A5E38072451, 05.2016 1
SITOP modular
6EP1336-3BA00 (24 V/20 A)
6EP1337-3BA00 (24 V/40 A)
Betriebsanleitung (kompakt)
Operating Instructions (compact)
Instrucciones de servicio (resumidas)
操作说明 (精简版)
Notice de service (compacte)
Istruzioni operative (descrizione sintetica)
Руководство по эксплуатации (компактное)
https://support.industry.siemens.com
1: Ansicht Geräte
1: View of the devices
1: Vista de aparatos
1: 设备外观
1: Vue des appareils
1: Vista degli apparecchi
. 1: Внешний вид устройств
Die SITOP modular 1-2 ph 20 A/40 A sind Einbaugerä-
te, Schutzart IP20, Schutzklasse I.
Primär getaktete Stromversorgung zum Anschluss an
1-phasiges Wechselstromnetz oder an 2 Außenleitern
von Drehstromnetzen (TN-, TT- oder IT-Netz nach
VDE 0100 T 300 / IEC 364-3) mit Nennspannungen
120/230 V, 50 - 60 Hz; Ausgangsspannung +24 V DC,
potenzialfrei, kurzschluss- und leerlauffest.
Bild 1 Ansicht Geräte (Seite 1)
Der einwandfreie und sichere Betrieb dieses
Gerätes/Systems setzt sachgemäßen Transport,
sachgemäße Lagerung, Aufstellung und Montage
sowie sorgfältige Bedienung und Instandhaltung
voraus.
Dieses Gerät/System darf nur unter Beachtung der
Instruktionen und Warnhinweise der zugehörigen
technischen Dokumentation eingerichtet und betrieben
werden.
Nur qualifiziertes Personal darf das Gerät/System
installieren und in Betrieb setzen.
Das Gerät erfüllt die ATEX Richtlinie 2014/34/EU;
SPANNUNGSEINSTELLUNG ODER
SCHALTERBETÄTIGUNG NUR IN NICHT-
EXPLOSIVER UMGEBUNG DURCHFÜHREN!
Montage auf Normprofilschiene TH35-7,5/15 (20 A)
bzw. TH35-15 (40 A) (EN 60715).
Das Gerät ist so zu montieren, dass die Klemmen
unten sind.
Unterhalb und oberhalb des Gerätes muss mindestens
ein Freiraum von je 50 mm eingehalten werden.
Bei Installation des Gerätes in explosionsgefährdeter
Umgebung (II 3G Ex nA nC IIC T3 Gc (20 A) / II 3G Ex
nA IIC T3 Gc (40 A)) ist dieses in einen Verteilerkasten
mit Schutzart IP54 oder höher einzubauen.
Bild 2 Montage/Demontage (Seite 2)
Vor Beginn der Installations- oder Instandhaltungs-
arbeiten ist der Hauptschalter der Anlage auszuschalten
und gegen Wiedereinschalten zu sichern. Bei Nichtbe-
achtung kann das Berühren spannungsführender Teile
Tod oder schwere Körperverletzung zur Folge haben.
Die Betätigung des Potenziometers ist nur mittels
isoliertem Schraubendreher zulässig.
The SITOP modular 1-2 ph 20 A/40 A are built-in units,
degree of protection IP20, protection class I.
Primary switched-mode power supplies for connection
to 1-phase AC system or to 2 line conductors of three-
phase line supplies (TN, TT or IT line system in ac-
cordance with VDE 0100 T 300 / IEC 364-3) with rated
voltages of 120/230 V, 50 - 60 Hz; +24 V DC output
voltage, isolated, short-circuit-proof and idling-proof.
Figure 1 View of the devices (Page 1)
Appropriate transport, proper storage, mounting, and
installation, as well as careful operation and service,
are essential for the error-free, safe and reliable
operation of the device/system.
Setup and operation of this device/system are
permitted only if the instructions and warnings of the
corresponding documentation are observed.
Only qualified personnel are allowed to install the
device/system and set it into operation.
The device complies with ATEX directive 2014/34/EU;
OPERATE VOLTAGE ADJUSTMENT OR SWITCHES
IN NON-HAZARDOUS AREAS ONLY!
Mounted on a standard mounting rail TH35-7,5/15
(20 A) or TH35-15 (40 A) (EN 60715).
The device should be mounted so that the terminals are
at the bottom.
A clearance of at least 50 mm must be maintained
above and below the device.
When installing the unit in a hazardous zone (II 3G Ex
nA nC IIC T3 Gc (20 A) / II 3G Ex nA IIC T3 Gc (40 A)),
then it must be accommodated in a distribution box with
a degree of protection IP54 or higher.
Figure 2 Mounting / removal (Page 2)
Before installation or maintenance work can begin, the
main system switch must be opened and measures
taken to prevent it from being reclosed. If this
instruction is not observed, touching live parts can
result in death or serious injury.
It is only permissible to use an insulated screwdriver
when actuating the potentiometer.
Los SITOP modular 1-2 ph 20 A/40 A son aparatos
empo-trables con grado de protección IP20 y clase de
protección I.
Fuente de alimentación conmutada en primario para la
conexión a la red alterna monofásica o a 2 conductores
de fase de redes trifásicas (redes TN, TT o IT según
VDE 0100 T 300 / IEC 364-3) con tensiones nominales
de 120/230 V, 50-60 Hz; tensión de salida +24 V DC,
aislamiento galvánico, resistente a cortocircuito y a
Figura 1 Vista de aparatos (Página 1)
El funcionamiento correcto y seguro de este
aparato/sistema presupone un transporte, un
almacenamiento, una instalación y un montaje
conformes a las prácticas de la buena ingeniería, así
como un manejo y un mantenimiento rigurosos.
Este aparato/sistema debe ajustarse y utilizarse úni-
camente teniendo en cuenta las instrucciones y adver-
tencias de la documentación técnica correspondiente.
La instalación y puesta en marcha del aparato/sistema
debe encomendarse exclusivamente a personal
cualificado.
El aparato cumple la directiva ATEX 2014/34/UE;
¡AJUSTAR LA TENSIÓN O ACCIONAR
INTERRUPTORES SÓLO EN ENTORNOS NO
EXPLOSIVOS!
Montaje en perfil normalizado TH35-7,5/15 (20 A) o
TH35-15 (40 A) (EN 60715).
El aparato debe montarse con los bornes en la parte
inferior.
Por encima y por debajo del aparato debe dejarse un
espacio libre de al menos 50 mm.
Si se va a instalar el aparato en una atmósfera potencial-
mente explosiva (II 3G Ex nA nC IIC T3 Gc (20 A) / II 3G
Ex nA IIC T3 Gc(40 A)), deberá montarse en una caja de
distribución con grado de protección IP54 o superior.
Figura 2 Montaje/desmontaje (Página 2)
Antes de comenzar los trabajos de instalación o
mantenimiento, se deberá abrir el interruptor principal
del cuadro/tablero y protegerlo para evitar su cierre. Si
no se observa esta medida, el contacto con piezas bajo
tensión puede provocar la muerte o lesiones graves.
El potenciómetro solo deberá girarse usando un
destornillador aislado.
SITOP modular 1-2 ph 20 A/40 A 为内装式设备,防护
方式为 IP20,防护等级 I。
本设备为主时钟电源,用于连接在一相交流供电系统或
三相电源的 2 根线路导线上(符合VDE 0100 T 300 /
IEC 364-3标准的 TN、TT 或 IT 电网);额定电压为
120/230 V,50 - 60 Hz;输出电压 +24 V DC,电位隔
离,具有短路保护和空载保护功能。
参见图 1 设备外观 (页 1)
本设备/系统的安全正常运行依赖于正确规范的运输、存
放、装配、安装作业以及仔细谨慎的操作和维护。
请务必阅读并遵守本设备/系统技术文档中包含的规定和
警示,否则禁止安装和运行本设备。
本设备/系统仅允许由专业技术人员安装和调试。
本设备符合 ATEX 指令 2014/34/EU、EN 60079-0、
TH35-7,5/15 (20 A)或(TH35-15 (40 A) (EN 60715)) 的
凹顶导轨安装
安装设备时应使端子位于下方。
设备的上方和下方必须至少保留 50 mm 的通风空间。
在爆炸危险环境(II 3G Ex nA nC IIC T3 Gc(20
Ex nA IIC T3 Gc (40 A))下安装设备时 ,必须将设备安
装在防护方式 IP54 或防护等级更高的配电箱内。
参见图 2 安装/拆卸 (页 2)
备再次被接通。违反该规定可能会导致作业人员接触到
带电零部件,从而导致严重的人身伤害甚至死亡。
电位计只允许使用绝缘螺丝刀进行操作。