T5HO PSN
62
Lamp / Ballast Guide
Key System Features
System Information
• Universal voltage (120-277V)
• Low-profile (0.86" High)
• 100% Ballast factor
• QUICKSENSE®ballast technology
(end-of-lamp-life sensing)
• PROStart programmed rapid start
• UL type CC rated
• Min. Starting Temp:
• 0°F/-18°C
• -20°F/-29°C for QTP 2x54T5HO
Models
• Operates at >40 Khz to reduce
potential interference with infrared
control systems
• High power factor
• Low harmonic distortion
• Lightweight
• UL, CSA, FCC
SYLVANIA QUICKTRONIC PHO
is ideally suited for:
• Commercial & retail
• Hospitality & institutional
• New construction
• Direct lighting
• Indirect lighting
• Surface mount
• Cove lighting
Application Information
54W T5 - PENTRON®HO
1-lamp QTP1x54T5HO/UNV
2-lamp QTP2x54T5HO/UNV
Also operates:
FT55DL, FT50DL, FPC55, L58T8
39W T5 - PENTRON HO
1-lamp QTP1x39-24T5HO/UNV
2-lamp QTP2x39-24T5HO/UNV
24W T5 - PENTRON HO
1-lamp QTP1x39-24T5HO/UNV
2-lamp QTP2x39-24T5HO/UNV
Also operates:
FT36DL, FT24DL, CF24DF, CF36DF,
FPC40, FPC22
80W T5 - PENTRON HO
1-lamp QTP1x80T5HO/UNV
Also operates:
FT80DL
Two lamp models can be wired for one
lamp operation.
System PHO operates from 120V through
277V, 50 or 60Hz, eliminating “wrong
voltage” wiring errors and reducing the
number of models in inventory by half.
PROStart ballasts provide optimum starting
conditions to provide up to 100,000
switching cycles for use on occupancy
sensors and building control systems.
QUICKSENSE ballast technology helps to
protect against overheated bases and
sockets, as well as cracking of the glass
wall, and uses dynamic end-of-lamp-life
sensing to avoid false shutdowns caused
by some static sensing methods. QUICK-
SENSE ballast technology will auto reset
when the end-of-life lamps are replaced
with new ones.
The two lamp unit can be wired for one
lamp operation, allowing for an additional
50% reduction in inventory model numbers.
Input Initial System
System Type Power System Efficacy
(W) Lumens LPW
F40T12 - E.S. Magnetic Ballast (4-lamp) 172 11590 67
F34T12 - E.S. Magnetic Ballast (4-lamp) 144 9500 66
FO32T8/XP - QT4x32IS (4-lamp) 114 10800 95
FP54T5HO - QTP2x54T5HO/UNV PSN (2-lamp) 121 10000 83
FO32T8/XP - QT2x32IS (2-lamp) 59 5400 92
FP54T5HO - QTP1x54T5HO/UNV PSN (1-lamp) 62 5000 81
QUICKTRONIC®PROStart®T5HO
Universal Voltage
www.sylvania.com
<10% THD Electronic T5HO Fluorescent
Programmed Rapid Start Systems
Normal Ballast Factor
Professional Series
SYSTEM PHO comes in a 22H x 30W mm
profile, and PENTRON lamps are designed
to provide peak performance at 35°C
fixture ambient, allowing for smaller and
more innovative fixtures.
A complete OSRAM SYLVANIA System
Performance Guide showing performance
characteristics of lamps and ballasts is
available upon request.
SYLVANIA QUICKTRONIC PHO operates
PENTRON HO, PENTRON HO Circline, and
DULUX®L T5 lamps with full lumen output
and optimal system performance.
SYSTEM PHO provides nearly twice the
light output (188%) of T8 systems, with
the same number of lamps, allowing
many new design options. One lamp
fixtures can now be used in place of two
lamp models.
SYSTEM PHO ballasts contain QUICK-
SENSE ballast technology, a patented
circuitry designed to shut down the
system reliably and safely when lamps
reach end-of-life.
Setting the standard for quality, SYSTEM
PHO is also covered by our QUICK 60+®
warranty, the first and most compre-
hensive system warranty in the industry.
SYSTEM PHO is available in one and two
lamp models to cover a wide range of
applications.