VAL-MS…DC-PV lightning
and surge arresters
Protect your photovoltaic system with
the new VAL-MS…DC-PV lightning and
surge arresters. The products are KEMA
approved and recognized as components
according to UL 1449.
Technical data
Designation
(with remote indication contact)
Order No.
VAL-MS-T1/T2
1000DC-PV/2+V-FM
2801161
VAL-MS-T1/T2
600DC-PV/2+V-FM
2801164
VAL-MS 1000DC-
PV/2+V-FM
2800627
VAL-MS 600DC-
PV/2+V-FM
2800641
Designation
(without remote indication contact)
Order No.
VAL-MS-T1/T2
1000DC-PV/2+V
2801160
VAL-MS-T1/T2
600DC-PV/2+V
2801163
VAL-MS 1000DC-
PV/2+V
2800628
VAL-MS 600DC-
PV/2+V
2800642
EN type according to prEN EN 50539-11 PV T1 / PV T2 PV T2
SPD failure behavior OCM OCM
Maximum continuous voltage UCPV 1050 V DC 720 V DC 1170 V DC 800 V DC
Immunity to short-circuiting ISCPV 300 A 300 A
Lightning test current Iimp (10/350)μs 5 kA –
Nominal discharge surge current In (8/20)μs 15 kA
Total discharge surge current ITotal (8/20)μs 40 kA
Protection level UP ≤ 3.5 kV ≤ 2.6 kV ≤ 3.7 kV ≤ 2.7 kV
Top Features
• Easy replacement, thanks to plug-in arresters
• Safe contacting through integrated rotating latch
• Optimum inverter protection,
thanks to low protection level
• Efficient replacement of defective plugs,
thanks to visual status indicator
• Optimized maintenance planning,
thanks to remote signaling
• Protection against incorrect connection
through keyed plugs and base elements
• Always the right arrester, thanks to
universal type1/type2 protective components
• KEMA approval, UL recognized components