T5HO PSN
62
Lamp / Ballast Guide
Key System Features
System Information
Universal voltage (120-277V)
Low-profile (0.86" High)
100% Ballast factor
QUICKSENSE®ballast technology
(end-of-lamp-life sensing)
PROStart programmed rapid start
UL type CC rated
Min. Starting Temp:
• 0°F/-18°C
• -20°F/-29°C for QTP 2x54T5HO
Models
Operates at >40 Khz to reduce
potential interference with infrared
control systems
High power factor
Low harmonic distortion
Lightweight
UL, CSA, FCC
SYLVANIA QUICKTRONIC PHO
is ideally suited for:
Commercial & retail
Hospitality & institutional
New construction
Direct lighting
Indirect lighting
Surface mount
Cove lighting
Application Information
54W T5 - PENTRON®HO
1-lamp QTP1x54T5HO/UNV
2-lamp QTP2x54T5HO/UNV
Also operates:
FT55DL, FT50DL, FPC55, L58T8
39W T5 - PENTRON HO
1-lamp QTP1x39-24T5HO/UNV
2-lamp QTP2x39-24T5HO/UNV
24W T5 - PENTRON HO
1-lamp QTP1x39-24T5HO/UNV
2-lamp QTP2x39-24T5HO/UNV
Also operates:
FT36DL, FT24DL, CF24DF, CF36DF,
FPC40, FPC22
80W T5 - PENTRON HO
1-lamp QTP1x80T5HO/UNV
Also operates:
FT80DL
Two lamp models can be wired for one
lamp operation.
System PHO operates from 120V through
277V, 50 or 60Hz, eliminating “wrong
voltage” wiring errors and reducing the
number of models in inventory by half.
PROStart ballasts provide optimum starting
conditions to provide up to 100,000
switching cycles for use on occupancy
sensors and building control systems.
QUICKSENSE ballast technology helps to
protect against overheated bases and
sockets, as well as cracking of the glass
wall, and uses dynamic end-of-lamp-life
sensing to avoid false shutdowns caused
by some static sensing methods. QUICK-
SENSE ballast technology will auto reset
when the end-of-life lamps are replaced
with new ones.
The two lamp unit can be wired for one
lamp operation, allowing for an additional
50% reduction in inventory model numbers.
Input Initial System
System Type Power System Efficacy
(W) Lumens LPW
F40T12 - E.S. Magnetic Ballast (4-lamp) 172 11590 67
F34T12 - E.S. Magnetic Ballast (4-lamp) 144 9500 66
FO32T8/XP - QT4x32IS (4-lamp) 114 10800 95
FP54T5HO - QTP2x54T5HO/UNV PSN (2-lamp) 121 10000 83
FO32T8/XP - QT2x32IS (2-lamp) 59 5400 92
FP54T5HO - QTP1x54T5HO/UNV PSN (1-lamp) 62 5000 81
QUICKTRONIC®PROStart®T5HO
Universal Voltage
www.sylvania.com
<10% THD Electronic T5HO Fluorescent
Programmed Rapid Start Systems
Normal Ballast Factor
Professional Series
SYSTEM PHO comes in a 22H x 30W mm
profile, and PENTRON lamps are designed
to provide peak performance at 35°C
fixture ambient, allowing for smaller and
more innovative fixtures.
A complete OSRAM SYLVANIA System
Performance Guide showing performance
characteristics of lamps and ballasts is
available upon request.
SYLVANIA QUICKTRONIC PHO operates
PENTRON HO, PENTRON HO Circline, and
DULUX®L T5 lamps with full lumen output
and optimal system performance.
SYSTEM PHO provides nearly twice the
light output (188%) of T8 systems, with
the same number of lamps, allowing
many new design options. One lamp
fixtures can now be used in place of two
lamp models.
SYSTEM PHO ballasts contain QUICK-
SENSE ballast technology, a patented
circuitry designed to shut down the
system reliably and safely when lamps
reach end-of-life.
Setting the standard for quality, SYSTEM
PHO is also covered by our QUICK 60+®
warranty, the first and most compre-
hensive system warranty in the industry.
SYSTEM PHO is available in one and two
lamp models to cover a wide range of
applications.
63
Catalog # Date Type
Project Prepared by
Comments
SPECIFICATION DATA
T5HO PSN
Starting Method: Programmed
Rapid Start
Ballast Factor: 1.00
Circuit Type: Series
Lamp Frequency: >40 kHz
Lamp CCF: Less than 1.6
Starting Temp: 0°F (-18°C) minimum4
-20°F (-29°C) Starting for
QTP2x54T5HO Models
Input Frequency: 50/60 Hz
Low THD: <10%
Power Factor: >98%
Voltage Range: ±10% of 120-277V
rated line (108-305V)
UL Listed Class P, Type 1, Outdoor,
Type CC
CSA Certified
70°C Max Case Temperature
FCC 47CFR Part 18 Non-Consumer
Class A Sound Rating
ANSI C62.41 Cat. A Transient Protection
Dynamic End-of-Lamp-Life Sensing
Remote Mounting (Max. wire length
from ballast case to lampholder):
up to 18 feet3
3 Data based on PENTRON HO lamp types
for primary ballast application. See the
Sylvania QUICKTRONIC®Electronic Ballast
Technology and Specification Guide (ECS-
ELECTRONIC) for Pentron Circline,
DULUX®L/F and other combinations.
4 Operation below 50°F (10°C) may affect
light output or lamp operation – see
“Low Temp. Starting” definition. Remote
red leads up to 18 feet. Keep blue leads
<10 feet.
Performance Guide
Specifications3
Universal Voltage (120-277V)
Input Rated1Ballast1Input1System
Item Current Lamp Lumens No. of Factor System1Mean1Power Efficacy
Number Description (AMPS) Type (lm) Lamps (BF) Lumens Lumens (Watts) (lm/W) BEF2
49101 QTP 1x39-24T5HO/UNV PSN 0.23/0.10 FP24T5HO 2000 1 1.00 2000 1860 29 70 3.45
(49100)*
49111 QTP 2x39-24T5HO/UNV PSN 0.47/0.20 FP24T5HO 2000 2 1.00 4000 3720 55/54 73/74 1.85
(49110)*
1 1.00 2000 1860 29 70 3.45
49101 QTP 1x39-24T5HO/UNV PSN 0.36/0.15 FP39T5HO 3500 1 1.00 3500 3255 42 83 2.38
(49100)*
49111 QTP 2x39-24T5HO/UNV PSN 0.76/0.32 FP39T5HO 3500 2 1.00 7000 6510 85/83 82/84 1.20
(49110)*
1 1.00 3500 3255 42 83 2.38
49121 QTP 1x54T5HO/UNV PSN 0.51/0.21 FP54T5HO 5000 1 1.00 5000 4650 62/60 81/83 1.67
(49120)*
49131 QTP 2x54T5HO/UNV PSN 1.00/0.43 FP54T5HO 5000 2 1.00 10000 9300 121/118 83/85 0.85
(49130)*
1 1.00 5000 4650 61 82 1.64
(49150)* QTP 1x80T5HO/UNV PSN 0.74/0.32 FP80T5HO 7000 1 1.00 7000 6510 90 78 1.11
FT80T5DL 6000 1 1.00 6000 5580 90 67 1.11
1: At 35°C lamp ambient temperature.
2: Ballast Efficiency Factor (BEF) shown = (Ballast Factor x 100) divided by Input Power (Note: calculation based on lowest wattage value).
*(Item Number) = Item Number/NAED in parentheses are models with leads/wires. Ballast with leads/wires contains 10 pieces each. Ballast without leads contain 20 pieces each.
Item Number 49131 QTP 2 x 54 T5HO/UNV PSN
QUICKTRONIC PROFESSIONAL
Number of Lamps (1, 2)
Starting/Ballast Factor
Line Voltage (120-277V)
Primary Lamp Wattage
System Life / Warranty
QUICKTRONIC products are covered
by our QUICK 60+®warranty, a
comprehensive lamp and ballast
system warranty. For additional
details, refer to our QUICK 60+
warranty bulletin.
Data based upon SYLVANIA PENTRON®
lamps shown. QUICKTRONIC®PHO
ballasts are also compatible with other
lamp manufacturers equivalent lamp
types that meet ANSI specifications.
Normal Ballast Factor
T5HO PROStart®UNV
Professional Series
OSRAM SYLVANIA
National Customer
Service and Sales Center
1-800-LIGHTBULB
(1-800-544-4828)
www.sylvania.com
Specifications subject to change without notice.
Dimensions:
Model QTP1x39-24T5HO/UNV PSN, QTP2x39-24T5HO/UNV PSN,
QTP1x54T5HO/UNV PSN and QTP1x80T5HO/UNV PSN enclosure size:
Overall: 360mm L x 30mm W x 22mm H
Mounting: 349mm
Model QTP2x54 T5HO/UNV PSN enclosure size:
Overall: 425mm L x 30mm W x 22mm H
Mounting: 415mm
Wiring:
Push-in connectors
Use 18AWG solid copper wire only
Product Weight:
1L: 0.68 lbs each (approx)
2L: 0.88 lbs each (approx)
BALLAST
1 LAMP
LAMP
White
Black
Red
Blue
2 LAMP
LAMP
LAMP
Blue
Yellow
Red
BALLAST
Black
White
Width
Mounting
Length
Length
Height