Electronic Thermostat
E5L
Ideal for Simple Built-in Control.
A high switching capacity of 10 A at 250 VAC enables
direct load switching.
A sensor is provided to enable immediate application.
Sockets with finger protection (PTF14A-E) or without
finger protection (PTF14A) can be used.
Simple operation and settings. Even simpler with digital
models.
Model Number Structure
Model Number Legend
Ordering Information
Electronic Thermostats
E5L-A@
E5L-C@
Note: The E5L-C is not available with a set temperature range of 0 to 50°C.
Options (Order Separately)
Sockets
12
E5L-@@
1. Setting and Indication Methods
A: Analog setting, no display
C: Digital setting, display
2. Set temperature
30-20 : 30 to +20°C
0-50 : 0 to +50°C
0-100 : 0 to +100°C
100-200 : +100 to +200°C
Size Type Control method Control
output Model
45 × 35 mm Plug-in ON/OFF operation Relay
E5L-A -30-20
E5L-A 0-50
E5L-A 0-100
E5L-A 100-200
Size Type Control method Control
output Model
45 × 35 mm Plug-in ON/OFF operation Relay
E5L-C -30-20
E5L-C 0-100
E5L-C 100-200
Type Model
Front-connecting Socket PTF14A
PTF14A-E
E5L
2
Ratings and Characteristics
Ratings
Note: Do not use the output from an Inverter as the power supply.
Characteristics
*The accuracy of the accessory thermistor is not included.
Item Model E5L-A@E5L-C@
Power supply voltage 100 to 240 VAC, 50/60 Hz
Operating voltage range 85% to 110% of the rated supply voltage
Power consumption Approx. 3 VA
Inputs Element-interchangeable thermistor
Control method ON/OFF control
Control output SPDT contacts, 250 VAC, 10 A, cosφ = 1 (resistive load) SPST-NO contacts, 250 VAC, 10 A, cosφ = 1 (resistive load)
Setting method Analog setting Digital settings using keys on front panel
Indication method No display LCD digital display (character height: 12 mm)
Other functions
Setting protection (key protection)
Input shift
Direct/reverse operation
Ambient temperature 10 to 55°C (with no icing or condensation)
Ambient humidity 25% to 85%
Storage temperature 25°C to 65°C (with no icing or condensation)
Item Model E5L-A@E5L-C@
Indication accuracy --- ±(1°C + 1 digit) max.*
Setting accuracy --- ±(1°C + 1 digit) max.*
Hysteresis
30 to 20°C models: Approx. 0.5 to 2.5°C (variable)
0 to 50°C models: Approx. 0.5 to 4°C (variable)
0 to 100°C models: Approx. 0.5 to 4°C (variable)
100 to 200°C models: Approx. 0.7 to 4°C (variable)
1 to 9°C (in increments of 1°C)
Repeat accuracy 1% FS max. ---
Minimum scale
(standard scale)
30 to 20°C models and 0 to 50°C models: 5°C
0 to 100°C models and 100 to 200°C models: 10°C---
Influence of temperature --- ±((1% of PV or 2°C, whichever is greater) +1 digit) max.
Influence of voltage ---
Sampling period --- 2 s
Insulation resistance 100 M max. (at 500 VDC)
Dielectric strength
2,300 VAC, 50/60 Hz for 1 min (between charged terminals and uncharged metallic parts, between power supply
terminals and input terminals, between power supply terminals and output terminals, and between input terminals
and output terminals)
Vibration (malfunction) Frequency of 10 to 55 Hz, 0.5-mm double amplitude for 10 min each in X, Y, and Z directions
Vibration (destruction) Frequency of 10 to 55-Hz, 0.75-mm double amplitude for 2 h each in X, Y, and Z directions
Shock (malfunction) 147 m/s2, 3 times each in 6 directions 100 m/s2, 3 times each in 6 directions
Shock (destruction) 294 m/s2, 3 times each in 6 directions
Electrical life expectancy
(control output relay) 100,000 operations min (at maximum applicable load)
Memory protection --- Non-volatile memory (100,000 write operations)
Weight (Thermostat) Approx. 80 g (Thermostat only)
Degree of protection Front panel: IP40, Terminals: IP00
Approved standards ---
Conformed standards EN 61010-1 (IEC 61010-1), Pollution Degree 2, Overvoltage Category II
EMC Directives
EMI: EN61326-1
Radiated EMI: EN55011 Group1 ClassA
Conducted EMI: EN55011 Group1 ClassA
EMS: EN61326-1
Electrostatic discharge immunity: EN61000-4-2
Electromagnetic field strength immunity: EN61000-4-3
Burst noise immunity: EN61000-4-4
Conducted disturbance immunity: EN61000-4-6
Surge immunity: EN61000-4-5
Voltage dip and power interruption immunity: EN6100-4-11
E5L
3
External Connections
Note: For thermistor wiring, separate the input power supply and load lines as much as possible to avoid the influence of inductive noise.
Nomenclature
Dimensions (Unit: mm)
Thermostats
E5L-A@E5L-C@
*Control output Heating load: Terminals 8 and 12
Cooling load: Terminals 4 and 12
Be careful of the cooling load contacts, because they will be electrically
charged even when the E5L input power supply is OFF.
* Control outputs: Terminals 8 and 12
Use the keys on the front panel to set direct/reverse operation.
250 VAC, 10 A
Control output*
Input power supply: 100 to 240 VAC
Element-
interchangeable
Thermistor
250 VAC, 10 A
Control output*
Input power supply: 100 to 240 VAC
Element-
interchangeable
Thermistor
Hysteresis
adjuster (DIFF.)
Operation indicator
Temperature dial
Operation Indicator
Operation
indicator
Output status
Heating load Cooling load
Lit red. ON OFF
Not lit. OFF ON
E5L-A@
Mode Key Down Key Up Key
Operation indicator
Set value indicator
Protection indicator
Process value
and set value
display
Operation Indicator: ON
Set Value Indicator: SV
Lit when the set value is displayed.
Setting Protection Indicator:
Lit when setting protection is set.
Operation
indicator
Output status
Reverse
operation Direct operation
Lit ON ON
Not lit OFF OFF
E5L-C@
6.4
64
75.0
(4.6)
45
35
E5L-A@
6.4
64
70.4
45
35
E5L-C@
E5L
4
Wiring Connection Sockets (Order Separately)
Accessories
E52-THE-E5L Element-interchangeable Thermistor
Temperature Sensors (Order Separately)
E52-THE5A, E52-THE6D, and E52-THE6F Temperature Sensors can be ordered separately. For details, refer to an OMRON Web site.
Dimensions
Terminal
Arrangement and
Internal Connections
Mounting Hole
Dimensions
Included with the following models: 30 to 20°C, 0 to 50°C, and 0 to
100°C.
Temperature Range
Note: PVC cable is heat resistant from
40 to 105
°
C.
PTFE cable is heat resistant from
40 to 250
°
C.
*Use a 0 to 100
°
C thermistor for 0 to 50
°
C applications.
Tolerance
Included with 100 to 200°C Models.
Mounting Brackets (Two)
30 max.
45.5 max.
78.5 max.
Two, 4.5 x 6
mounting holes
8
35.4
3.4
7±0.2
14, M3.5 x 8
Sems screws
7±0.2
33 max.
45.5 max.
78.5 max.
Two, 4.5 x 6
mounting holes
14, M3.5 x 8
Sems screws
8
35.5
3.4
PTF14A PTF14A-E Socket with Finger Protection
8
11 10
9
12
13
14
7 6 5
4 3 2 1
(TOP VIEW)
68
±0.3
36
±0.2
Two, M4 or
4.5-dia. holes
(TOP VIEW)
Note: Can be mounted to
a DIN Track.
Color code PVC cable (12/0.18)
(5.5-dia.)
10
30
50030
Temperature
range
Color
code
Nominal
resistance
Thermistor
constant Lead wires
30 to 20°CBlue6 k (0°C) 3,390 K Heat-resistant
PVC cable
0 to 100°C*Black 6 k (0°C) 3,390 K
100 to 200
°
C
Yellow 0.55 k
(200°C) 4,300 K PTFE
Measured temperature Tolerance
30 to 100°C±2°C max.
100 to 200°C Measured temperature ±2% max.
Color code
10
15 60
50030
5-dia. max. PTFE cable (7/0.2)
E5L
5
Operating the E5L-C@
Set temperature
1. Press the Key to enter the Set Temperature Mode.
2. Press the and Keys to set the temperature. The display
will continue to change for as long as the key is held down.
Note: The default setting is the lowest temperature in the range.
Setting the Hysteresis
1. Press the Key to enter the Hysteresis Mode.
2. Press the and Keys to set the value. Each time the key is
pressed, the setting will change by 1°C. The setting will not
continue to change even if the key is held down. The key must be
released after each change. The hysteresis can be set from 1 to
9°C, in increments of 1°C.
Note: The default setting is 1°C.
Setting the Temperature Input Shift
1. Press the Key for at least 3 s to enter the Temperature Input
Shift Mode.
2. Press the and Keys to set the value. Each time the key is
pressed, the setting will change by 1°C. The setting will not
continue to change as the key is held down. The key must be
released after each change.
The input shift can be set from 9 to 9°C, in increments of 1°C.
Note: 1. The default setting is 0°C.
2. The control output turns OFF while this setting is being
made.
Setting Direct or Reverse Operation
1. Press the Key for at least 3 s to enter the Direct/Reverse
Selection Mode.
2. Press the and Keys to set the value. Direct operation can
be set by pressing the Key, and reverse operation can be set
by pressing the Key.
Note: 1. The default setting is for reverse operation.
2. The control output turns OFF while this setting is being
made.
Process value
Power ON
Set temperature
display
Process value
display
Setting Protection
Press the Key
for at least 3 s.
Press the Key
for less than 1 s.
Temperature Input Shift Direct/Reverse
Operation
Set
temperature
Hysteresis
Control stops.
Press the
and Keys
for at least 1 s.
Press the
and Keys
for at least 1 s.
Press the and Keys for at least 1 s. Press the Key for at least 3 s.
Press the Key
for at least 3 s.
Press the Key
for less than 1 s.
Press the Key
for less than 1 s.
Hysteresis Display
+1°C
+5°C
+9°C
OFF
Power ON
Set temperature
example: -5°C 4°C
OFF
Power ON
Hysteresis (1°C set)
Example:
64°C
Set temperature:
65°C
Control output (relay)
Control output (relay)
Hysteresis (1°C set)
Reverse Operation (Heating Control) Direct Operation (Cooling Control)
Input shift display Thermistor measured
temperature
Tempera-
ture dis-
play
(No shift) 25°C 25°C
(+9°C shift) 25°C 34°C
(-9°C shift) 25°C 16°C
Direct/reverse operation Display
Reverse operation
Direct operation
E5L
6
Setting Protection
1. Setting Protection (Process Value Display)
Press the and Keys simultaneously while the process
value is being displayed to change to the setting protection state.
2. Setting Protection (Set Temperature Display)
From the Setting Protection (process value display) Mode, press
the and Keys simultaneously to change to the setting
protection (set temperature display) state.
3. From the Setting Protection (set temperature display) Mode, press
the and Keys simultaneously to return to the process
value display with no setting protection.
Note: 1. Setting protection disables key operations to prevent the
settings from being changed accidentally. will be lit
while protection is in effect.
2. Protection will be maintained even when the power supply
is turned OFF and ON.
Error Displays and Causes
E5L-A@
When a thermistor disconnection occurs, the built-in relay operates at the OFF side (when NO contacts are used).
E5L-C@
When an error occurs, the display shows the error code. Take the necessary measures, referring to the following table.
Note: 1. Errors are not displayed while settings are being changed, except for memory errors. The control output status will be as shown in the
above table while the set temperature or hysteresis is being set. The control output will be OFF while the temperature input shift or direct/
reverse operation setting is being set. Key operations will be possible when an error occurs, except for a memory error.
2. The setting protection indicator ( ) and set value indicator ("SV") will be continued even when settings are protected, except when a
memory error occurs.
Display example Display
Process value display
Set temperature display
Thermistor
NO contacts
(Terminal numbers 8 and 12)
* Heating load
NC contacts
(Terminal numbers 4 and 12)
* Cooling load
Disconnection OFF ON
Short-circuit OFF ON
Display Meaning Cause Control output
FFF (lit) Overflow The process value is higher than the set
temperature range.
Reverse operation: OFF
Direct operation: ON
--- (lit) Underflow The process value is lower than the set
temperature range
Reverse operation: ON
Direct operation: OFF
FFF (flashing) Thermistor short-
circuited The thermistor is short-circuited. Reverse operation: OFF
Direct operation: OFF
--- (flashing) Thermistor
disconnected The thermistor is disconnected. Reverse operation: OFF
Direct operation: OFF
E11 (lit) Memory error The thermostat has failed. OFF
E5L
7
Safety Precautions
Do not touch the terminals while power is being supplied.
Doing so may occasionally result in minor injury due to
electric shock.
Do not allow pieces of metal, wire clippings, or fine metallic
shavings or filings from installation to enter the Product.
Doing so may occasionally result in electric shock, fire, or
malfunction.
Do not use the Product where subject to flammable or
explosive gas. Otherwise, minor injury from explosion may
occasionally occur.
Never disassemble, modify, or repair the Product or touch
any of the internal parts. Minor electric shock, fire, or
malfunction may occasionally occur.
If the output relays are used past their life expectancy,
contact fusing or burning may occasionally occur. Always
consider the application conditions and use the output
relays within their rated load and electrical life expectancy.
The life expectancy of output relays varies considerably
with the output load and switching conditions.
Tighten the terminal screws to between 0.74 and 0.90 N·m.
Loose screws may occasionally result in fire.
Set the parameters and wiring of the Product so that they
are suitable for the system being controlled. Unexpected
operation may occasionally result in property damage or
accidents.
A malfunction in the Product may occasionally make
control operations impossible or prevent alarm outputs,
resulting in property damage. To maintain safety in the
event of malfunction of the Product, take appropriate safety
measures, such as installing a monitoring device on a
separate line.
Be sure to observe the following precautions to prevent failure to
operate, malfunction, or adverse effects on the performance and
functions of the Thermostat. Not doing so may occasionally result in
unexpected events.
1. The Product is designed for indoor use only.
Do not use the Product outdoors or in any of the following
locations.
Locations directly subject to heat radiated from heating
equipment
Locations subject to water or oil
Locations subject to direct sunlight
Locations subject to dust or corrosive gas (in particular, sulfide
gas and ammonia gas)
Locations subject to sudden or extreme temperature changes
Locations subject to icing or condensation
Locations subject to vibration or shock
2. Use and store the Product within the rated temperature and
humidity ranges. Provide forced cooling if required.
3. To allow heat to escape, do not block the area around the
Product.
4. Be sure to wire the Product properly with the correct terminal
polarity.
5. Use the specified size of crimped terminals for wiring (M3.5, width
of 6.8 mm or less). To connect bare wires to the terminals, use
copper wires with a gauge of AWG24 to AWG14 (equal to a
cross-sectional area of 0.205 to 2.081 mm2). (The stripping length
is 5 to 6 mm.) Do not connect more than two wires or two crimp
terminals to one terminal. When connecting two wires, they must
be of the same size and type.
6. Do not connect anything to terminals that are not used.
7. Allow as much space as possible between the Thermostat and
devices that generate powerful high frequencies or surges.
Separate the wiring to the Thermostat from high-voltage or high-
current lines, and do not place the wiring to the Thermostat in
parallel with or in the same wiring paths as power lines.
8. Use this Product within the rated load and power supply
specifications.
9. Turn ON the power supply at least 30 minutes prior to starting
control operations.
10. A switch or circuit breaker must be provided close to the
Thermostat. The switch or circuit breaker must be within easy
reach of the operator, and must be marked as a disconnecting
means for the Thermostat.
11. Do not use paint thinner or similar solvents to clean the
Thermostat. Use standard grade alcohol.
12. Design the system (e.g., the control panel) considering the 2.5
second of delay between turning ON the Thermostat and
stabilization of the Thermostat's output.
CAUTION Precautions for Safe Use
E5L
8
Mounting the Thermostat
1. Using the PTF14A Socket or PTF14A-E Socket with Finger
Protection, mount the Thermostat to the bracket that is provided.
2. The structure does not allow the case to be removed. Do not apply
excessive force when mounting the Thermostat.
Settings
1. E5L-A@ Temperature Dial
The temperature dial has some backlash. To adjust the
temperature more accurately, turn the dial clockwise when
adjusting the temperature.
Do not change the setting of the temperature dial more than 20
times.
Do not attempt to turn the dial past the range of the setting scale.
Applying excessive force may damage the Thermostat.
2. E5L-A@ Hysteresis Dial
This dial can be used to set hysteresis for the ON/OFF operation.
Turn the dial clockwise to reduce the hysteresis and
counterclockwise to increase the hysteresis. Increase the
hysteresis to extend the life of the relay by preventing relay
chattering caused by the control output turning ON and OFF
frequently.
Do not change the setting of the temperature dial more than 20
times.
Mounting the Thermistor
Select a location for the temperature sensor of the thermistor
where the temperature distribution of sensing objects will not be
changed by installation.
Insert the temperature sensor as far in as possible.
When measuring fluid temperature, the thermistor should be
installed against the current. Before mounting, take factors such as
the bending moment of inertia and vibration into consideration.
Do not apply mechanical force to the temperature-sensing part of
the thermistor.
The E52-THE@@ Thermistor can be used for applications that
require metal protective tubing. Consult with your OMRON
representative.
Other Precautions
Do not use the E5L-C@ if the front sheet is peeling or torn.
Use appropriate tools to disassemble the Thermostat for disposal.
Precautions for Correct Use
(98.6)
(4.6)
(4.6)
(98.6)
E5L+PTF14A E5L+PTF14A-E
9
MEMO
MEMO
10
Warranty and Application Considerations
Read and Understand This Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you
have any questions or comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or
other period if specified) from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT,
MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER
ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET
THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR
IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS,
OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON
CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE
PRODUCTS UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED,
INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE
MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of
products in the customer's application or use of the products.
Take all necessary steps to determine the suitability of the product for the systems, machines, and equipment with which it will
be used.
Know and observe all prohibitions of use applicable to this product.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT
ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON
PRODUCTS ARE PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR
SYSTEM.
Disclaimers
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a
warranty. It may represent the result of OMRON's test conditions, and the users must correlate it to actual application
requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability.
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons. Consult with
your OMRON representative at any time to confirm actual specifications of purchased product.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
Authorized Distributor:
In the interest of product improvement,
specifications are subject to change without notice.
Cat. No. H162-E1-01
OMRON Industrial Automation Global: www.ia.omron.com
Printed in Japan
0309 (0309)
OMRON Corporation
Industrial Automation Company
Regional Headquarters
OMRON EUROPE B.V.
Wegalaan 67-69-2132 JD Hoofddorp
The Netherlands
Tel: (31)2356-81-300/Fax: (31)2356-81-388
OMRON ELECTRONICS LLC
One Commerce Drive Schaumburg,
IL 60173-5302 U.S.A.
Tel: (1) 847-843-7900/Fax: (1) 847-843-7787
OMRON ASIA PACIFIC PTE. LTD.
No. 438A Alexandra Road # 05-05/08 (Lobby 2),
Alexandra Technopark, Singapore 119967
Tel: (65) 6835-3011/Fax: (65) 6835-2711
OMRON (CHINA) CO., LTD.
Room 2211, Bank of China Tower,
200 Yin Cheng Zhong Road,
PuDong New Area, Shanghai, 200120, China
Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200
Control Devices Division H.Q.
Analog Controller Division
Shiokoji Horikawa, Shimogyo-ku,
Kyoto, 600-8530 Japan
Tel: (81) 75-344-7080/Fax: (81) 75-344-7149
2-2-1 Nishikusatsu, Kusatsu-shi,
Shiga, 525-0035 Japan
Tel: (81) 77-565-5216/Fax: (81) 77-565-5568
© OMRON Corporation 2009 All Rights Reserved.
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Omron:
E5LC-6 E5LC-2 E5LC-5 E5LC-4 E5LC-1 E5LC-3 E5LC-7