DC Square-body Fuses
Sizes 300 - 302 - 2x302
gR Brackets size 302 - 2000V DC
SCDC49
Protistor DC fuses
Protistor DC fuses
gRC-gRE from 100 to 280 A
DC applications data
Time vs. current characteristics
Electrical characteristics Peak arc voltage
vs. working voltage
t (s) t (s)
I (A)
I (A)
10210 3 10 410 5
10 4
10 3
10 2
10
1
10 -1
10 -2
10 -3
10 -4
10 4
10 3
10 2
10
1
10 -1
10 -2
10 -3
10 -4
100
125
160
10 210 3 10 410 5
Above, left and right: Curves indicate, for each rated current,
pre-arcing time vs. R.M.S. pre-arcing current
a= 130
A2=0.6
B1= 1.25
B2= 0.6
Cf3= 0.8
a= 130
A2=0.6
B1= 1.25
B2= 0.6
Cf3= 0.8
±10% tolerance for mean pre-arcing current
160
200
250
280
gRC gRE
U (V)
100
90
80
70
60
50
40
30
20
10
0
Above: Curves indicate maximum permissible value of
time constant L/R as a function of DC working voltage 1 Curve gRC : L/R = 30 ms
2 Curve gRE : L/R = 15 ms
Max. AC voltage (50/60 Hz):
1700 V with breaking capacity of 80 kA
Um(V)
U (V)
0
1000
2000
4000
2000
0
1
3
42
Above: Curves indicate for various time constants
L/R the peak arc voltage which may appear across
the fuse terminals, vs. DC working voltage
3 Curve gRC 2000 V
4 Curve gRE 2000 V
L/R (ms)
12/04
1200
1600
2000
2200