Electronic High Performance Timing Relays
Product Data
(Catalog Number 700–FS)
The Bulletin 700–FS Electronic High Performance Timing Relays consist of
Multi–Function, Single Function and Special Function designs. These
products offer the customer optimum space utilization and maximum
functionality. In addition, the timing ranges are easily adjusted, and the LEDs
provide visual indication of the coil and timing status.
22.5mm (57/64 inch) Wide
Dual Voltage
24–48V DC
24–240V AC
DIN Rail Mounting
Finger Safe Terminals
Single Pull Double Throw (SPDT) Contact Configuration
Multi–Function/Multi–Range (On–Delay , Off–Delay , On–and–Off–Delay ,
One Shot, Fleeting Off–Delay, Flasher, On–Delay Pulse Generator, Pulse
Convertor, On–Function, Off–Function, with 10 Timing Ranges)
Single Function (On–Delay, Off– Delay, On–and–Of f–Delay, One Shot,
Fleeting Off–Delay, Flasher (Pulse), Flasher (Pause), On–Delay Pulse
Generator, On–Delay (Pulse Controlled), One Shot/Watch Dog, Pulse
Converter, with 12 Timing Ranges)
Special Function/Multi–Range (Flasher , True Off–Delay, Star–Delta, with
12 Timing Ranges)
Double Pull Double Throw (DPDT) Contact Configuration
Multi–Function/Multi–Range (On–Delay , Off–Delay , On–and–Off–Delay ,
One Shot, Fleeting Off–Delay, Flasher, On–Delay Pulse Generator, Pulse
Convertor, On–Function, Off–Function, with 10 Timing Ranges)
Single Function/Multi–Range (On–Delay, Off–Delay, with 10 Timing Ranges)
2700–FS Electronic High Performance Timing Relays
Catalog Number Explanation FS H U700 U233
First Position
Bulletin Number
Second Position
Type of Relay Third Position
Function
Sixth Position
Supply Voltages
Fifth Position
Time Ranges
Fourth Position
Assembly of Contacts
Multi–Function Timing Relays
700-FS M 3 U U23
Function Assembly of contacts Time ranges Supply voltages
MMulti-function timing
relays 8 Single-functions:
A, B, C, D, E, F, I, & L.
ON and OFF function
additional (for installation
and maintenance)
31 Change-
over contact 1 C/O
(SPDT)
42 Change-
over contacts 2 C/O
(DPDT)
U0.05 s...60 h Z12 12 VDC
U23 24...48 VDC
24...240 V 50/60 Hz
Single Function Timing Relays
700-FS A 3 A U23
Function Assembly of contacts Time ranges Supply voltages
AOn-delay
BOff-delay
COn- and off-delay
DOne shot
EFleeting off-delay
FFlasher (repeat cycle
starts w/pulse)
GFlasher (repeat cycle
starts w/pause)
IOn-delay pulse generator
JOn-delay (pulse
controlled)
KOne shot / watch dog
(pulse controlled)
LPulse converter
all functions:
31 Change-
over contact 1 C/O
(SPDT)
Functions A and B:
42 Change-
over contacts 2 C/O
(DPDT)
A0.05...1 s
B0.15...3 s
C0.5...10 s
D1.5...30 s
E0.05...1 min
F0.15...3 min
G0.5...10 min
H1.5...30 min
I0.05...1 h
J0.15...3 h
K0.5...10 h
L3.0...60 h
U0.05 s...60 h
Z12 12 VDC
U23 24...48 VDC
24...240 V 50/60 Hz
NOTE: Only the 700–FSA and
700–FSB are available with the “U”
multi–time setting ranges (0.05s to
60h).
Special Function Timing Relays
700-FS H 3 U U23
Function Assembly of contacts Time ranges Supply voltages
HFlasher (repeat cycle
starting with pulse or
pause)
31 Change-
over contact 1 C/O
(SPDT)
U0.05 s...60 h
V0.05 s ... 60 h
(2 ranges)
Z12 12 VDC
U23 24...48 VDC
24...240 V 50/60 Hz
700-FS Q 3 Q U18
Function Assembly of contacts Time ranges Supply voltages
QOff-delay without supply
voltages (true off–delay) 31 Change-over contact
1 C/O (SPDT)
42 Change-over contact
2 C/O (DPDT)
Q0.15 s ... 10 min U18 24...240 VDC
24...240 V 50/60 Hz
700-FS Y 2 C U23
Function Assembly of contacts Time ranges Supply voltages
YStar-delta timing relays 22 normally open
contacts 2 N.O. C0.5...10 s
D1.5...30 s
E0.05...1 min
F0.15...3 min
G0.5...10 min
U23 24...48 VDC
24...240 V 50/60 Hz
3
700FS Electronic High Performance Timing Relays
Technical Data
700FSM MultiFunction High Performance Timing Relays
Description SPDT DPDT
Multi-function timing relays 700-FSM3U includes 10 setting functions:
(A) - On-delay
(B) - Off-delay
(C) - On- and off-delay
(D) - One shot
(E) - Fleeting off-delay
(F) - Flasher (repeat cycle starts w/pulse)
(I) - On-delay pulse generator
(L) - Pulse converter
(On) - ON-Function *
(Off) - OFF-Function *
* (for installation and maintenance)
Up
Down
700–FSM4
0
0.2
0.4
0.6
0.8
1.0
A
Multi-time setting range 0.05 s...60 h
(1s) 0.05...1 s
(3s) 0.15...3 s
(10s) 0.5...10 s
(1mn) 0.05...1 min
(3mn) 0.15...3 min
(10mn) 0.5...10 min
(1h) 0.05...1 h
(3h) 0.15...3 h
(10h) 0.5...10 h
(60h) 3...60 h
10h
NOTE: Switch is on DPDT relays only. Supply voltages (A1/A2) Cat. No. Cat. No.
When switch is down, one contact is U23 24...48 VDC; 24...240 VAC, 50/60 Hz 700-FSM3UU23 700-FSM4UU23
instantaneous and one is timed. When
switch is up, both contacts are timed. Z12 12 VDC 700-FSM3UZ12 700-FSM4UZ12
700FS Single Function High Performance Timing Relays
Description SPDT DPDT
Supply voltages (A1/A2)
Z12 12 VDC
U23 24...48 VDC
24...240 VAC, 50/60 Hz
0
0.2
0.4
0.6
0.8
1.0
22.5 mm Timing
Relays available mono-time ranges
Complete the Cat. No. with the cor-
responding identification ĥfrom
the table on the next page.
NOTE: Only the 700FSA and
700–FSB are available with the “U”
multi–time setting ranges (0.05s to
60h).
Multi-time setting ranges
0.05 s...60 h
(1s) 0.05...1 s
(3s) 0.15...3 s
(10s) 0.5...10 s
(1mn) 0.05...1 min
(3mn) 0.15...3 min
(10mn) 0.5...10 min
(1h) 0.05...1 h
(3h) 0.15...3 h
(10h) 0.5...10 h
(60h) 3...60 h
10h
See 700FS Timing Charts Cat. No. Cat. No.
(A) On-delay 700–FSA3CU23
The output contact changes state after the time delay is completed. 700–FSA3FU23
700–FSA3UU23
ĥ
700-FSA4UU23
700-FSA4UZ12
700–FSA3ĥZ12
700–FSA3ĥU23 700-FSA4UZ12
(B) Off-delay 700-FSB3CU23
(B) Off-delay
Input power must be supplied to terminal (A1/A2) continuously. The output contact
changes state when switch “S” is closed. When switch “S” is opened, the time delay
700-FSB3FU23
700-FSB3UU23
ĥ
700-FSB4UU23
700-FSB4UZ12
changes state when switch “S” is closed. When switch “S” is opened, the time delay
begins. After the time delay is completed, the contact returns to shelf state. 700-FSB3ĥZ12
700-FSB3ĥU23 700-FSB4UZ12
(C) On- and off-delay
Input power must be supplied to terminal (A1/A2) continuously. The output contact 700-FSC3KU23
700-FSC3LU23
changes state when switch “S” is closed and the time delay complete. When switch
“S” is opened, the time delay begins again. After the time delay is completed, the
contact returns to shelf state.
700-FSC3LU23
700-FSC3ĥZ12
700-FSC3ĥU23
(D) One shot 700-FSD3KU23
700-FSD3LU23
The output contact changes state when the relay is energized. The output contact
returns to shelf state when the time delay is completed. 700-FSD3LU23
700-FSD3ĥZ12
700-FSD3ĥU23
(E) Fleeting off-delay (Min. Pulse AC 50ms DC 30ms)
Input power must be supplied to terminal (A1/A2) continuously. The output contact
changes state after closing and opening switch “S”. After the time delay is completed,
the contact returns to shelf state.
700-FSE3KU23
700-FSE3LU23
700-FSE3ĥZ12
700-FSE3ĥU23
(F) Flasher (Repeat Cycle Starting with Pulse)
The output contact changes state when power is applied. At the end of the time
delay, the output contact returns to shelf state. This cycle continues until the power is
removed.
700-FSF3KU23
700-FSF3LU23
700-FSF3ĥZ12
700-FSF3ĥU23
4700FS Electronic High Performance Timing Relays
Technical Data, Continued
See 700FS Tining Charts SPDT DPDT
See 700FS Tining Charts Cat. No. Cat. No.
(G) Flasher (Repeat Cycle Starting with Pause)
The output contact remains in the shelf state until the time delay is completed. When
the time delay is completed, the contact changes state. This cycle continues until the
power is removed.
700-FSG3KU23
700-FSG3LU23
700-FSG3ĥZ12
700-FSG3ĥU23
(I) On-delay pulse generator
The output contact changes state when the time delay is completed. After 0.5s the
contact opens.
700-FSI3KU23
700-FSI3LU23
700-FSI3ĥZ12
700-FSI3ĥU23
(J) On-delay (pulse controlled) (Min. Pulse AC 50ms DC 30ms)
Input power must be supplied to terminal (A1/A2) continuously. When switch “S is closed,
the time delay begins. The output contact changes state at the end of the time delay. The
output contact returns to shelf state when the power to (A1/A2) is removed.
700-FSJ3KU23
700-FSJ3LU23
700-FSJ3ĥZ12
700-FSJ3ĥU23
(K) One shot / watch dog (pulse controlled) (Min. Pulse AC 50ms DC 30ms)
Input power must be supplied to terminal (A1/A2) continuously. When switch “S” is
closed, the output contact changes state. The output contact will open when switch “S”
is open for longer than the time setting.
700-FSK3KU23
700-FSK3LU23
700-FSK3ĥZ12
700-FSK3ĥU23
(L) Pulse converter (Min. Pulse AC 50ms DC 30ms)
Input power must be supplied to terminal (A1/A2) continuously. When switch “S is closed,
the output contact changes state. When the time delay is completed, the output contact
returns to shelf state. The time “t is not influenced by the duration of the control pulse.
700-FSL3KU23
700-FSL3LU23
700-FSL3ĥZ12
700-FSL3ĥU23
ĥ Mono-Time Ranges
Complete the Cat. No. with mono-time range identification
Time ranges 0.05...1 s 0.15...3 s 0.5...10 s 1.5...30 s 0.05...1 min 0.15...3 min
ĥA B C D E F
Time ranges 0.5...10 min 1.5...30 min 0.05...1 h 0.15...3 h 0.5...10 h 3.0...60 h 0.05 s...60 h
ĥG H I J K L U
700FSH Special Function Flasher (repeat cycle starting with pulse or pause) Timing Relays
Description SPDT
Up
Down
Switch
FSH3U
t2 Setting
t1 Setting
Separate Range Settings
1 Range Setting
700–FSH3U 700–FSH3V
Supply voltages (A1/A2)
Z12 12 VDC
U23 24...48 VDC
24...240 VAC, 50/60 Hz
Multi-time setting ranges
U 0.05s...60 h (1 Range Setting)
V 0.05s...60 h (2 Range Settings)
(1s) 0.05...1 s
(3s) 0.15...3 s
(10s) 0.5...10 s
(1mn) 0.05...1 min
(3mn) 0.15...3 min
(10mn) 0.5...10 min
(1h) 0.05...1 h
(3h) 0.15...3 h
(10h) 0.5...10 h
(60h) 3...60 h
10h
See 700FS Timing Charts Cat. No.
(H) Flasher (repeat cycle starting with pulse or pause)
The repeat cycle timer permits different settings for on and off times.
The following operating modes are possible:
Oscillating mode; repeat cycle starts with voltage applied at A1 and B1, and continues to repeat until voltage is off.
One cycle mode; started by energizing B1 with voltage on A1 and A2.
Output starts with pulse or pause (switch Up or Down).
700FSH3U provides (1) range setting for t1 and t2.
700FSH3V provides (2) range settings for t1 and t2.
700-FSH3UU23
700-FSH3VU23
700-FSH3UZ12
Supply voltage controlled, Oscillating Mode starting with pause Switch is Up 700-FSH3VZ12
Supply voltage controlled, Oscillating Mode starting with pulse Switch is Down
Pulse controlled, output starts with pulse (Min. Pulse AC 50ms DC 30ms) Switch is Up
Pulse controlled, output starts with pulse (Min. Pulse AC 50ms DC 30ms) Switch is Down
NOTE:If B1 is pulsed, a one full time cycle consisting of t1 and t2 is completed.
5
700FS Electronic High Performance Timing Relays
Technical Data, Continued
700FSQ Special Function OffDelay without Supply Voltage Timing Relays
Description SPDT DPDT
Supply voltages (A1/A2)
U18 24...240 V AC 50/60 Hz
24...240 V DC
Multi–time setting range, Q 0.15 s...10 min
(2.5s) 0.15...2.5 s (10s) 0.5...10 s
(80s) 4...80 s (10mn) 0.5...10 min
See 700FS Timing Charts Cat. No. Cat. No.
(Q) Off-delay without supply voltage (true offdelay)
When the input power is turned on, the output contact changes state. When the power is
removed, the time delay begins. The output contact returns to shelf state at the end of the
time delay.
700–FSQ3QU18 700–FSQ4QU18
700FSY Special Function Star Delta Timing Relays
Description 2 NO
Supply voltages (A1/A2)
U23 24...48 VDC
24...240 VAC, 50/60 Hz
A vailable mono-time ranges
Complete the Cat. No. with the cor-
responding identification ĥfrom
the table below.
Cat. No.
(Y) Star-delta timing relay
When power is applied, the output contact 17/18(Y) changes state. After the time setting, the output contact 17/18(Y) returns
to shelf state. After the fixed time (50 to 60 ms), the output contact 17/28n changes state. Both output contacts return to shelf
state whenever the power is removed.
700-FSY2DU23
700-FSY2ĥU23
ĥ Mono-Time Ranges
Complete the Cat. No. with mono-time range identification. For 700FSY relays only.
Time ranges 0.5...10 s 1.5...30 s 0.05...1 min 0.15...3 min 0.5...10 min
ĥC D E F G
Specifications
Time characteristics (according to VDE 0435, Part 2021)
Setting accuracy $5% of full scale
Repeatability $0.2% of the setting values
Tolerance voltage: $0.001%/%DU
temperature: $0.025%/°C
Supply
Supply voltages 24...48 VDC and 24...240VAC, 50/60 Hz (dual voltage)
V oltage tolerance 20% to +20% (DC), 15% to +10% (AC)
Power consumption 0.5 W at 24 VDC, 5 VA at 240 VAC
Time energized 100%
Reset time 50 ms
V oltage isolation v20 ms without reset (supply voltage)
Cable length (supply voltage control) max. 250 m (800 ft)
Pulse control (B1)
Pulse duration w50 ms (AC), w30 ms (DC)
Input voltage Supply voltage range
Input current 1 mA
Cable length max. 250 m (800 ft) without parallel load between B1 and A2 max. 50 m (160 ft) with load (t3 kW) between B1 and A2
6700FS Electronic High Performance Timing Relays
Specifications, Continued
Outputs
Contact type Relay as changeover switch
Switching capacity Voltage: 440 VAC Current Ith: 8 A Power: 2000 VA
according to IEC 947-5-1:
3 A/440 VAC (inductive load, AC 14) 3 A/250 VAC (inductive load, AC 15)
1 A/24 VDC (inductive load, DC 13)
according to UL 508:
1.5 A/250 VAC (B300) 3 A/120 VAC (B300)
Short-circuit protection 10 A gL (Fast Blow Fuse)
Life mechanical: 30 Mil. of operations
electrical operations:
4 Mil. at 1 A/250 VAC, cos ö = 1 0.2 Mil. at 6 A/250 VAC, cos ö = 1
1.5 Mil. at 1 A/250 VAC, cos ö = 0.3 0.3 Mil. at 3 A/250 VAC, cos ö = 0.3
0.5 Mil. at 6 A/24 VDC, resistive 2 Mil. at 4 A/24 VDC, resistive
2 Mil. at 0.2 A/230 VDC, resistive 1 Mil. at 0.4 A/24 VDC, L/R = 20 ms
1 Mil. at 0.2 A/110 VDC, L/R = 20 ms 1 Mil. at 0.1 A/230 VDC, L/R = 20 ms
State indicator 1 LED, combination signal
Setting accuracy $5% of full scale
General Data
Insulation characteristics 2 kVAC/50 Hz test voltage according to VDE 0435
and 6 kV 1.2/50 ms surge voltage according to IEC 947-1 between all inputs and outputs
EMC/Interference immunity Performance of following requirements:
Surge capacity of the supply voltage according to IEC 1000-4-5: 4 kV 1.2/50 ms
Burst according to IEC 1000-4-4: 6 kV 6/50 ns
ESD discharge according to IEC 1000-4-2: Contact 8 kV, air 8 kV
Electromagnetical HF field according to IEC 801-3 and conducted electromagnetical HF signal according
to IEC 801-6: Level 3
EMC/Emission Electromagnetical fields according to EN 55 022: class B
Safe isolation according to VDE 106, part 101
Climatic withstand 56 Cycles (24 h) at 25...40°C and 95% rel. humidity according to IEC 68-2-30 and IEC 68-2-3
Vibration resistance 4 g in 3 axis at 10...500 Hz, test FC according to IEC 68-2-6
Shock resistance 50 g according to IEC 68-2-27
Protection class Enclosure: IP 40
IP 30 (Single-function)
Terminal: IP 20 according to IEC 947-1
Weight 100 g
Approval UL, C-UL, Germanischer Lloyd, CE Certified
Ambient temperature Open: –25°C ... +60°C
Enclosed: –25°C ... +45°C
Storage: –40°C ... +85°C
Terminals Screw terminal M3.5 for Posidrive Number.2, Philips and slotted screws Number.2. suitable for power screwdriver.
Rated tightening torque 8.8 LBIN 0.8 Nm (max. 1.2 Nm)
Dual-chamber system for terminal cross-sections of 1 x 0.5 mm2 ... 2 x 2.5 mm2 (solid) or stranded 2 x 2.5 mm2
(flexible with sleeve), AWG 20 to 14.
Finger protection according to VDE 0106
Mounting Front mounting; For snap-on mounting on DIN rail 35 mm or screw fixing by adapter and 2 screws M4
Disposal Synthetic material without dioxin according to EC/EFTA notification Number. 93/0141/D electrical contacts with
cadmium
7
700FS Electronic High Performance Timing Relays
Approximate Dimensions
(13/8)
(9/32)
(9/32)
(13/8)
(13/8)
(9/32)
700-FS (1 C/O)
700-FS (2 C/O)
700-FSH3V...
(33/32)
(57/64) (325/32)
(363/64)
(45/16)
(57/64) (325/32)
(33/32)
(363/64)
(45/16)
(33/32)
(57/64) (325/32)
(363/64)
(45/16)
Dimensions are shown in millimeters (inches).
Dimensions are not intended to be used for
manufacturing purposes.
199-FSA
For panel mounting, Use the 199–FSA Panel Mounting Adapter .
8700FS Electronic High Performance Timing Relays
Timing Charts, Single Function
(A) On-delay (B) Off-delay
(D) One shot
(F) Flasher (Repeat cycle starting with pulse)(E) Fleeting off–delay (Min. Pulse AC 50ms DC 30ms)
(L) Pulse converter
(C) On–and–Off-delay
(I) On-delay pulse generator(G) Flasher (Repeat cycle starting with pause)
(J) On-delay (pulse controlled) (Min. Pulse AC 50ms DC 30ms) (K) One shot/watch dog (pulse controlled)
(Min. Pulse AC 50ms DC 30ms)
Output
Output
1
Output
2
Output
2
Output
Output
1
Output
2
Output
2
Output
Output
Output
Output
Output Output
Output Output
Output
(Off) OFF-Function
(On) ON-Function Cleverly designed function display LED (Green)
Output in rest position, no timing
Output in rest position, time running
Output in operation position, no timing
Output in operation position, time running
A voltage other than the supply voltage can also be used at B1.
Output 2, selectable as instantaneous contact with sliding switch () on front panel (instantaneous when switch is down, timed when switch is up).
Bridge or potentiometer 10 kW, min. 0.25 W (low voltage) for external time setting. Set timer dial to 0.0.
Output
1
Output
2
Output
1
Output
2
9
700FS Electronic High Performance Timing Relays
Timing Charts, Special Function
(Y) Star–Delta
Wiring Connections
17 Common
18 Y
28 D
2 NO with Common
(H) Flasher repeat cycle timer Switch “X” is Up
Supply voltage connected to A1 and B1.
Oscillating Mode starting with pause.
(H) Flasher repeat cycle timer Switch “X” is Down
Supply voltage connected to A1 and B1.
Oscillating Mode starting with pulse.
(H) Flasher repeat cycle timer Switch “X” is Up
Pulse controlled, output starts with pause
(Min. Pulse AC 50ms DC 30ms)
One Cycle Mode
(H) Flasher repeat cycle timer Switch “X” is Down
Pulse controlled, output starts with pulse
(Min. Pulse AC 50ms DC 30ms)
One Cycle Mode
Output Output
Output Output
LED Operation Chart Green LED
Output at Shelf State, No Timing LED Off
Output at Shelf State, Time is Running LED Flashing
Output NO Contact is Closed, No Timing LED On
Output NO Contact is Closed, Time is Running LED Long Flashing
(Q) Offdelay without supply voltage
(T rue OffDelay)
Output
Output 1
Output 2
LED 25 28
26
15 18
16
A1/A2
Applications
Sequence Description Wiring Diagram
On–Delay (A)
Switch (X) Down,
(Contact 2124/22) is
Instantaneous
700–FSM DPDT Only
Delayed Motor Starting
Pushing the Start Button energizes A1.
After the time delay, Motor 1M will start Stop
TR
21 24
A1 A2
1815
Start
22
TR
TR O.L.
10 700FS Electronic High Performance Timing Relays
Applications, Continued
Sequence Description Wiring Diagram
Off–Delay (B)
Switch (X) Down,
(21–24/22) is
Instantaneous
700–FSM DPDT Only
Delayed Motor Stopping
A1 and A2 must be energized
continuously. Pushing the Start Button will
energize Motor 1M. Pushing the Stop
Button will deenergize B1 and Motor 1M
will be deenergized after the time delay
is completed.
L1 Stop
TR B1
A1 A2
1815
TR
Start L2
21 24
22
TR O.L.
On–and–Off Delay (C)
Motor Starting and
Stopping in a Sequence
Input Power must be applied to A1 and A2
continuously. Pushing the Start Button will
energize B1 to start the OnDelay, and
energize Motor 1M after the time delay is
complete. When B1 is deenergized by
pushing the Stop Button, the Off–Delay
will begin, and Motor 2M will turn off after
the time delay is completed.
Stop
B1
A1 A2
1815
Start
TR
TR
O.L.
O.L.
One Shot (D)
Motor On for a
Predetermined Time
Each time the Float Switch is closed,
Motor 1M will run for the predetermined
time that is set on the one shot timer. A1 A2
15 18
Float SW O.L.
Fleeting OffDelay (E)
Motor On for a
Predetermined Time
After a Stop
Pushing the Start Button and then the
Stop Button to energize and de–energize
Motor 1M, will cause Motor 2M to be
energized for a set time delay.
Stop Start
B1
TR
A1 A2
15 18
TR
1M
O.L.
O.L.
Flasher (Repeat Cycle
Starting with Pulse) (F) When Limit Switch (1LS) closes, the T imer
(TR) will close and open the contact,
causing the forward FM and Reverse RM
Motor Starters to go on and off.
1LS
TR
15
Flasher
A1
18
A2
TR
FM
RM
O.L.
11
700FS Electronic High Performance Timing Relays
Applications, Continued
Sequence Description Wiring Diagram
Flasher (Repeat Cycle
Starting with Pause) (G)
Turning On an Alarm
Horn After a Time Delay
When Limit Switch (1LS) closes, the Timer
TR will be energized. The Horn will not
sound until the time setting is completed.
15 18
1LS
TR
TR
A1 A2
Horn
Flasher
OnDelay Pulse
Gene rat or (I)
Turning On or Off a
Latching Contactor for
Lighting
The Selector Switch will energize the
daylight sensor. The Contact (1DL) closes
due to darkness and the Timer (1TR) will
time out, and then close contact 1TR to
send a pulse (0.5s) to the Latching
Contactor to turn on the lights. When
daylight comes, the switch 1DL will switch
back and energize 2TR after a time delay.
The 2TR contact will pulse closed (0.5s)
to reset the lighting contactor. If the
signals to 1DL are short, the 1TR and 2TR
contacts will not pulse.
On Off
1DL
1TR
2TR
TR1
Daylight
Sensor
1DL
2TR
1CLatch
Reset
A1 A2
A1 A2
1C
15 18
15 18
Timers 1TR and 2TR are set to eliminate short sensor signals.
OnDelay (Pulse
Controlled) (J)
Pulse Starts The
On–Delay that Turns
On a Motor
A1 and A2 must be energized
continuously. A pulse or input from the
“ON” Pressure Switch starts the
On–Delay. After the delay is complete, the
Motor 1M will start. A signal from the
“Reset” Pressure Switch turns the Motor
1M off. The delay prevents short off times.
On SW
Reset SW
Low Pressure
Hi Pressure
1TR
15
B1
A1 A2
18
1TR
O.L.
One Shot/Watch Dog
(Pulse Controlled) (K)
Conveyor Keeps
Running Only As Long
As a Package is
Sensed Every Time
Setting (5 Min)
A1 and A2 must be energized
continuously. A pulse must be received
every time setting (or sooner) to maintain
the Motor 1M running. This could be an
energy saver, because the Motor 1M will
turn off if the Photo SW is open for a
period of time.
1TR
15 18
B1
A1 A2
1TR
Photo SW
O.L.
12 700–FS Electronic High Performance Timing Relays
Publication 700–2.17 April 1998 Copyright 1998 Rockwell International Corporation Printed in USA
Applications, Continued
Sequence Description Wiring Diagram
Pulse Converter (L)
Pulses Are Turned Into a
Set or Predetermined
Output
When the Photo Switch closes the first
time, the contact TR closes to energize
Motor 1M for the predetermined time
setting. The timer will not be reset by the
opening or pulsing of the Photo SW until
the time delay is completed.
Time setting is 0.05s to 10h.
15 18
Photo SW B1
A1 A2
1TR
1TR O.L.
Off–Delay Without
Supply Voltage (Q)
(T rue Off–Delay)
A1 and A2 do not require continuous
power for the off–delay time setting to be
completed. T urning the switch to On will
energize Motor 1M. When the switch is
turned to Off, or the power is removed,
Motor 1M will remain on for the time delay
setting A1 A2
ON OFF TR
TR O.L.
Star–Delta (Y)
Starting a Star–Delta
Motor
Pushing the Start Button energizes the
relay CR and the timer TR. Both will hold
in through CR. Contact 17–18 will close
energizing the Star Contact (Y), and
starting the motor for the predetermined
time. Then contact 17–18 will open and
50ms to 65ms later contact 17–28 will
close to energize the Delta Contact (n).
Stop Start
L1
CR
A1
17
L2
A2
18
28
TR