Type: PKZM01−2,5
Article No.: 278481
Ordering information
Motor rating AC−3 220 V 230 V 240 V PkW 0.37
Motor rating AC−3 380 V 400 V 415 V PkW 0.75
Motor rating AC−3 440 V PkW 1.1
Motor rating AC−3 500 V PkW 1.1
Motor rating AC−3 690 V PkW 1.5
Rated uninterrupted current IuA 2.5
Overload release, min. – Overload release, max. IrA 1,6 – 2,5
max. Irm A 35
Notes concerning the product group
Accessories Page
3 Standard auxiliary contact 072896
5 Trip−indicating auxiliary contact 072898
1
6 Shunt release, undervoltage release 073187
Single−phasing sensitivity to IEC/EN 60947−4−1
Can be snap−fitted to IEC/EN 60715 top−hat rail with
7.5 or 15 mm height.
General
Standards IEC/EN 60947, VDE 0660, UL 508, CSA C
22.2 No. 14
Climatic proofing Damp heat, constant, to IEC 60068−2−78
Damp heat, cyclic, to IEC 60068−2−30
Ambient temperature
Storage °C −25/80
Open °C −25/55
Enclosed °C −25/40
Direction of incoming supply As required
Degree of protection
Device IP20
Terminations IP00
Protection against direct contact Finger− and back−of−hand proof
Mechanical shock resistance half−sinusoidal shock 10
ms to IEC 60068−2−27 g 25
Altitude m 2000
Terminal capacities
Solid mm21 × (1 – 6)
2 × (1 – 6)
Flexible with ferrule to DIN 46228 mm21 × (1 – 6)
2 × (1 – 6)
Solid or stranded AWG 18 – 10
Specified tightening torque for terminal screws
Main cable Nm 1,7
Control circuit cables Nm 1
Main conducting paths
Rated impulse withstand voltage Uimp V AC 6000
Overvoltage category/pollution degree III/3
Rated operational voltage UeV AC 690
Rated uninterrupted current = rated operational current Iu = IeA16 or current setting of the overcurrent
release
Rated frequency Hz 40 – 60
Current heat loss (3−pole at operating temperature) W 6
Lifespan, mechanical Operations × 106> 0,05
Lifespan, electrical (AC−3 at 400 V) Operations × 1060,05
Maximum operating frequency
Max. operating frequency Ops/h 25
Short−circuit rating
DC
Short−circuit rating kA 60
Short−circuit rating 60
Motor switching capacity
2
AC−3 up to 690 V A 16
DC−5 (up to 250 V) A 16 (3 contacts in series)
Trip blocks
Temperature compensation
to IEC/EN 60 947, VDE 0660 °C −5 – 40
Operating range °C −25 – 55
Temperature compensation residual error for T > 20
°C %/K f 0.25
Setting range of overload releases × Iu0,6 – 1
Short−circuit release fixed × Iu14
Short−circuit release tolerance % 20
Phase−failure sensitivity IEC/EN 60947−4−1, VDE 0660 Part 102
Dimensions
Mounting position
Mounting position
Dimensions
3
Moeller GmbH, Hein−Moeller−Str. 7−11, D−53115 Bonn
E−Mail: catalog@moeller.net, Internet: www.moeller.net, http://catalog.moeller.net
Copyright 2005 by Moeller GmbH. Subject to modifications. HPL−C2005GB−INT V3.0
4