04/04/2013 HPL-ED2012 V2.0 EN 1 / 4
Trip-Block�ZM-PKZ2
Part�no. ZM-10-PKZ2
Article�no. 040844
Delivery�programme
Product range Accessories: PKZ2 System - PRODUCT DISCONTINUATION IN 2012
Accessories Trip blocks
with overload release
Max. motor rating
AC-3
220 V
230 V
240 V
220 V 230 V P kW 2.2
380 V
400 V
415 V
380 V 400 V P kW 4
440 V P kW 4
500 V P kW 5.5
660 V
690 V
660 V 690 V P kW 7.5
Rated uninterrupted current IuA 10
Setting�range
Overload releases IrA 6 - 10
Short-circuit releases Irm A 80 - 140
Notes
Single‐phasing sensitivity to IEC/EN 60947‐4‐1
Suitable for the protection of EEx e motors
PTB Certificate No.: 3.53‐388.299
Extension to ATEX applied for
Overload releases, adjustable
Ir = 0.6 - 1.0 x Iu
Adjustable short‐circuit release
Irm = 8.5 - 14 x Iu
Factory set to 12 x Iu
NotesService factor (SF)
Set value Ir on the current scale, depending on the load factor
Calculate motor power in this range according to the rated operational current. Stated values to NEC Table 430 - 150.
Approved rating data
Devices for world markets IEC UL/CSA
Notes
When using the M‐…‐PKZ2 for short-circuit protection of motors with heavy-duty starting, the rated operating current e must be overdimensioned by the following factors in the
course of the project engineering:
CLASS Factor
5 1.0
10 1.0
15 1.22
20 1.41
25 1.58
30 1.73
35 1.89
40 2.0
Approvals
Product Standards UL 508; CSA-C22.2 No. 14; IEC60947-4-1; CE marking
UL File No. E36332