SPECIFICATION
DR-60-5 DR-60-12 DR-60-15 DR-60-24
MODEL
DCVOLTAGE
RATEDCURRENT
CURRENTRANGE
RATEDPOWER
OUTPUT VOLTAGE ADJ.RANGE
LINEREGULATION
LOADREGULATION
SETUP,RISETIME
HOLDUP TIME (Typ.)
VOLTAGERANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
ACCURRENT (Typ.)
INPUT
INRUSHCURRENT (Typ.)
SAFETY STANDARDS
HARMONICCURRENT
EMSIMMUNITY
WORKINGHUMIDITY
WORKINGTEMP.
STORAGETEMP.,HUMIDITY
TEMP.COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD
OVERVOLTAGE
5V 12V 15V 24V
6.5A 4.5A 4A 2.5A
0~6.5A 0~4.5A 0~4A 0~2.5A
32.5W 54W 60W 60W
80mVp-p 120mVp-p 120mVp-p
13.5~16.5V
150mVp-p
21.6~26.4V
2.0% 1.0% 1.0% 1.0%
11.1~13.2V4.75~5.5V
1.0% 1.0% 1.0% 1.0%
1.0% 1.0% 1.0% 1.0%
100ms,30ms/230VAC200ms,30ms/115VAC atfullload
100ms/230VAC23ms/115VAC atfullload
88~264VAC124~370VDC
47~63Hz
76% 82% 83% 84%
1.2A/115VAC0.8A/230VAC
COLDSTART 18A/115VAC36A/230VAC
105~160% ratedoutputpower
Protectiontype: Constantcurrentlimiting,recoversautomaticallyafterfaultconditionisremoved
5.75~6.75V
Protectiontype:Shutdowno/pvoltage,re-powerontorecover
13.8~16.2V 17.25~20.25V 27.6~32.4V
-20~+60 (Refertooutputloadderatingcurve)
20~90%RHnon-condensing
-40~+85 ,10~95%RH
0.03%/ (0~50
10~500Hz,2G10min./1cycle,periodfor60min. eachalongX, Y,Zaxes;Mounting:CompliancetoIEC60068-2-6
216.2Khrsmin.MIL-HDBK-217F(25 )
78*93*56mm(W*H*D)
0.3Kg;48pcs/15.4Kg/1.02CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
FileName:DR-60-SPEC2008-04-07
CompliancetoEN55011,EN55022(CISPR22)ClassB
Complianceto EN61000-3-2,-3
CompliancetoEN61000-4-2,3,4,5,6,8,11,ENV50204,EN55024,EN61000-6-2,EN61204-3,heavyindustrylevel,criteria A
60WSingleOutputIndustrialDINRailPowerSupply DR-60 series
Universal AC input/Full range
Protections: Short circuit / Overload / Over voltage
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
UL 508(industrial control equipment)approved
Isolation class
LED indicator for power on
100% full load burn-in test
3 years warranty
Features :
RIPPLE&NOISE(max.) Note.2
VOLTAGETOLERANCE Note.3
ENVIRONMENT
PROTECTION
SAFETY &
EMC
(Note4)
WITHSTANDVOLTAGE
ISOLATIONRESISTANCE
EMICONDUCTION&RADIATION
I/P-O/P:3KVAC
I/P-O/P:100MOhms/500VDC
UL60950-1, TUVEN60950-1a EN50178pproved,Designreferto