Publication No: US-CYC-SG-003 - June 2008
www.enersys.com
Products A B C D E F G H I J Weight
in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm lb. kg
D cell 0.27 6.9 0.51 13.0 0.187 4.75 22° 0.27 6.9 0.025 0.64 2.41 61.2 0.05 1.3 0.13 3.3 1.35 34.3 6.28 178.0
DT cell 0.27 6.9 0.51 13.0 0.187 4.75 22° 0.27 6.9 0.025 0.64 3.78 96.0 0.05 1.3 0.13 3.3 1.35 34.3 9.68 274.4
X cell 0.29 7.4 0.61 15.5 0.250 6.35 22° 0.34 8.6 0.025 0.64 2.87 72.9 0.06 1.5 0.14 3.6 1.75 44.5 12.77 362.0
E cell 0.29 7.4 0.61 15.5 0.250 6.35 22° 0.34 8.6 0.025 0.64 3.94 100.1 0.06 1.5 0.14 3.6 1.75 44.5 17.28 489.9
J cell 0.32 8.1 0.74 18.8 0.312 7.92 22° 0.49 12.4 0.032 0.81 4.85 123.2 0.05 1.3 0.15 3.8 2.04 51.8 29.60 839.2
DIMENSIONS
CYCLON® Battery Single Cell mechanical specifications (E, G, H & J - Maximum)
Products A B C D E F G H I Weight
in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm lb. kg
BC cell 0.65 16.5 1.30 33.0 22 0.57 14.5 0.22 5.6 6.25 158.8 0.06 1.5 0.13 3.3 2.57 65.3 3.68 1.67
DIMENSIONS
CYCLON® Battery BC Single Cell mechanical specifications (F, G & I - Maximum)
14 Publication No: US-CYC-SG-003 - June 2008
www.enersys.com
CYCLON® Battery Single Cell constant power (CP) discharge
CYCLON® Battery Single Cell constant current (CC) discharge
15
Publication No: US-CYC-SG-003 - June 2008
www.enersys.com
Products 5 min 10 min 15 min 30 min 60 min 90 min 5 hr 8 hr 10 hr 20 hr
D cell (2.5Ah) 14.3 8.1 5.9 3.4 1.9 1.4 .48 .32 .26 .13
X cell (5.0Ah) 28.9 18.1 13.5 7.1 4.0 2.8 1.0 .61 .52 .26
E cell (8.0Ah) 41.7 26.4 19.0 11.0 6.2 4.4 1.6 1.0 .81 .42
DURATION
4V & 6V Constant current discharge/amps to 1.67Vpc @ 25°C
Products 5 min 10 min 15 min 30 min 60 min 90 min 5 hr 8 hr 10 hr 20 hr
D cell (2.5Ah) 25.3 15.9 11.7 6.8 3.8 2.7 .93 .60 .49 .25
X cell (5.0Ah) 48.8 32.3 24.2 13.8 7.8 5.6 2.0 1.2 1.0 .52
E cell (8.0Ah) 77.8 51.0 35.5 21.1 12.4 8.9 3.1 2.0 1.7 .85
DURATION
4V & 6V Constant power discharge/watts per cell to 1.67Vpc @ 25°C
Products Cyclic Float Storage, discharge Safety C/5 Cycle life Float life at
& charge pressure 100% DOD 25°C (20°C)
relief valve
4V D, X, & E CV 4.90-5.00 CV 4.54-4.70 -40°C to +40°C 8 psi 300 Up to 8 yrs
Monobloc CC* CC* (Up to 8 yrs)
6V D, X, & E CV 7.35-7.50 CV 6.81-7.05 -40°C to +40°C 8 psi 300 Up to 8 yrs
Monobloc CC* CC* (Up to 8 yrs)
CHARGING PER CELL TEMPERATURE RANGE LIFE EXPECTANCY
Maximum recommended storage time before recharge - 24 months @ 25°C or 2.0Vpc, whichever is earlier
Atmospheric pressure range - Vacuum to 2 atmospheres
Mounting - Each Monobloc is equipped with mounting holes in the cover. The tightening torque for mounting the Monobloc is 25 in-lbs. When using 4 mounting bolts, small spacers
(washers) 1 to 3 mm thick should be placed between the battery and the mounting surface to prevent bowing or stressing the battery case.
*Users planning to use CC should consult the EnerSys® Application Support Department.
UL Recognized Component. Meets UL 1989
Caution: Batteries contain toxic materials (Pb and H2SO4) • Avoid short circuit • Do not charge in gas-tight container
Sealed-lead rechargeable battery must be recycled or disposed of properly. Contact EnerSys® Customer Service for details.
Charging/Temperature/Life
CYCLON® Battery 4V/6V Monobloc performance specifications
16 Publication No: US-CYC-SG-003 - June 2008
www.enersys.com
CYCLON® Battery 4V/6V Monobloc standard assemblies
CYCLON® Battery 4 Volt Monoblocs
0819-0010 4V, 2.5Ah Monobloc 3.13 79.5 1.81 46.0 2.75 69.9 .80 .36
0809-0010 4V, 5.0Ah Monobloc 3.80 96.5 2.12 53.8 3.02 76.7 1.62 .74
0859-0010 4V, 8.0Ah Monobloc 3.81 96.8 2.13 54.1 4.00 101.6 2.11 .96
Product Length Width Height Weight
Number Description in. mm in. mm in. mm lbs. kg
CYCLON® Battery 6 Volt Monoblocs
0819-0012 6V, 2.5Ah Monobloc 4.48 113.8 1.81 46.0 2.75 69.9 1.15 .52
0809-0012 6V, 5.0Ah Monobloc 5.48 139.2 2.12 53.8 3.02 76.7 2.16 .98
0859-0012 6V, 8.0Ah Monobloc 5.48 139.2 2.13 54.1 4.00 101.6 3.15 1.43
Product Length Width Height Weight
Number Description in. mm in. mm in. mm lbs. kg
CYCLON® Battery 12 Volt 2x3 Monoblocs
0819-0030 12V, 2.5Ah, 2x3 4.48 113.8 3.52 89.4 2.77 70.4 2.30 1.04
0809-0030 12V, 5.0Ah, 2x3 5.48 139.2 4.18 106.2 3.04 77.2 4.32 1.96
0859-0030 12V, 8.0Ah, 2x3 5.48 139.2 4.18 106.2 4.02 102.1 6.30 2.86
Product Length Width Height Weight
Number Description in. mm in. mm in. mm lbs. kg
CYCLON® Battery 12 Volt 1x6 Monoblocs
0819-0016 12V, 2.5Ah, 1x6 8.84 224.5 1.81 46.0 2.77 70.4 2.30 1.04
0809-0016 12V, 5.0Ah, 1x6 10.88 276.4 2.12 53.8 3.04 77.2 4.32 1.96
0859-0016 12V, 8.0Ah, 1x6 10.88 276.4 2.13 54.1 4.02 102.1 6.30 2.86
Product Length Width Height Weight
Number Description in. mm in. mm in. mm lbs. kg
All dimensions, excluding weight, are maximum
Resealable
Safety vent
Positive and
negative plates
Direct thru-the-wall
intercell connections
Highly retentive
separator
High integrity
terminal seal
One-piece
plastic case
One-piece
plastic cover
Lead grids
17
Publication No: US-CYC-SG-003 - June 2008
www.enersys.com
D Monobloc 2.75 69.9 3.13 79.5 1.81 46.0 .61 15.5 1.23 31.2 .80 .36 .187x.025 4.75x0.64
X Monobloc 3.02 76.7 3.80 96.5 2.12 53.8 .73 18.5 1.45 36.8 1.62 .74 .250x.025 6.35x0.64
E Monobloc 4.00 101.6 3.81 96.8 2.13 54.1 .73 18.5 1.45 36.8 2.11 .96 .250x.025 6.35x0.64
DIMENSIONS
CYCLON® Battery 4V Monobloc mechanical specifications (A, B & C - maximum)
Products A B C D E Weight Tabs
in. mm in. mm in. mm in. mm in. mm lb. kg in. mm
D Monobloc 2.75 69.9 4.48 113.8 1.81 46.0 .61 15.5 1.23 31.2 1.33 33.8 .67 17.0 1.15 .52 .187x.025 4.75x0.64
X Monobloc 3.02 76.7 5.48 139.2 2.12 53.8 .73 18.5 1.45 36.8 1.71 43.4 .86 21.8 2.12 .98 .250x.025 6.35x0.64
E Monobloc 4.00 101.6 5.48 139.2 2.13 54.1 .73 18.5 1.45 36.8 1.71 43.4 .86 21.8 3.15 1.43 .25x.025 6.35x0.64
DIMENSIONS
CYCLON® Battery 6V Monobloc mechanical specifications (A, B & C - maximum)
Products A B C D E F G Weight Tabs
in. mm in. mm in. mm in. mm in. mm lb. kg in. mm lb. kg in. mm
A
A
B
C
F
G
E
.216 DIA. TYP
(5.49)
E
D
D
B
C
D Monobloc
X & E Monobloc
18 Publication No: US-CYC-SG-003 - June 2008
www.enersys.com
4V/6V Monobloc constant current (CC) curves to 1.67Vpc
4V/6V Monobloc constant power (CP) curves to 1.67Vpc
19
Publication No: US-CYC-SG-003 - June 2008
www.enersys.com
ENERSYS® STANDARD PRODUCT LIST
SINGLE CELL (sc)
PART PERFORMANCE MECHANICAL
NUMBER DESCRIPTION VOLTAGE 10 Hr RATE SPECIFICATIONS SPECIFICATIONS
0810-0004 D Single Cell (Dsc) 2V 2.5Ah Page 10 Page 13
0860-0004 DT Single Cell (DTsc) 2V 4.5Ah Page 10 Page 13
0800-0004 X Single Cell (Xsc) 2V 5.0Ah Page 10 Page 13
0850-0004 E Single Cell (Esc) 2V 8.0Ah Page 10 Page 13
0840-0004 J Single Cell (Jsc) 2V 12.0Ah Page 10 Page 13
0820-0004 BC Single Cell (BCsc) 2V 25.0Ah Page 12 Page 13
SINGLE CELL STANDARD BATTERY DESIGNS
PART PERFORMANCE MECHANICAL
NUMBER DESCRIPTION VOLTAGE 10 Hr RATE SPECIFICATIONS SPECIFICATIONS
0810-0102 1x3 Dsc, double slot, shrink wrap 6V 2.5Ah Page 10 Page 11
0810-0103 1x3 Dsc, shrink wrap, leads 6V 2.5Ah Page 10 Page 11
0810-0011 1x3 Dsc, double slot, ABS case 6V 2.5Ah Page 10 Page 11
0810-0077 1x3 Dsc, single slot, ABS case, leads 6V 2.5Ah Page 10 Page 11
0860-0102 1x3 DTsc, double slot, shrink wrap 6V 4.5Ah Page 10 Page 11
0860-0103 1x3 DTsc, shrink wrap, leads 6V 4.5Ah Page 10 Page 11
0800-0102 1x3 Xsc, double slot, shrink wrap 6V 5.0Ah Page 10 Page 11
0800-0103 1x3 Xsc, shrink wrap, leads 6V 5.0Ah Page 10 Page 11
0800-0011 1x3 Xsc, double slot, ABS case 6V 5.0Ah Page 10 Page 11
0800-0071 1x3 Xsc, single slot, ABS case, leads 6V 5.0Ah Page 10 Page 11
0850-0102 1x3 Esc, double slot, shrink wrap 6V 8.0Ah Page 10 Page 11
0850-0103 1x3 Esc, shrink wrap, leads 6V 8.0Ah Page 10 Page 11
0810-0108 1x6 Dsc, double slot, shrink wrap 12V 2.5Ah Page 10 Page 11
0810-0109 1x6 Dsc, shrink wrap, leads 12V 2.5Ah Page 10 Page 11
0810-0016 1x6 Dsc, double slot, ABS case 12V 2.5Ah Page 10 Page 11
0810-0075 1x6 Dsc, single slot, ABS case, leads 12V 2.5Ah Page 10 Page 11
0810-0114 2x3 Dsc, double slot, shrink wrap 12V 2.5Ah Page 10 Page 11
0810-0115 2x3 Dsc, shrink wrap, leads 12V 2.5Ah Page 10 Page 11
0810-0008 2x3 Dsc, double slot, ABS case 12V 2.5Ah Page 10 Page 11
0810-0067* 2x3 Dsc, Styrene case, leads 12V 2.5Ah Page 10 Page 11
0860-0108 1x6 DTsc, double slot, shrink wrap 12V 4.5Ah Page 10 Page 11
0860-0109 1x6 DTsc, shrink wrap, leads 12V 4.5Ah Page 10 Page 11
0860-0114 2x3 DTsc, double slot, shrink wrap 12V 4.5Ah Page 10 Page 11
0860-0115 2x3 DTsc, shrink wrap, leads 12V 4.5Ah Page 10 Page 11
0800-0108 1x6 Xsc, double slot, shrink wrap 12V 5.0Ah Page 10 Page 11
0800-0109 1x6 Xsc, shrink wrap, leads 12V 5.0Ah Page 10 Page 11
0800-0016 1x6 Xsc, double slot, ABS case 12V 5.0Ah Page 10 Page 11
0800-0072 1x6 Xsc, single slot, ABS case, leads 12V 5.0Ah Page 10 Page 11
0800-0114 2x3 Xsc, double slot, shrink wrap 12V 5.0Ah Page 10 Page 11
0800-0115 2x3 Xsc, shrink wrap, leads 12V 5.0Ah Page 10 Page 11
www.enersys.com
EnerSys
P.O. Box 14145
Reading, PA 19612-4145
USA
Tel: +1-610-208-1991
+1-800-538-3627
Fax: +1-610-372-8613
EnerSys Europe
Zurich, Switzerland
Tel: +41 (0) 44 215 74 10
EnerSys Asia
Guangdong, China
Tel: +86-755-2689 3639
Distributed by:
© 2008 EnerSys. All rights reserved.
Trademarks and logos are the property of
EnerSys and its affiliates unless otherwise noted.
0800-0008 2x3 Xsc, double slot, ABS case 12V 5.0Ah Page 10 Page 11
0800-0047* 2x3 Xsc, Styrene case, leads 12V 5.0Ah Page 10 Page 11
0850-0108 1x6 Esc, double slot, shrink wrap 12V 8.0Ah Page 10 Page 11
0850-0109 1x6 Esc, shrink wrap, leads 12V 8.0Ah Page 10 Page 11
0850-0114 2x3 Esc, double slot, shrink wrap 12V 8.0Ah Page 10 Page 11
0850-0115 2x3 Esc, shrink wrap, leads 12V 8.0Ah Page 10 Page 11
0820-0030 2x3 BCsc, double slot, copper strap 12V 25.0Ah Page 12 Page 12
MONOBLOC (mb)
PART DESCRIPTION VOLTAGE 10 Hr RATE PERFORMANCE MECHANICAL
NUMBER SPECIFICATIONS SPECIFICATIONS
0819-0010 D Monobloc (Dmb) 4V 2.5Ah Page 15 Page 17
0809-0010 X Monobloc (Xmb) 4V 5.0Ah Page 15 Page 17
0859-0010 E Monobloc (Emb) 4V 8.0Ah Page 15 Page 17
0819-0012 D Monobloc (Dmb) 6V 2.5Ah Page 15 Page 17
0809-0012 X Monobloc (Xmb) 6V 5.0Ah Page 15 Page 17
0859-0012 E Monobloc (Emb) 6V 8.0Ah Page 15 Page 17
MONOBLOC STANDARD BATTERY DESIGNS
PART DESCRIPTION VOLTAGE 10 Hr RATE PERFORMANCE MECHANICAL
NUMBER SPECIFICATIONS SPECIFICATIONS
0819-0016 1x6 Dmb 12V 2.5Ah Page 15 Page 16
0819-0030 2x3 Dmb 12V 2.5Ah Page 15 Page 16
0809-0016 1x6 Xmb 12V 5.0Ah Page 15 Page 16
0809-0030 2x3 Xmb 12V 5.0Ah Page 15 Page 16
0859-0016 1x6 Emb 12V 8.0Ah Page 15 Page 16
0859-0030 2x3 Emb 12V 8.0Ah Page 15 Page 16
CAPACITY RATINGS BASED ON END OF DISCHARGE VOLTAGE OF 1.67 VOLTS/CELL AT 25°C
*Due to special assembly, consult the EnerSys® Customer Service Department for availability.
PART DESCRIPTION VOLTAGE 10 Hr RATE PERFORMANCE MECHANICAL
NUMBER SPECIFICATIONS SPECIFICATIONS
SINGLE CELL STANDARD BATTERY DESIGNS (continued)
Publication No. US-CYC-SG-003 June 2008 - Subject to revision without prior notice. E.&O.E.