Specifications, model OSBFAC Sensor Head
The Bi-Modal™ output of OMNI-
BEAM dc power blocks is wired
for current sinking (NPN) opera-
tion (100mA max.) by connecting
the BROWN supply wire to +V dc,
and the BLUE wire to dc common.
The Bi-Modal™ output of OMNI-
BEAM dc power blocks is wired for
current sourcing (PNP) operation
(100mA, max.) by connecting the
BLUE supply wire to +V dc, and the
BROWN wire to dc common.
OSBFAC dc hookup (power blocks OPBT2 & OPBT2QD)* OSBFAC ac hookup (power blocks OPBA2, OPBA2QD,
OPBB2, and OPBB2QD)*
*Note that when standard OMNI-BEAM power blocks are used with the
OSBFAC, the power block ALARM output functions as a second output
that exactly follows the action of the main output. The capacity of this
second output is 100mA max. (for dc-powered power blocks) and 200mA
max. (for ac-powered power blocks). Also note that, when dc-powered
power blocks (OPBT2 and OPBT2QD) are used with the OSBFAC, they are
not short-circuit protected.
OMNI-BEAM ac power block
models OPBA2 and OPBA2QD are
for 105-130V ac power. Models
OPBB2 and OPBB2QD are for
210-250V ac power. The hookup
diagram (right) is the same for all
four models.
The LOAD output (500mA, maxi-
mum) is isolated. The ALARM
output is internally connected to ac
"hot", and exactly follows the ac-
tion of the LOAD output. The
ALARM output is capable of
switching up to 200mA, maximum.
Sensing Beam: infrared, 880nm
Sensing Range: see "box" on page 1
Response Time: 1 millisecond
Adjustments: GAIN control (15-turn clutched potentiometer) ad-
justs the sensitivity of the ac-coupled amplifier. Located on top of the
sensor beneath a transparent LEXAN® window.
Indicators: LOCK LED lights whenever the AGC system has
locked onto a signal. LOAD LED lights whenever the sensor's output
circuit is energized. Both indicators located on top of the sensor
beneath a transparent LEXAN® window.
Operating Temperature Range: -40 to +70°C (-40 to +158°F)
Construction: housing is molded from rugged VALOX® thermo-
plastic polyester for outstanding electrical and mechanical perfor-
mance in demanding applications. The top window is of transparent
LEXAN® polycarbonate. Hardware is stainless steel. When as-
sembled to a compatible power block module, all parts are fully
gasketed.
Dimensions, OSBFAC Sensor Head Module
with standard dc Power Block Module Attached*
Banner Engineering Corp. 9714 10th Ave. No., Minneapolis, MN 55441 Telephone 612/544-3164 FAX (applications) 612/544-3573
Installation and adjustment
OLM8
logic module (slide in)
Light/Dark
Operate
slide switch:
DO
(slide left);
LO
(slide right)
*Standard ac power block is .88" taller in height; overall height
of OSBFAC sensor head with an ac power block attached is 3.88".
1) The OSBFAC requires the use of an OLM8 Series slide-in logic
module. Refer to the data sheet packed with the logic module. Program
the OLM8's DIP switches for the required pulse type and duration range,
then slide the OLM8 into the slot in the sensor head. Set the OSBFAC
sensor head for either light- or dark-operate, using the slide switch on
the underside of the sensor head (see bottom photo, right).
2) Detach the clear LEXAN® top window from the OSBFAC by removing the single hold-down screw.
Assemble the OSBFAC head to the power block module using the four captive screws at the corners of the
module. Mount the sensor assembly at a convenient location (Banner mounting bracket model SMB30MM
is ideal for use with OMNI-BEAM sensors). Attach two individual glass fiber optic assemblies or one
bifurcated glass fiber optic assembly to the OSBFAC, following the instructions packed with the fibers.
Mount and align the sensing end(s) of the fiber(s), at the sensing location, in a position that will optimize
the differential between the "light" and "dark" conditions. Refer to the data sheet packed with the power
block in use. Connection of the load at this time is optional: the LOAD LED, shown in the photo (right),
will simulate the action of the load. Connect the power block to a compatible power source and apply power.
3) Present the "light" condition to the sensor*. Check to assure that the LOCK LED is "on". If necessary,
adjust the position of the fiber sensing tips so that the LOCK indicator reliably stays "on". While observing
the LOAD LED (and remembering the programmed pulse time, step #1), simulate the sensing situation by
presenting the sensing event to the sensor. If necessary, adjust the GAIN control (clockwise = increase;
counterclockwise = decrease) so that the LOAD LED changes state positively and reliably in response to
all desired variations of the sensing event. Note: Too much gain may result in response to unwanted
conditions (i.e. movement of fiber sensing ends due to vibration, etc.). While observing the LOAD
indicator, adjust the OLM8 timing exactly as desired. Connect the load to the sensor, and test the system.
*Note: If the "light" condition is a quick transition that cannot be simulated as a static condition, present
the "dark" condition in lieu of the "light" condition.