Application Report
SLUA250 - March 2001
1
A Power Management Interface Circuit for Telecom
Hot Swap with Local DC/DC Conversion
Andrew Ripanti Power Distribution and Processing Solutions
ABSTRACT
Much of the Telecom and Datacom equipment infrastructure operates from a power
architecture based on a –48 Vdc distribution bus. This supply level has emerged as a
standard and efficient means of distributing power throughout equipment racks, while
facilitating alternate source operation from secondary power, such as batteries, when the AC
line supply is unavailable. To further improve uptime ratios while meeting the needs of
maintenance and reconfiguration, hot swap capability is often incorporated in removable
subassembly specification and design.
Today, the brains of these communication systems; i.e., microprocessors, DSPs, ASICs, and
programmable logic, are evolving to ever-lower operating voltages. Typical integrated
circuits run at supply levels of 3.3 V, 2.5 V, and even lower. As this occurs, new devices and
modules are being developed to address the functions of hot-swapping the –48 Vdc bus, and
subsequent conversion to local regulation levels. These devices provide a high level of
integration for the point-of-use power supplies, saving the system designer both design time
and critical board space.
This application report presents one possible solution to the telecom plug-in power problem,
based on a nominal –48 Vdc system bus and a module needing two low-voltage supply
outputs. The material includes a detailed design methodology for tailoring the circuit to the
specific requirements of the reader’s system. The solution is based on two device families
offered by Texas Instruments, the UCC3913 and UCC3921 hot swap power manager ICs,
and the PT3320 series of integrated switching regulators (ISRs).
The document organization is such that some example system requirements are defined,
then a step-by-step procedure is presented for determining external component values to set
user-programmable features. There is discussion of some optional features. Finally, the
circuit operation and performance is further illustrated through scope plots of the circuit’s
response to various live insertion events, and input and output fault conditions.
SLUA250
2A Power Management Interface Circuit for Telecom Hot Swap with Local DC/DC Conversion
CONTENTS
1 The Power Transmission Problem 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 The Power Management Interface 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 Additional Features 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 Performance Evaluation and Sample Waveforms 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5 Notes 33. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6 References 33. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SLUA250
3
A Power Management Interface Circuit for Telecom Hot Swap with Local DC/DC Conversion
1 Introduction
1.1 The Power Transmission Problem
Many telecom and datacom systems are configured from subsystem racks and chassis, or
boxes, each containing a system host or controller card, one or more power supplies, and
various sub-assembly cards performing functions of data processing, data transmission and
switching. The interconnect between the different modules is often accomplished with a
backplane or motherboard. Power is commonly provided to the various module slots via a
48 Vdc distribution bus. This is an efficient means of supplying power throughout the box for
two main reasons:
1. Current bussing requirements are significantly reduced compared to the current levels that
would be encountered if power were distributed at the regulation levels of 5.0 V, 3.3 V, or
even lower, and
2. System supply voltage droops and spikes of several volts are more easily tolerated by the
driven electronics, as significant voltage margin now exists between the power bus and
the regulation levels.
This configuration, however, creates the need for efficient and cost-effective voltage conversion
to the local regulation levels at the points-of-use.
The power conversion issue is further complicated when the driven boards are specified to have
hot swap or hot plug capability. Simply put, hot swap is the ability to safely insert a module into
or remove it from a host system, without first interrupting power to the host. This feature is
generally designed in wherever there is a need to replace modules on-the-fly. Such a
requirement may be for purposes of repair, reconfiguration, redundancy, or system upgrade. It is
also useful in systems with high availability requirements (i.e., high up-time ratios). Finally, hot
swap requirements may be included in the target industry specification that is being designed to,
such as PCI, Compact PCI, USB, and 1394. Not surprisingly, it has seen significant use in
telecom systems.
As a highly desirable feature in many applications, hot swap capability also creates several
issues that must be addressed in the system design. A number of related phenomena occur with
a live insertion or removal event, including contact bounce, arcing between connector pins, and
large voltage and current transients. The stresses on the mechanical interface, power supply,
and input filter components can produce latent defects leading to intermittent or premature
failures. Therefore, a power interface is needed which can safely mitigate these effects. This
interface provides protection for both the host and plug-in electronics, data stored or transferred
in the system, and any transactions within or between systems.
This application note presents one possible solution for hot swapping a 48-Vdc bus, and
performing the required DC/DC conversion. The organization is such that the operating
parameters are defined, a toplevel electrical schematic presented, followed by a detailed
procedure for determining component values, description of some optional features, and
performance verification.
The proposed solution is built around two main device types offered by Texas Instruments (TI).
The UCC3921 Hot Swap Power Manager (HSPM) integrated circuit handles the main functions
needed for hot swap capability; the conversion is performed using the PT3320 series of
integrated switching regulators (ISRs).
SLUA250
4A Power Management Interface Circuit for Telecom Hot Swap with Local DC/DC Conversion
The UCC3921 IC is a floating, negative-voltage hot-swap controller which, in conjunction with an
external N-channel FET, provides inrush current limiting, fault timeout, and fault reporting. An
on-chip shunt regulator generates the internal supply voltages and the gate drive for the external
pass element. Other features include continuous supply current monitoring with electronic circuit
breaker, remote enable, and userprogrammable duty cycle to limit dissipation in the FET in
automatic retry mode. For a complete description of the UCC3921 features and operation,
please refer to the device data sheet.
The PT3320 is a series of 30-W, isolated DC/DC converter modules designed specifically for
48-V distribution systems. They are complete modules assembled onto a space-saving,
PCB-based, vertical- or horizontal-mount SIP package. A wide range of output voltage/current
combinations is available from 2 V to 15 V (see Table 1). A wide input voltage operating range
(36.0 V to 75.0 V) and high efficiencies make them applicable in numerous distributed power
applications. The converters contain an external inhibit function, and remote sense inputs to
compensate for any voltage drop from converter output to load. The only external component
required for operation is a 330-µF electrolytic capacitor. For further information on the full range
of 48-V converter products, including the 3-W to 7-W PT4200/4300 and 15-W PT3100 series
modules, please visit www.ti.com.
Table 1. PT3320 Series of Converters
DEVICE NUMBER
OUTPUT
DEVICE NUMBER VOLTAGE (V) CURRENT (A)
PT3321 3.3 8
PT3322 5.0 6
PT3323 12.0 2.5
PT3324 15.0 2
PT3325 2.0 8
PT3326 2.5 8
PT3327 1.8 8
PT3328 5.2 6
SLUA250
5
A Power Management Interface Circuit for Telecom Hot Swap with Local DC/DC Conversion
1.2 Design Requirements
To illustrate the detailed design steps for using the UCC3921 in a 48 V (or Telecom) system,
the following system-level requirements were defined:
Input supply voltage: nominal 48 Vdc, 36 Vdc (min) to 72 Vdc (max)
Output voltage/current: 1.8 Vdc at 6.0 A (max), and 2.5 Vdc at 6.0 A (max)
Isolated outputs
Redundant supply operation (2 sources)
Hot-swap capability
Interface to host ENABLE signal
Fault indication to host
0_C to 70_C ambient operating temperature
Host VDD supply: 3.3 Vdc
SLUA250
6A Power Management Interface Circuit for Telecom Hot Swap with Local DC/DC Conversion
2 The Power Management Interface
2.1 Electrical Schematic Diagram
The electrical schematic for one type of implementation of the power interface specified in the
design requirements is shown in Figure 1. Some of the secondary functions are shown here in
block form for later discussion. The output voltages are generated from the 48-Vdc input via the
PT3326 (2.5 V) and PT3325 (1.8 V) modules[1]. The PT3320 modules are fully isolated, thus
eliminating the need for additional transformers. The UCC3921 HSPM resides between the input
supply and the VIN pins of the converters. It drives N-channel FET Q1, which switches the low
side of the supply (48 V). The SNS input of the IC monitors the voltage drop across sense
resistor R5, so the current load on the 48 V supply is monitored.
UDG00143
C1 0.1µF
C2 1.0µF
R1
1.0 M
1%
R4
82 k
R2
13 k
1%
C3
1.0 µ F
R3
10 k, 1 W
R5
0.025
1 W, 1%
D1
MBR3100
F1
3 AG, 2 A
D2
MBR3100
F2
3 AG, 2 A
R7
100 k
C5
100µF
100 V
C6
330µF
6.3 V
GND
SD
FLT
HOST_VDD
U1
Q2
2N7000
Q1
IRF530
1
2
3
45
6
7
8
SDFL
IMAX
VDD
CT VSS
SNS
OUT
PL
UCC3921
R13
0
VIN+
VIN+
VIN+
VIN
VIN
VIN
INH
N/C
N/C
+SNS
VOUT+
VOUT+
VOUT+
VOUT+
VOUT
VOUT
VOUT
SNS
ADJ
PT3325
7
8
9
2
1
3
4
5
6
19
17
16
15
14
18
12
11
10
13
VIN+
VIN+
VIN+
VIN
VIN
VIN
INH
N/C
N/C
+SNS
VOUT+
VOUT+
VOUT+
VOUT+
VOUT
VOUT
VOUT
SNS
ADJ
PT3326
7
8
9
2
1
3
4
5
6
19
17
16
15
14
18
12
11
10
13
C8
330µF
6.3 V
C7
100µF
100 V
U2
U3
LCLRTN
R17
0
HOST/
SYSTEM
INTERFACE UVLO
VIN
+1.8VDC
+2.5VDC
48VDC_N1
48VDC_N2
Figure 1. Top-Level Schematic Diagram for –48 Vdc Hot Swap with DC/DC Conversion
SLUA250
7
A Power Management Interface Circuit for Telecom Hot Swap with Local DC/DC Conversion
Table 2. Hot Swap Power Circuit Signal Descriptions
SIGNAL NAME DESCRIPTION
48VDC_N1 48-Vdc input supply no. 1 to the plug-in PCB.
48VDC_N2 48-Vdc input supply no. 2 to the plug-in PCB.
GND Supply common for the two 48 Vdc supplies. This is also intended as the system ground node.
HOST_VDD Host or controller VDD node, +3.3 V dc.
SD Active low SHUTDOWN input for remote or host control of the module ON/OFF status.
FLT Active low FAULT output to the system.
+1.8VDC +1.8 V dc power supply output.
+2.5VDC +2.5 V dc power supply output.
LCLRTN Common local return for the two output supply rails.
2.2 Detailed Circuit Description
The UCC3921 device determines load current levels by monitoring the voltage drop across a
low-ohmic value sense resistor, R5, as shown in Figure 1. The device has two distinct current
thresholds for defining different modes of operation. The first threshold is the fault current,
referred to herein as IFLT. This can be thought of as the circuit breaker trip current. When
enabled, and under normal load conditions below the fault current threshold, the UCC3921 OUT
pin drives external FET Q1 gate with a nominal 9.5-V source, relative to the VSS node. Q1 is
switched on, and completes the low impedance return path from the load (VIN pins of the
ISRs). When the device detects a nominal drop of 50 mV or greater between the SNS and VSS
pins, an internal source begins charging an external capacitor connected to the CT pin,
essentially generating a time delay before tripping, or opening the supply return path by turning
off transistor Q1. However, during this timeout period, the pass FET is still driven as a
lowohmic value switch. If the fault condition is removed prior to timeout, the capacitor is
discharged, and supply operation continues uninterrupted.
The second threshold is the maximum current that will be sourced to the load by the HSPM
circuit, or IMAX. Under heavy overcurrent or short-circuit conditions, the input current to the
converter circuit will be clamped at this maximum level. During a live PCB insertion, inrush
current caused by charging bulk capacitance (C5 and C7 in Figure 1) will also be limited to this
level. The threshold is programmable by using a resistor divider to set the voltage at the U1
IMAX pin. The VDD node provides a ready reference for this divider. In the Figure 1 schematic,
this threshold is set by the R1/R2 resistor network.
Since the UCC3921 is a current-driven device, it essentially floats from the positive supply input.
Resistor R3 sets the biasing supply level for the VDD input. Capacitor C1 provides supply
bypassing for U1, and C2, tied to the CT pin, is the timing capacitor. Resistor R7 is an optional
component used by the UCC3921 to further limit power dissipation in the pass element, under
certain fault conditions, below the limits that are automatically provided by the IC.
The detailed procedure for determining component values for the hot swap interface will be
shown in Section 2.3, Circuit Design Procedure. For a complete description of the HSPM IC
operation and electrical specifications, see the UCC3921 device data sheet.
Capacitors C6 and C8 provide the energy storage capability required for proper operation of the
PT3320 switcher modules, U2 and U3 respectively. They also provide some output filtering for
the DC/DC converters. The 330-µF value used is the manufacturers recommended value. The
input capacitors C5 and C7 are used to ensure good power quality to the ISRs.
SLUA250
8A Power Management Interface Circuit for Telecom Hot Swap with Local DC/DC Conversion
Diodes D1 and D2 provide a diodeOR function between the two redundant supply nodes
(48VDC_N1 and 48VDC_N2). If only one supply is present, or if one supply has failed, supply
return is still provided by the alternate path. Note that Schottky diodes are used; at least one of
these devices is always conducting, so Schottkys are used to minimize the reduction in overall
efficiency of the interface.
Fuses F1 and F2 provide a one-shot over-current protection in the event of catastrophic failure
of the more intelligent protection devices downstream. The PT3320 ISRs feature output
short-circuit protection. The UCC3921 features both a programmable current limit, and circuit
breaker operation. These provide redundancy to the output protection, and protect against an
overcurrent or short-circuit on the primary (VIN) side. Should these devices fail in the right
combination, fuses F1 and/or F2 provide a permanent, mechanical interrupt.
The block labeled HOST/SYSTEM INTERFACE in Figure 1 is an optional sub-circuit to allow
remote ON/OFF control of the plug-in module, and generate a current fault indication back to the
host. This block provides the level-translation needed to refer the multifunctional SDFL pin of the
UCC3921 to the system common, or GND node. If these features are not needed,
implementation of this circuit is not necessary.
The block labeled UVLO provides an optional undervoltage lockout (UVLO) function to the
startup of the two DC/DC converters. However, the PT3320 regulators incorporate an internal
UVLO circuit, the threshold of which is specified to be 33 ±2.0 Vdc. Since the design
specification requires this circuit to operate down to a 36-V supply level, and the maximum ISR
UVLO level is just below this voltage, this solution was developed assuming the internal UVLO is
to be used. To address a wider range of application requirements, an alternative implementation
of an external UVLO circuit is shown in Section 3.3, Optional UVLO Circuit.
2.3 Circuit Design Procedure
The following is a sequence of design steps that can be used to determine component values for
the configuration circuitry around the hot-swap controller IC. The process takes into
consideration the load characteristics, both during startup and under dc operating conditions,
and the device parameter specifications. To assist the reader in determining the source and
value of the UCC3921-specific variables plugged into the following equations, Appendix I
summarizes the key device parameters.
2.3.1 Step 1 – Determine Input Load Current
In order to set the fault levels for the HSPM IC, the nominal load current on the input supply
must be estimated. Given the operating loads on the two regulated outputs from the design
specification, the converter efficiency can be used to estimate the average load on the primary
(bus) side. Also, since the PT3320 modules are switching regulators, the peak load is
anticipated to occur when the bus potential is at its lowest.
From the PT3321 curves shown in the data sheet[2], the efficiency at 6 A for input voltage of
36 V is nearly 80%, decreasing to about 75% at 75 V. Power delivered to the loads, POUT, and
subsequently input current to the board, IIN, are estimated from the following equations.
POUT +PO1 )PO2 +ǒVO1 ILOAD1Ǔ)ǒVO2 ILOAD2Ǔ
where:
(1)
SLUA250
9
A Power Management Interface Circuit for Telecom Hot Swap with Local DC/DC Conversion
VO1 = local regulation level No. 1, +2.5VDC
ILOAD1 = maximum output load on VO1
VO2 = local regulation level No. 2, +1.8VDC
ILOAD2 = maximum output load on VO2
The input supply current under normal steady-state operation, IIN, can then be estimated from:
IIN +PIN
VIN +
PO1
h1)PO2
h2
VIN
IIN +VO1 ILOAD1
h1 VIN )VO2 ILOAD2
h2 VIN
where:
PIN = input power delivered to the board
η1, η2 = respective converter efficiencies for outputs 1 and 2
VIN = the input supply voltage level
For reasons detailed in Section 2.3.5, the designer must determine the maximum input current
at each of the input voltage extremes. Therefore, two maximum current levels need to be
calculated. Defining IIN(max) as the supply current when the bus is at its lowest potential, and
IIN(max ) as the supply current when the bus is at its highest potential, then substituting the
values from the requirements specification, the input current levels shown in equations 4 and 5
are obtained. Note that equations 4 and 5 are a simplification of equation 3 when the converters
are anticipated to be operating at virtually equivalent efficiency points.
IIN(max) +ǒVO1 ILOAD1Ǔ)ǒVO2 ILOAD2Ǔ
h36 VIN(min)
IIN(max) +[(2.5 V 6.0 A))(1.8 V 6.0 A)]
(0.8 36 V)
or
IIN(max) +0.896 A
and
IIN(maxȀ)+ǒVO1 ILOAD1Ǔ)ǒVO2 ILOAD2Ǔ
h75 VIN(max)
IIN(maxȀ)+[(2.5 V 6.0 A))(1.8 V 6.0 A)]
(0.75 72 V)
or
IIN(maxȀ)+0.478 A
(2)
(3)
(4)
(5)
SLUA250
10 A Power Management Interface Circuit for Telecom Hot Swap with Local DC/DC Conversion
These estimates were made considering the dc or average-output currents. For the PT3320
series, the input ripple current is typically less than 0.25 A peak. This is added to the average
values to get an approximation of the peak input current under normal operating conditions, to
ensure that the HSPM does not trigger due to expected input ripple. The results (rounded to the
nearest 10 mA) are:
IIN(max) ^1.15 A
IIN(maxȀ)^0.730 A
2.3.2 Step 2 Set Fault Current Level And Determine Sense Resistor Value
The fault current level for the hot swap interface circuit must be selected. This is established by
the value of the sense resistor, R5 in the Figure 1 schematic. Since the nominal overcurrent
threshold of the UCC3921 is 50 mV, the resistor value can be determined from equation 6.
R5 +VFLT
IFLT +50 mV
2.0 A +25 mW
Selecting a nominal fault threshold of 2.0 A provides nearly 100% margin over the anticipated
peak operating levels. Some design margin is desirable to provide headroom for any transient
peaks on the output supplies, tolerances on the converter efficiency from unit-to-unit, transients
on the 48-V supply bus that cause surges in input current, and as an overall guard against
nuisance trips. Using the UCC3921 specification values for the overcurrent threshold, and with
the sense resistor value fixed, the minimum and maximum current fault levels can be verified
using equations 7 and 8.
IFLT(min) +VFLT(min)
R5 +1.84 A
IFLT(max) +VFLT(max)
R5 +2.14 A
where :
VFLT(min) = minimum fault (overcurrent) threshold
VFLT(max) = maximum fault threshold
The calculated minimum value, 1.84 A, demonstrates that significant margin is available even
with a device at the low end of its specification limit.
(6)
(7)
(8)
SLUA250
11
A Power Management Interface Circuit for Telecom Hot Swap with Local DC/DC Conversion
2.3.3 Step 3 Set IMAX Threshold And Determine IMAX Divider Values
The maximum sourcing current level of the hot swap circuit, herein referred to as IMAX, is user
programmable, using the IMAX input pin of U1. In an effort to predict performance under
worst-case parameter conditions, it is recommended to establish the lower threshold for this
maximum sourcing capability, or IMAXMIN. Generally, this will correspond to the IMAX level for a
device with a regulator output (VDD) at the specification minimum voltage, taking into account
two other sources of variance, the input offset voltage and bias current of the internal linear
current amplifier (LCA). For proper device operation, this value should be greater than the
calculated maximum fault current, IFLT(max). If a relatively fast rate of input current slewing is
allowed, or a large amount of bulk capacitance exists at the input to the plug-in, the IMAX
feature can be used to accomplish faster charging of the load capacitance, thus minimizing the
startup transient duration. However, if the distribution supply has a slow transient response,
minimal output capacitance, or is required to operate near peak capability at the expected
system steady-state load, the IMAX level should be selected with these limitations in mind. In
addition, under a short-circuit situation, the load current of the affected module(s) will make a
step change to this level. For this example, a minimum sourcing level of 4.0 A is used.
Figure 2 is a simplified model of the UCC3921 operation when the sense voltage, VSNS, is
above the IMAX threshold. During inrush or short-circuit conditions, the HSPM device acts to
control the gate of Q1 such that it appears as a constant-current source. The internal LCA will
respond to maintain the VSNS node equal to the IMAX reference, (i.e., the drop across the sense
resistor equal to the drop across R2.) Therefore, an equation for the sense voltage is generated
by writing the loop equation at the linear current amplifier (LCA) inputs (equation 9).
UDG00141
3LINEAR
CURRENT
AMPLIFIER
+
2
6
5
7
RSNS
IBIAS
R2
R1
VDD
OUTPUT
VIMAX
VSNS
UCC3921
±VOS
Figure 2. Model of UCC3921 Linear-Mode Operation
SLUA250
12 A Power Management Interface Circuit for Telecom Hot Swap with Local DC/DC Conversion
VSNS +VIMAX *VBIAS "VOS
where:
VSNS = the drop across the sense element
VIMAX = the voltage at the 3921 IMAX input pin
VBIAS = the error component developed by the IMAX bias current
VOS = the input offset of the internal LCA
Also from Figure 2, the VIMAX DC voltage is given by the R1/R2 divider equation.
VIMAX +R2
R1 )R2 VREF
where:
VREF = the internal shunt regulator output, VDD
Considering that the bias current flow is into the IMAX pin, the smallest error contribution occurs
for a device with negligible bias current, which is approximated here to zero. Then, a special
case of equation 9 for the minimum sense voltage in linear mode, is given by equation 11.
VSNS(min) +VIMAX(min) *VOS
Given that VSNS(min) = IMAXMIN × R5, combining equations 10 and 11, and solving for R2 in
terms of R1, yields:
R2 +ǒIMAXMIN R5Ǔ)VOS
ƪVREF(min) *ǒIMAXMIN R5Ǔ*VOSƫ R1
The value for R1 can be set to limit the overall current draw of the divider net; if R1 is set to
1 M, equation 12 then becomes:
R2 +(4.0 0.025))15 mV
[9.0 *(4.0 0.025)*15 mV] 1.0 MW
or
R2 +12.94 kW
The standard 1% value of 13 k was selected for R2.
(9)
(10)
(11)
(12)
(13)
SLUA250
13
A Power Management Interface Circuit for Telecom Hot Swap with Local DC/DC Conversion
With values now selected for resistors R1 and R2, the actual minimum and maximum sourcing
current levels is predictable. These values are useful for determining the startup time (ramp-up
from 0 V to the dc input level) under different conditions. Equations 14 and 15 are obtained by
manipulating equation 12. For the IMAXMAX value, the error contribution from the bias current is
included.
IMAXMIN +ƪR2
R1)R2 VREF(min)ƫ*VOS
R5 +4.02 A
IMAXMAX +ƪR2
R1)R2 VREF(max)ƫ)VOS )VBIAS
R5 +6.07 A
2.3.4 Step 4 Soft-Start Programming
The UCC3921 is easily configured for optional soft-start operation. Without soft-start, when a
plug-in is inserted into a live socket, the resultant inrush makes a step change to the IMAX limit,
where it becomes clamped for the duration of the transient period. Soft-start operation provides
an inrush slew rate control, such that the load charging current is gradually ramped, potentially
to the maximum value established by the IMAX pin programming resistors.
Soft-start is selectable by installing a capacitor in parallel with the IMAX programming resistor
(shown in Figure 1 as capacitor C3.) The feature operates by putting an RC time constant on the
voltage ramp at the IMAX pin when the power manager is started. This forces the device to
operate in linear mode immediately from Q1 turnon, essentially producing a dynamic IMAX
function.
For a UVLO-protected load, such as presented by the two ISRs in this solution, the startup
voltage ramp to the converter inputs will have two stages. During the first stage of rampup, from
turnon until achieving the UVLO threshold, the load appears virtually capacitive to the charging
source. This capacitance, CLOAD, is the equivalent capacitance of the input filter capacitors, the
converter input capacitance, and any parasitics. Wherever this quantity is used in this document
to derive other values, it is approximated as the 200-µF value of C5 and C7.
For a constant-current source of value IMAX (i.e., no soft-start), the voltage at the converter
inputs during this stage, for a charging time of t, is given by equation 16.
nINU1(t) +IMAX t
CLOAD
Once the load charges to the UVLO threshold, VUV, the ISRs are allowed to start up. During this
second stage of the voltage ramp, the load capacitance is charged by the sourcing current in
excess of the ISR startup load, iL(t). This portion of the ramp-up curve is given by:
nINA1(t) +ƪǒIMAX *iL(t)Ǔ ǒt*tVUVǓƫ
CLOAD )VUV
(14)
(15)
(16)
(17)
SLUA250
14 A Power Management Interface Circuit for Telecom Hot Swap with Local DC/DC Conversion
where:
iL(t) = load startup current
VUV = the UVLO threshold voltage
tVUV = the time to charge the input from 0 V to VUV, from equation 16
When soft-start programming is used, both the input voltage and current waveforms are of
interest. Due to the control action of the U1 LCA described above in step 3, we know that the
sense voltage tracks the R2 voltage during rampup, which is now the voltage across capacitor
C3. Since the output current of the HSPM circuit can be determined from the drop across R5,
the following equation for input current to the load is derived:
iIN(t) +IMAX ȧ
ȱ
Ȳ1*eǒ*t
TSSǓȧ
ȳ
ȴ
where:
iIN(t) = the charging load on the 48-Vdc supply
SS = the soft-start time constant, given by SS = R2 × C3, in seconds.
Since the capacitor charging current is given by equation 18 under this condition, the input
voltage profile has an exponential term also. The first stage of the input rampup, prior to startup
of the ISRs, is defined by equation 19.
nINU(t) +
TSS IMAX
CLOAD ȧ
ȱ
Ȳeǒ*t
TSSǓ)t
TSS *1ȧ
ȳ
ȴ
where:
SS = the soft-start time constant
Different criteria may be used for establishing the target slew rate of the hot swap circuit on
powerup. However, one overriding requirement is that the input current must be allowed to attain
a minimum value prior to the voltage across the input capacitance achieving the UVLO
threshold. This minimum level is the current that is demanded by the load. In this case, it is the
startup current of the two converters. If the minimum current is not obtained, the active load will
begin discharging the input capacitance (C5 and C7 in this case). Some amount of voltage
droop may be tolerated by the load, but that is dictated by the complexity and hysteresis of the
UVLO circuitry. As a general guideline, be sure to provide sufficient current to avoid any voltage
droop. This target current, or set current, is referred to as ISET in the following paragraphs.
To simplify what easily becomes a complicated math exercise, assume that the load startup
current is constant, or iL(t) = IL. To further simplify, assume that this constant value is in fact the
value previously calculated for the peak operating current, or IIN(max). For this example, the
minimum current required at load startup, ISET, is set to 5% over this value, or
ISET +1.05 IIN(max) +1.208 A
(18)
(19)
(20)
SLUA250
15
A Power Management Interface Circuit for Telecom Hot Swap with Local DC/DC Conversion
Given the voltage ramp profile of equation 19, what is the value of C3 which will ramp the input
current to at least ISET by the time the voltage reaches the UVLO threshold? By solving
equation 18 for the time t when iIN(t) = ISET, plugging this expression into Eq. 19, and solving for
the C3 term, equation 21 is derived.
C3 +*VUV
ȧ
ȱ
ȲǒR2
CLOADǓ ǒISET )IMAX ȏnǒ1*ISET
IMAXǓǓȧ
ȳ
ȴ
Examination of equation 18 reveals that the slowest current ramp occurs under minimum
sourcing conditions. Substituting IMAXMIN for IMAX in equation 21, and using the minimum
specified UVLO threshold (31 V), yields C3 = 2.09 µF. Because of the criteria used to establish
equation 21, the 2.09-µF value represents essentially the maximum size capacitor that should
be used in this solution.
To demonstrate an alternative, assume that a maximum slew rate requirement of 0.5 A per msec
is included in the design specification. The value of the soft-start capacitor, C3, for a given slew
rate can be found by taking the derivative of the input current during the startup voltage ramp,
given by equation 18. The result is equation 22 .
di
dt +IMAX
TSS eǒ*t
TSSǓ
Setting di/dt for t = 0 to the maximum slew rate spec, and substituting IMAXMAX for IMAX yields:
C3 +IMAXMAX
ǒR2 ǒdińdt)MAXǓ+0.934 mF
As shown in the schematic, a value of 1.0 µF was used.
2.3.5 Step 5 Estimating Ramp TIme
The minimum delay to a fault timeout must be long enough to allow charging of the input
capacitance at startup. Therefore, an estimate of the total voltage ramp time at module startup is
needed. An empirical approach can be taken by bench-testing the interface circuit with the load
connected, and measuring the time for the converter input voltage to ramp to the DC input
potential. To do this, the fault timer can be defeated by temporarily installing a resistor with a
value 1 kin place of capacitor C2. Alternatively, the analysis detailed in this section can be
used to better predict the worst-case timing.
For the analysis, two possible scenarios exist.
1. Either soft-start is not used, or soft-start reset switch Q2 is not used. For this case, the
output voltage equations 16 and 17 apply.
2. Output soft-start is used. The required delay is given by the tCTSS calculation shown in the
discussion after Figure 5.
For case 1, the HSPM IC operates in fault mode immediately from turn-on, and the
minimum delay needed is the total start time. This is given by equations 24 and 25.
(21)
(22)
(23)
SLUA250
16 A Power Management Interface Circuit for Telecom Hot Swap with Local DC/DC Conversion
tCT +tST1X +CLOAD ǒnINA1(t) *VUVǓ
IMAXMIN *IL)tVUVX
where:
tVUVX +CLOAD ǒVUV *0Ǔ
IMAXMIN
Solve tCT for VINA1(t) = VIN(max) and VUV = VUV(min).
For case 2, soft-start, equation 19 determines the time required to reach the UVLO threshold,
designated here as tVUV. Through repeated sampling of the voltage equation, the following
values were determined:
tVUVX = 6.89 ms, the time for VIN(t) to reach VUV when IMAX = IMAXMIN
tVUVM = 5.51 ms, the time for VIN(t) to reach VUV when IMAX = IMAXMAX
To approximate the worst case startup time, the minimum UVLO threshold of the converters,
31 V, was used as the target voltage level. Due to the tedious nature of sampling the voltage
waveforms at different times, it may be useful to create a spreadsheet or use some other
software tool to generate a table of values while sweeping the time variable.
At time t = tVUV, the load starts up. This defines the transition point between the two equations
for the input profile. The second stage of the ramp-up, from VIN(t) = VUV to the dc input level, is
given by:
nINA(t) +ƪTSS
CLOADƫ
ȧ
ȱ
Ȳ
ȧ
ȡ
ȢIMAX eǒ*t
TSSǓ)ǒIMAX *iL(t)Ǔ t
TSS ȧ
ȣ
Ȥ*ȧ
ȡ
ȢIMAX eǒ*tVUV
TSS Ǔ)ǒIMAX *iL(t)Ǔ tVUV
TSS ȧ
ȣ
Ȥ
ȧ
ȳ
ȴ)
nINUǒtVUVǓ
Figures 3 through 5 show a graphic representation of the input current and voltage waveforms
during the transient ramp-up. Plots were produced for sourcing current limit, IMAX, at the
nominal, minimum and maximum levels.
(24)
(25)
(26)
SLUA250
17
A Power Management Interface Circuit for Telecom Hot Swap with Local DC/DC Conversion
Figure 3. ISR Input Voltage and Current
IMAXMAX Condition
01224 6 810
0
10
20
30
40
50
60
3.0
2.5
2.0
1.5
1.0
0.5
0.0
t Time ms
IMAX(t)
VMAX(t)
Figure 4. ISR Input Voltage and Current
IMAXNOM Condition
3.0
2.5
2.0
1.5
1.0
0.5
0.0 01224 6 810
0
10
20
30
40
50
60
t Time ms
INOM(t)
VNOM(t)
Figure 5. ISR Input Voltage and Current
IMAXMIN Condition
01224 6 810
0
10
20
30
40
50
60
3.0
2.5
2.0
1.5
1.0
0.5
0.0
t Time ms
IMIN(t)
VMIN(t)
The selection of a minimum value for the fault timing capacitor, C2, is described in more detail in
Section 2.3.7. Since input current greater than the fault level may occur during the turn-on
transient, the time delay generated by C2 must be sufficient to allow charging of the input
capacitance after plug-in insertion or remote turn on. Therefore, the total duration of the turn-on
transient must be known. However, the internal fault timer is not started until the current fault
threshold is crossed, so the time for charging current to ramp to the minimum (i.e., worst-case)
fault threshold must also be determined. Ultimately, it is the maximum time difference, for a
given IMAX value, from fault threshold to the total startup time, which dictates the value of C2.
SLUA250
18 A Power Management Interface Circuit for Telecom Hot Swap with Local DC/DC Conversion
Inspection of equation 18 for iIN(t) indicates that the current ramp is independent of the supply
voltage, but is directly proportional to the IMAX level of the particular module. So the extremes of
the fault timing are determined by rewriting equation 18 to determine the time to reach the
IFLT(min) under both the IMAXMIN and IMAXMAX conditions.
tFLT +*R2 C3 ȏnǒ1*IFLT(min)
IMAX Ǔ
and
tFLT(min) = 4.695 ms, the fault time when IMAX = IMAXMAX
tFLT(max) = 7.956 ms, the fault time when IMAX = IMAXMIN
These values were calculated with the 1.84 A minimum fault current determined in Section 2.3.2.
The total duration of the ramp time must also be estimated. From the startup plots of Figures 3
through 5, it is almost intuitive that this value not only depends on the IMAX tolerance, but is
also a function of the UVLO threshold and the input supply level. These voltage curves show
that an earlier load turn-on, and a higher voltage to charge to extend the total voltage ramp time.
Therefore, in order to use equation 26 to determine the total startup times (tSTM and tSTX), some
definitions are needed. First, the worst-case start time calculations should be performed for the
maximum input potential, in this case, 72 Vdc. Secondly, the load is assumed to be a constant
at the peak input current. But since the bus potential is at its maximum, the current calculated for
a 72 Vdc input will be used, or iL(t) = IIN(max ). Lastly, we will define a target DC voltage to be
100mV below the input DC level, or 71.9 V.
By sampling equation 26, first setting tVUV = tVUVM while IMAX = IMAXMAX, then for tVUV = tVUVX
when IMAX = IMAXMIN, the following startup times were determined:
For t = 12.78 ms, VINA(t) = 71.846 V (tSTX; IMAXMIN condition)
For t = 9.72 ms, VINA(t) = 71.892 V (tSTM; IMAXMAX condition)
The maximum time delay needed to guarantee hot-swap startup when using soft-start, tCTSS, is
calculated as:
tCTSS = MAX[ (tSTX tFLT(MAX)), ( tSTM tFLT(MIN)) ]
= 9.72 ms 4.695 ms = 5.025 ms
It is interesting to note that, at least for this solution, the maximum timeout needed occurs under
the IMAXMAX condition.
Consider one final point regarding soft-start operation. Once capacitor C3 has charged up to its
dc level, it will remain charged as long as the board is powered. This means that soft-start
operation occurs only at insertion, and is disabled under any other conditions of turn-on,
including restart under the fault retry mode of operation, and also from a remote enable using
the SD input. Transistor Q2 is added to the circuit to provide a discharge path for C3 whenever
the output is turned off. The gate of Q2 is driven by the SDFL node, so that Q2 is turned on
whenever U1 asserts the fault output, or SDFL is pulled high externally. The soft-start reset
action of Q2 ensures that the HSPM soft-starts each time the output is turned on.
(27)
SLUA250
19
A Power Management Interface Circuit for Telecom Hot Swap with Local DC/DC Conversion
2.3.6 Step 6 Set Average Power Limiting For Pass Fet; Determine Power Limiting
Resistor Value, R7
The UCC3921 can be configured for either of the two modes of operation during fault conditions,
latched mode or retry mode.
In retry mode, the device periodically turns on the FET switch Q1 and checks for continued fault
conditions. Timing control of this mode is automatically provided by the device. During retry
operation, U1 alternately charges C2 with a nominal 36-µA internal constant-current source
while Q1 is on, then discharges C2 at a nominal 1 µA while the output is off. This provides a
nominal 2.7% duty cycle. To select retry mode, resistor R4 in the Figure 1 schematic would not
be used (left open).
In latched mode, once a fault condition times out, the device latches off the pass element. In
order to restart the output, either the SDFL pin must be pulled to the shutdown level for > 1 ms,
or device power must be cycled. To select latched operation, install resistor R4 as shown. In this
mode, the need for power dissipation limiting is essentially negated; therefore, R7 would not be
installed.
When using the retry feature of the UCC3921, care must be taken not to exceed the dissipation
capability of the FET switch. Under normal (non-fault) operating conditions, the FET is fully
enhanced by the gate drive, and dissipation in the device is relatively low, assuming an
appropriate device has been selected for the application parameters. However, under
short-circuit conditions, the full-input potential appears across Q1 while it is on. The power limit
function gives the user a means of externally limiting the duty cycle of the external FET
switching, further reducing it below the nominal 2.7% level. This is done by sensing the output
voltage level, and providing additional charging current for the timing capacitor, through a
high-value resistor, based on the output level relative to the VSS node of the device, (i.e., the
voltage drop across the FET switch.) The total current now available for charging the timing
capacitor, IQ, is now given by equation 28.
IQ+Iq)IPL
where:
Iq = the device internal charging source, 36-µA nominal
IPL = the current through the power limiting resistor
In Figure 1, R7, connected to the drain of Q1, is the power limiting resistor.
The IRF630 FET selected for this solution comes in the TO220AB package, rated for a 62_C/W
thermal resistance, junction to ambient. Maximum operating junction temperature is specified as
150_C. For the 70_C ambient operating temperature specified in Section 1.2, the average
dissipation in Q1 will be limited to 1.0 W as a conservative level. The maximum allowable duty
cycle, D, can then be derived from equation 29:
D+PD(avg)
IMAXMAX VIN(max) [0.23%
Since this is significantly less than the HSPM guaranteed maximum of 3.7%, the power limiting
function will be used. Because 1/D >> 1, a good approximation of the timing capacitor
charge-current contribution required through R7 (IPL in equation 28) is obtained from
equation 30:
(28)
(29)
SLUA250
20 A Power Management Interface Circuit for Telecom Hot Swap with Local DC/DC Conversion
IPL +Idq(max)
D*Iq(min)
where:
Idq(MAX) = maximum capacitor discharge current into the U1 CT pin
Iq(MIN) = the minimum charging current sourced from CT
Substituting the values from the UCC3921 data sheet for Idq(max) and Iq(min) ,the required power
limiting current is determined to be about 634 µA. The value of R7 is then found from
equation 31:
R7 +VIN *VPLIM
IPL
The obvious worst-case dissipation in the FET occurs when input voltage and drain output
current are at their maximum. Therefore, the value of 72 V is substituted for VIN, and the
calculated value for R7 is:
R7 +72 V *5.0 V
634 mA+105.7 kW
A standard 5% value suffices for this function. R7 is set to 100 k.
2.3.7 Step 7 Determine value for fault timing capacitor C2
The power-limiting current required, and subsequently the value of R7, are determined under
worst-case dissipation conditions (e.g., a short-circuit across the input capacitors). However,
during a normal startup voltage ramp, input voltage to the ISRs is not shorted, but ramps up
according to the appropriate equations. Therefore, the timing current IPL is not a constant under
these conditions, but decreases over the period of the input ramp from a maximum value of
ǒVIN *VPLIMǓ
R7 .
Approximating the input transient as a linear ramp, the average current through R7 is estimated
from equation 33.
IPL(avg) +ǒVDC *VPLIMǓ
2 R7 +ǒVIN(max) *VPLIMǓ
2 R7
Therefore, the minimum value of capacitor C2 needed to ensure startup of the output is:
C2 +ƪIq(max) )IPL(avg)ƫ tCT
dVCT
where:
Iq(max) = maximum charging current sourced from CT
tCT = required fault time delay
dVCT = the delta-V that must be developed across C2 for the UCC3921 to detect a fault
(30)
(31)
(32)
(33)
(34)
SLUA250
21
A Power Management Interface Circuit for Telecom Hot Swap with Local DC/DC Conversion
From the device data sheet, the minimum fault threshold at the CT input pin is given as 2.20 V,
and the maximum level for fault reset is 0.57 V. However, for latched mode of operation, only the
initial fault timeout is of concern, in which case the voltage at CT is ramping up from 0 V. This
allows selection of a slightly smaller value for C2 than if retry mode is used, as shown in
equations 35 and 36.
For retry mode:
C2 +ƪIq(max) )IPL(avg)ƫ tCT
ǒVLS *VLRǓ
where:
VLS = the internal fault latch SET threshold
VLR = the internal fault latch RESET threshold
For latched mode:
C2 +ƪIq(max) )IPL(avg)ƫ tCT
VLS
Since the proposed solution makes use of input current slewing, the tCTSS value calculated in
Section 2.3.5 Step 5 – Estimating Ramp TIme is used. Substituting tCT = tCTSS 5 ms, the calculated
value of C2 is about 0.88 µF, and a standard value of 1.0 µF was used in the solution.
2.3.8 Step 8. Set resistor R3 value
Resistor R3 is the supply biasing resistor for the UCC3921. The maximum supply current
required by the HSPM IC to maintain the internal-shunt-regulator voltage within the data sheet
specifications is 2.0 mA. A value of 2.5 mA was used in the development of this solution to
provide some margin and bias the IMAX divider network when the supply voltage is at its
minimum potential. To provide this minimum bias current, the value of R3 is defined by:
R3 +ǒVIN *VREFǓ
0.0025
So, the maximum allowable value of R3 is provided by:
R3 +ǒVIN(min) *VREF(max)Ǔ
0.0025 +36 V *10.15 V
0.0025 A ^10 kW
At maximum bus potential conditions (72 V), about 6.64 mA of current could flow through R3
(assuming a 5% tolerance resistor); which is well below the specification maximum of 50 mA.
Also, this corresponds to a maximum power dissipation of about 420 mW; therefore, a 1-W-rated
resistor is used in this application.
3 Additional Features
The design of the basic power management interface is now complete. The main functions of
hot swapping the 48-Vdc input and converting it to local VDD levels is accomplished through
the circuitry described previously. However, there are some additional features which can be
easily implemented. Two of these functions, which see frequent usage in power management,
are presented in the following sections. First, this report describes a host interface to provide a
remote shutdown/enable input (SD) and fault indication to the system. Secondly, an inexpensive
circuit is shown for shifting the UVLO threshold of the PT332x module.
(35)
(36)
(37)
(38)
SLUA250
22 A Power Management Interface Circuit for Telecom Hot Swap with Local DC/DC Conversion
3.1 Host Interface to SDFL Pin
Pin 1 of the UCC3921 is a three-function pin. The use of a resistive pull-down at this pin to
select the fault mode of operation is described in Section 2.3.6, Step 6 Set Average Power
Limiting For Pass Fet; Determine Power Limiting Resistor Value, R7. This pin is also an active-high
input for turning off the external FET (shutdown), and provides an output fault indication.
However, the signal levels at this pin are referred to the VSS node of the circuit (i.e., the VSS pin
of U1). An interface circuit is needed to translate these signals to a system ground reference,
and generate the FLT output and the SD input, as shown in the top level schematic. Figure 6 is
the Figure 1 diagram redrawn to show the details of one interface implementation.
UDG00143
C1 0.1µF
C2 1.0 µF
R1
1.0 M
1%
R4
82 k
R2
13 k
1%
C3
1.0 µ F
R3
10 k, 1 W
R5
0.025
1 W, 1%
D1
MBR3100
F1
3 AG, 2 A
D2
MBR3100
F2
3 AG, 2 A
R7
100 k
C5
100 µF
100 V
C6
330 µF
6.3 V
48VDC_N1
48VDC_N2
U1
Q2
2N7000
Q1
IRF530
1
2
3
45
6
7
8
SDFL
IMAX
VDD
CT VSS
SNS
OUT
PL
UCC3921
R13
0
VIN+
VIN+
VIN+
VIN
VIN
VIN
INH
N/C
N/C
+SNS
VOUT+
VOUT+
VOUT+
VOUT+
VOUT
VOUT
VOUT
SNS
ADJ
PT3325
7
8
9
2
1
3
4
5
6
19
17
16
15
14
18
12
11
10
13
VIN+
VIN+
VIN+
VIN
VIN
VIN
INH
N/C
N/C
+SNS
VOUT+
VOUT+
VOUT+
VOUT+
VOUT
VOUT
VOUT
SNS
ADJ
PT3326
7
8
9
2
1
3
4
5
6
19
17
16
15
14
18
12
11
10
13
C8
330 µF
6.3 V
C7
100 µF
100 V
U2
U3
+1.8VDC
+2.5VDC
LCLRTN
R17
0
UVLO
VIN
GND
SD
FLT
HOST_VDD R12
62 k
R10
10 k
R11
270 k
R8
10 kD3
1N4148
R9
120 k
Q5
ZVN3310A
Q4
ZTX553
Q3
ZVP3310A
Figure 6. Schematic Diagram with Host Interface Details
The FAULT output translation is comprised of the circuit of R8, R9 and Q5. Under normal
operating conditions, U1 sinks a nominal 100 µA at pin 1. This keeps the gate of Q5 discharged.
With Q5 turned off, R8 applies a pull-up to the HOST_VDD potential at the FLT output, indicating
normal operation.
During any condition that causes the HSPM device to turn off the gate drive to the FET Q1, the
SDFL output attempts to drive to the UCC3921 VDD rail. Device Q5 turns on, and R8 and R9
form a divider on the HOST_VDD to VSS potential. From the divider equation for the fault signal
level, the following equation for R9 is derived.
R9 +VFLT#
ǒHVDD *VSS *VFLT#Ǔ R8 (39)
SLUA250
23
A Power Management Interface Circuit for Telecom Hot Swap with Local DC/DC Conversion
where:
VFLT# = the voltage level of the FLT signal line
HVDD = the voltage level of the system HOST_VDD supply
VSS = the VSS node potential of the plug-in module
If the maximum assertion level of FLT, VFLT#(max), is defined to be 0.5 V maximum, then:
VFLT#(max) +0.5 V +0.5 V *ǒ*VSS(min)Ǔ+36.2 V ,
when referenced to the module VSS node, and allowing for about a 300-mV drop across the
Schottkys and fuses when the load is not powered. For this condition, the maximum value that
should be used in the R9 position is given by equation 41.
R9(max) +VFLT#(max)
ǒHVDD *VSS(min) *VFLT#(max)Ǔ R8
Substituting the system values into equation 41, and setting R8 to a nominal 10 k, the resulting
R9 value is:
R9 +36.2 V
[3.3 V *(*35.7 V)*36.2 V] 10 kW^129 kW
The next lowest 5% value of 120 k was used for R9. Now, the minimum voltage level for fault
assertion can be determined from:
VFLT#(min) +ƪǒR9
(R8 )R9)Ǔ ǒHVDD *VSS(max)Ǔƫ)VSS(max)
+ƪǒ120 kW
130 kWǓ (3.3 V )72 V)ƫ*72V ^*2.5V
Due to the possibly large signal level below the host or system ground potential, small-signal
diode D3 is used as shown in the schematic to clamp the assertion level at about 0.5 V below
the GND node.
The interface block of circuitry must also provide level-shift of the host shutdown or enable input,
SD in the schematic. A brief description of the circuit operation follows.
To turn on the HSPM output, the SD input is pulled high by the host controller. Since the Q3 gate
is tied to the system GND node, Q3 turns on and provides a strong pull-up on the base of
transistor Q4, above the emitter potential. With Q4 off, the internal pull-down at U1 pin 1 is
dominant, and the output pulls to a low state. This enables the hot swap controller to turn on the
pass FET Q1.
When shutdown is asserted (SD pulls low), FET Q3 turns off. Resistor R11 can now pull the Q4
base towards VSS, and Q4 turns on. Q4 now sources sufficient current from the GND potential to
overcome the internal pull-down, pulling pin 1 above the shutdown input threshold. The HSPM
IC subsequently turns off Q1.
(40)
(41)
(42)
(43)
SLUA250
24 A Power Management Interface Circuit for Telecom Hot Swap with Local DC/DC Conversion
The use of the two-transistor (Q3/Q4) level shifter as shown in figure 6 provides an additional
feature. If at some point the host VDD supply fails while the controlled module is plugged in, the
module outputs will be automatically disabled via the HSPM circuit. Loss of the host supply
would mean loss of the SD drive to the Q3 source, turning off P-FET Q3. Since the Q4 emitter is
tied to the GND node, as opposed to a backplane-side input signal, Q4 is still able to source
shutdown current into the SDFL pin.
A quick methodology is given here to determine recommended values for resistors R11 and
R12. Per the device specification, the SDFL input has a maximum shutdown threshold of
(VDD + 1) V. In addition, this pin may sink a maximum of 250 µA. Therefore, R11 and R12 must
be selected to ensure that PNP transistor Q4 can source a minimum of 250 µA while pulling the
pin high.
Under minimum input supply conditions, the drop across limiting resistor R12 is given by:
VR12(min) +*VSS(min) *VEC(max) *VSD(max)
Set up this level translator to keep Q4 in saturation under minimum supply conditions. For the
ZTX553 transistor, the maximum VCE is specified as 250 mV at a gain of 10. The drop across
R12 is:
VR12(min) +35.5 V *0.25 V *11 V +24.25 V
Under the same conditions the current consumed by latching resistor R4 is
IR4(max) +VSD(max)
R4MIN ^141 mA (assuming a 5% tolerance resistor is used). Therefore, the
maximum value of R12 that can ensure shutdown control is determined by equation 46.
R12(max) +VR12(min)
ǒIR4(max) )ISD(max)Ǔ+62 kW
The drive current that will be needed, and the value for R11 to provide that current can be found
from the following.
IB(Q4) uVR12(min)
[R12(max) 10]+24.25 V
[(1.05 R12) 10]^37 mA
and,
R11 tƪ*VR12(min) *0.6V *ǒ*VSS(min)Ǔƫ
IB(Q4)
+[*24.25 V *0.6 V *(*35.5 V)]
37 mA^288 kW
The closest available 5% tolerance value is 270 k.
(44)
(45)
(46)
(47)
(48)
SLUA250
25
A Power Management Interface Circuit for Telecom Hot Swap with Local DC/DC Conversion
3.2 Alternate Host Interface
The interface circuit described in Section 3.1 (Figure 6) would be useful when the ON/OFF
control-electronics biasing supply (the HOST_VDD input) and the control lines are referenced to
the GND node. This is also the return line for the two 48 V power busses. However, in a truly
isolated system, logic supply returns would not have a common connection with the power
section. Therefore, Figure 7 illustrates an optional interface configuration to maintain isolation
from the power bus.
In the Figure 7 circuit, the return of the two DC/DC converters (LCLRTN) is used as the
reference for the I/O signals (SD and FLT). Opto-couplers maintain isolation from the primary
side. The pull-up on the FLT line is shown on the plug-in schematic to provide extra detail.
However, this pull-up can just as easily be located in the control module or board, eliminating the
need for bussing the HOST_VDD to the controlled slot altogether.
UDG00147
270 k
4N29
62 k
43 k
1
1 k
2
5
4ZTX553
4N29
1
2
5
4
ZTX453
10 k
TO U1 SDFL
TO U1 VSS
10 k
SD
HOST_VDD
FLT
LCLRTN
Figure 7. Alternate Host/System Interface for Isolated Controller
3.3 Optional UVLO Circuit
The solution developed through the steps of Section 2.3, Circuit Design Procedure, assumes
that the internal UVLO circuit of the PT3320 regulators is used. However, during a live insertion,
any current consumed by the load, in this case, the two ISRs, is not available for charging up the
input capacitance (C5 and C7). For a given maximum current-sourcing level, as controlled by
the UCC3921, faster charging of this load capacitance can be achieved when the source does
not have to also supply the regulators and secondary-side load. Therefore, when the operating
input supply range allows, or if using different converters, or where large input capacitance
exists, it may be desirable to keep the load disabled until the input voltage has achieved a higher
potential. One way of doing this is to shift the threshold of the UVLO function upward.
SLUA250
26 A Power Management Interface Circuit for Telecom Hot Swap with Local DC/DC Conversion
The Figure 8 schematic shows the details of an undervoltage lockout sub-circuit achieved with a
few discrete components. The circuit is driven by the supply voltage across the VIN terminals of
U2 and U3. During the input ramp-up transient, diode D4 keeps transistor Q6 off until its
breakdown voltage is exceeded. R16 is then able to bias Q7 on, which pulls the converter INH
pins to the VIN potential. This keeps the converter outputs off.
Once the converter input voltage exceeds the D4 Zener threshold, D4 conducts, turning on Q6.
Q6 acts to pull the Q7 base low, which turns Q7 off. The inhibit control circuitry of the PT3320
modules features a nominal 10-µA pull-up. With external transistor Q7 presenting a high
impedance, the INH input is internally pulled high, above the enable threshold of 2.5 V, and the
converters start up. Using the 39-V Zener diode as shown in the schematic should provide a
UVLO function of 39 V to 41 V.
UDG00146
C1 0.1µF
C2 1.0 µF
R1
1.0 M
1%
R4
82 k
R2
13 k
1%
C3
1.0 µ F
R3
10 k, 1 W
R5
0.025
1 W, 1%
D1
MBR3100
F1
3 AG, 2 A
D2
MBR3100
F2
3 AG, 2 A
R7
100 k
C5
100 µF
100 V C6
330 µF
6.3 V
GND
SD
FLT
HOST_VDD
U1
Q2
2N7000
Q1
IRF530
1
2
3
45
6
7
8
SDFL
IMAX
VDD
CT VSS
SNS
OUT
PL
UCC3921
R13
0
VIN+
VIN+
VIN+
VIN
VIN
VIN
INH
N/C
N/C
+SNS
VOUT+
VOUT+
VOUT+
VOUT+
VOUT
VOUT
VOUT
SNS
ADJ
PT3325
7
8
9
2
1
3
4
5
6
19
17
16
15
14
18
12
11
10
13
VIN+
VIN+
VIN+
VIN
VIN
VIN
INH
N/C
N/C
+SNS
VOUT+
VOUT+
VOUT+
VOUT+
VOUT
VOUT
VOUT
SNS
ADJ
PT3326
7
8
9
2
1
3
4
5
6
19
17
16
15
14
18
12
11
10
13
C8
330 µF
6.3 V
C7
100 µF
100 V
U2
U3
LCLRTN
R17
0
VIN
Q7
ZTX453
R16
510 k
Q6
ZTX453
R12
R15
10 k
R14
10 k
D4
1N5259B
39 V
Q4
ZTX553
R10
10 k
R11
270 k
R8
10 kD3
1N4148
R9
120 k
Q5
ZVN3310A
+1.8VDC
+2.5VDC
48VDC_N1
48VDC_N2
Q3
ZVP3310A
62k
Figure 8. Complete Detailed Application Circuit
4 Performance Evaluation and Sample Waveforms
The oscilloscope plots presented in this section demonstrate the operation of the circuit shown
in Figure 8. To obtain these figures, the external UVLO circuit was disabled, so that the DC/DC
turn-on is controlled by the on-board UVLO circuit. The HOST_VDD supply was set to a nominal
3.3 V. Unless stated otherwise, the ISR outputs were each loaded at 6.0 A. Generally, the scope
channel connections in the plot labels refer to the node names in any of the preceding
schematics; IIN refers to input current into the plug-in module.
SLUA250
27
A Power Management Interface Circuit for Telecom Hot Swap with Local DC/DC Conversion
Figure 9 shows the input voltage ramp-up and output turn-on following a live insertion event,
with the supply voltage at 48 Vdc. In Figures 9 and 10, hot swap was performed with the
48VDC_N1 making last. Both figures demonstrate the smooth ramp of the converter input
voltage, (i.e., the voltage across filter capacitors C5 and C7) Figure 10 shows the nearly linear
ramp of the inrush current during the voltage ramp. Of particular interest is that the startup delay
of the converters (from VIN reaching the UVLO threshold) is such that the outputs do not ramp
until after the input ramp is complete.
Figure 9. Hot-Swap Startup Sequence
500 mA
48VDC_N1
50 V/div
VIN
20 V/div
1.8VDC OUT
2 V/div
2.5VDC OUT
2 V/div
VIN = 48 Vdc
IMAXNOM
t Time 2.5 ms/div
48VDC_N1
50 V/div
VIN
20 V/div
IIN
1 A/div
t Time 2.5 ms/div
Figure 10. Hot-Swap Startup Input V/I Profile
SLUA250
28 A Power Management Interface Circuit for Telecom Hot Swap with Local DC/DC Conversion
Figures 11, 12, and 13 show the insertion waveforms for a 72 Vdc bus potential, for an HSPM
IC operating at the minimum, maximum and nominal sourcing current levels, respectively.
Figure 11. IMAXMIN Startup Waveforms
t Time 2.5 ms/div
VIN = 72 Vdc
IMAXMIN
48VDC_N1
50 V/div
VIN
50 V/div
IIN
1 A/div
48VDC_N1
50 V/div
VIN
50 V/div
IIN
1 A/div
Figure 12. IMAXMAX Startup Waveforms
t Time 2.5 ms/div
VIN = 72 Vdc
IMAXMAX
Figure 13. IMAXNOM Startup Waveforms
48VDC_N1
50 V/div
VIN
50 V/div
IIN
1 A/div
VIN = 72 Vdc
IMAXNOM
t Time 2.5 ms/div
Figure 12, at 72 Vdc input and IMAXMAX was generated under conditions closely representing
the worst-case scenario for starting up with a fully discharged plug-in (tCTSS determination in
Section 2.3.5 Step 5 Estimating Ramp TIme). The Figure 12 waveforms confirm that the module
starts up smoothly even under this condition. Also, it can be seen that at this input potential, with
the extension in rampup time, the turn-on of the two converter modules occurs during the input
ramp-up transient.
SLUA250
29
A Power Management Interface Circuit for Telecom Hot Swap with Local DC/DC Conversion
In order to verify some of the equations used in Section 2.3, Circuit Design Procedure, in
determining circuit component values, some theoretical input voltage ramp times and peak
inrush levels were calculated using equations 19 and 26, under some sample circuit conditions.
These start times and peak currents, shown in the Calculated columns in Table 3, were
determined for an HSPM IC operating at its nominal, minimum and maximum current limit
thresholds. A nominal ISR UVLO threshold of 33 Vdc was assumed. These values were then
checked against measurements obtained from the transient waveforms of Figures 9 through 13,
and similar plots. The results are summarized in Table 3.
Table 3. Startup Time and Peak Current Comparison
SUPPLY
VOLTAGE
TOTAL STARTUP TIME
(ms) PEAK CURRENT
(A) CONDITIONS
VOLTAGE
Calculated Measured Calculated Measured
CONDITIONS
8.825 7.85 2.403 2.26 IMAXNOM
48 Vdc 10.05 9.05 2.164 1.90 IMAXMIN
48
Vdc
7.67 7.15 2.705 2.48 IMAXMAX
11.13 10.70 2.805 2.66 IMAXNOM
72 Vdc 12.685 12.15 2.505 2.26 IMAXMIN
72
Vdc
9.66 9.30 3.183 3.0 IMAXMAX
Table 3 shows good correlation between the anticipated and actual startup times. In general, the
actual ramps were about 1 ms faster at the 48-Vdc input level. The primary factor for this is
most likely the delay in ISR output turnon, which means that the use of the maximum input
current estimates for IL(t) in equation 24 is overly conservative. For the 72-Vdc input case, the
start time estimates are only about 500 µs too high; not surprising because at this supply level,
the converters do start supplying the load currents prior to the end of the input voltage ramp.
The waveform graphics in Figures 14 and 15 demonstrate the startup from SD deassertion. For
the Figure 15 plot, the soft-start capacitor C3 was removed to show the transient current clamp
at the IMAX level. The nominal current limit obtained is the 4.8-A theoretical value. In addition,
the 48VDC_N1 traces demonstrate the extent of the disturbance on the supply bus. At
200 mV/div (Figure 15), the bus transients are only about +600/100 mV about the steady-state
level, even without inrush current slewing.
SLUA250
30 A Power Management Interface Circuit for Telecom Hot Swap with Local DC/DC Conversion
Figure 14. Startup from SD Deassertion
48VDC_N1
100 mV/div
VIN
50 V/div
IIN
1 A/div
VIN = 48 Vdc
IMAXNOM
CH1 ac Coupled
t Time 1 ms/div
Figure 15. Startup from SD No Soft-Start
48VDC_N1
200 mV/div
VIN
50 V/div
IIN
2 A/div
VIN = 48 Vdc
IMAXNOM
CH1 ac Coupled
t Time 500 s/div
Figure 16 shows another hot swap event at the 48-Vdc supply level, with the time base
expanded to view the inrush current ramp under softstart. Using the 10% and 90% points, the
average di/dt obtained with the circuit was determined to be:
(2.0 A *0.222 A)
6.52 ms ^0.27 A
ms .
Recall that capacitor C3 was selected in Step 4 for a maximum slew rate of 0.5 A per ms;
therefore, the average di/dt obtained is approximately half that value.
Figure 16. Slew Rate Calculation
48VDC_N1
50 V/div
VIN
20 V/div
IIN
1 A/div
VIN = 48 Vdc
IMAXNOM
t = 6.52 ms
t Time 1 ms/div
t10
t90
The waveforms in Figures 17 and 18 demonstrate the operation of the FLT output during startup
(Figure 17) and shut-down (Figure 18) sequences, when initiated from the SD input.
SLUA250
31
A Power Management Interface Circuit for Telecom Hot Swap with Local DC/DC Conversion
Figure 17. FLT Output Operation During Startup
SD
5 V/div
FLT
1 V/div
VIN
50 V/div
2.5VDC OUT
2 V/div
VIN = 48 Vdc
IMAXNOM
t Time 2.5 ms/div Figure 18.
FLT Output Operation During Shutdown
SD
5 V/div
FLT
1 V/div
VIN
50 V/div
2.5VDC OUT
2 V/div
VIN = 48 Vdc
IMAXNOM
t Time 100 ms/div
Figure 19 shows the circuit response should the HOST_VDD supply be removed or fail. As
desired, the pass FET is switched off, and the FLT output is asserted. The input voltage to the
ISRs decays in a manner dictated by the load characteristics. There is an initial step drop in
voltage, and then, when the input hits the UVLO threshold, the ISRs turn off, and the 200-µF
bulk capacitance is discharged by leakage only.
Figure 19. Shutdown for HOST_VDD Failure
HOST_VDD
5 V/div
1 V/div
VIN
20 V/div
VIN = 48 Vdc
t Time 100 ms/div
FLT
SLUA250
32 A Power Management Interface Circuit for Telecom Hot Swap with Local DC/DC Conversion
The next two scope plots show the circuits fault response to a short-circuit condition at the
DC/DC converter inputs. Figure 20 depicts initial normal steady-state operation with a 48 V dc
input supply and about an 800-mA load, from the IIN trace. With the sudden application of a
short (see VINtrace), the HSPM IC clamps the short-circuit current at approximately 4.8 A,
times out in about 6 ms, and ultimately latches the pass FET off. Figure 21 shows attempted
startup into a short across the VIN terminals of the converters. The input current slews up as
programmed, but no voltage develops across the converter inputs (VIN scale is 1V/div), and
the HSPM again times out and latches off. In this case, the total time-out is longer than that
shown in Figure 20. Recall that the fault timer does not start until the input current exceeds the
nominal 2-A overcurrent threshold.
Figure 20. Short-Circuit at Converter Inputs
VIN
20 V/div
5 V/div
IIN
2 A/div
VIN = 48 Vdc
IMAXNOM
t Time 1 ms/div
FLT
Figure 21. Startup into Shorted ISR Input
VIN
1 V/div
48VDC_N1
50 V/div
IIN
1 A/div
VIN = 48 Vdc
IMAXNOM
t Time 2.5 ms/div
The scope plots of Figures 22 and 23 demonstrate the short-circuit response of the PT3320
converters. In Figure 22, the module is initially operating steady-state with 48-V input, and a
6-A load on each of the ISR outputs. When a short-circuit is applied to the +1.8 Vdc output, the
converter shuts off, then periodically pulses on to test for a continued fault condition (IOUT trace).
Because of the voltage step-down, the input current peaks remain below the HSPM overcurrent
threshold, and the HSPM does not trigger. Because of this, the second output (+2.5 Vdc, not
shown), can continue to operate normally. Applying a short to the +2.5V output produces the
corresponding pulsed current response. Figure 23 is a plot of the same fault conditions, but with
the power bus at a 36 V potential.
SLUA250
33
A Power Management Interface Circuit for Telecom Hot Swap with Local DC/DC Conversion
Figure 22. Output Short-Circuit Response
(48-V Supply)
5 A/div
1.8VDC OUT
2 V/div
IIN
1 A/div
t Time 1 ms/div
IOUT 5 A/div
1.8VDC OUT
2 V/div
IIN
1 A/div
Figure 23. Output Short-Circuit Response
(36-V Supply)
t Time 1 ms/div
IOUT
5 Notes
1. The PT3327 module produces a nominal 1.8 Vdc output voltage. However, the PT332x
converters also provide for output voltage adjustment from 90% to 110% of nominal value
using an external resistor. Due to sample availability at the time of this study, the 2-V
PT3325 unit was used, with output adjustment to 1.8-V using R17 in the Figure 1
schematic.
2. Since only three of the available devices in the series are characterized in the data sheet,
the PT3321 curves were used as the closest available output voltage/current match to the
modules used in this solution.
6 References
1. UCC3921 Latchable Negative Floating Hot Swap Power Manager; Data Sheet; Texas
Instruments Literature No. SLUS207; March 1998
2. PT3320 Series 30Watt Isolated DC/DC Converter; Data Sheet; Texas Instruments Literature No.
SLTS018A; June 2000
3. Adjusting the Output Voltage of the Power Trends 30W Isolated DC/DC Converter Series,
Application Note; Texas Instruments Literature No. SLTS018A
4. Using the Inhibit Function of the Power Trends 30W Isolated DC/DC Converter Series,
Application Note; Texas Instruments Literature No. SLTS018A
5. ISR Input/Output Filters, Application Note; Texas Instruments Literature No. SLTA013A, June
2000
The UCC3921 device parameters used in this document are listed in the Table A1for quick
reference. To aid the user in determining the source of these values, the corresponding data
sheet parameter name is shown. For a complete listing of the UCC3921 specifications, the user
is referred to the device data sheet.
SLUA250
34 A Power Management Interface Circuit for Telecom Hot Swap with Local DC/DC Conversion
Table 4. UCC3921 Hot Swap Power Manager Device Parameters
PARAMETER DATA SHEET REF CONDITIONS VALUE UNIT DESCRIPTION
VFLT(MIN) Overcurrent Threshold Over Op. Temp 46 mV Minimum fault threshold (Overcurrent Comparator)
VFLT(MAX) Over Op. Temp 53.5 mV Maximum fault threshold (Overcurrent Comparator)
VREF(MIN) Regulator Voltage 9.0 V Minimum shunt regulator voltage
VREF(NOM) 9.5 V Nominal shunt regulator voltage
VREF(MAX) 10.15 V Maximum shunt regulator voltage
VOS Input Offset Voltage VIMAX = 100mV ±15 mV VOS of the Linear Current Amplifier (LCA)
VIMAX = 400 mV ±30 mV
IBIAS LCA Input Bias 500 nA Input bias current on the LCA
Iq(MIN) CT Charge Current IPL = 0 22 µA Minimum CT charge current (overcurrent condition)
Iq(MAX) IPL = 0 50 µA Maximum CT charge current (overcurrent condition)
Idq(MAX) CT Discharge Current 1.5 µA Maximum CT discharge current
VLS CT Fault Threshold 2.2 V Minimum Fault Comparator SET threshold
VLR CT Reset Threshold 0.57 V Maximum Fault Comparator RESET threshold
VPLIM VSENSE Regulator 5.0 V Voltage at PL pin (sink condition)
VSD(MAX) Shutdown Threshold VDD + 1 V Maximum shutdown threshold
ISD(MAX) Input Current, SDFLTCH 250 µA Maximum IIH at SDFL pin
IMPORTANT NOTICE
Texas Instruments and its subsidiaries (TI) reserve the right to make changes to their products or to discontinue
any product or service without notice, and advise customers to obtain the latest version of relevant information
to verify, before placing orders, that information being relied on is current and complete. All products are sold
subject to the terms and conditions of sale supplied at the time of order acknowledgment, including those
pertaining to warranty, patent infringement, and limitation of liability.
TI warrants performance of its products to the specifications applicable at the time of sale in accordance with
TIs standard warranty . T esting and other quality control techniques are utilized to the extent TI deems necessary
to support this warranty. Specific testing of all parameters of each device is not necessarily performed, except
those mandated by government requirements.
Customers are responsible for their applications using TI components.
In order to minimize risks associated with the customers applications, adequate design and operating
safeguards must be provided by the customer to minimize inherent or procedural hazards.
TI assumes no liability for applications assistance or customer product design. TI does not warrant or represent
that any license, either express or implied, is granted under any patent right, copyright, mask work right, or other
intellectual property right of TI covering or relating to any combination, machine, or process in which such
products or services might be or are used. TIs publication of information regarding any third partys products
or services does not constitute TIs approval, license, warranty or endorsement thereof.
Reproduction of information in TI data books or data sheets is permissible only if reproduction is without
alteration and is accompanied by all associated warranties, conditions, limitations and notices. Representation
or reproduction of this information with alteration voids all warranties provided for an associated TI product or
service, is an unfair and deceptive business practice, and TI is not responsible nor liable for any such use.
Resale of TIs products or services with
statements different from or beyond the parameters
stated by TI for
that product or service voids all express and any implied warranties for the associated TI product or service,
is an unfair and deceptive business practice, and TI is not responsible nor liable for any such use.
Also see: Standard Terms and Conditions of Sale for Semiconductor Products. www .ti.com/sc/docs/stdterms.htm
Mailing Address:
Texas Instruments
Post Office Box 655303
Dallas, Texas 75265
Copyright 2001, Texas Instruments Incorporated