Current Transducer HAIS 50..400-P
and HAIS 50..100-TP
For the electronic measurement of currents : DC, AC, pulsed, mixed,
with a galvanic isolation between the primary circuit (high power)
and the secondary circuit (electronic circuit).
All Data are given with a RL = 10 k
Electrical data
Primary nominal Primary current, Type RoHS since
current rms measuring range date code
IPN (A) IPM (A)
50 ± 150 HAIS 50-P, HAIS 50-TP1) 45231, 46272
100 ± 300 HAIS 100-P, HAIS 100-TP1) 45231, 46012
150 ± 450 HAIS 150-P 46172
200 ± 600 HAIS 200-P 45231
400 ± 600 HAIS 400-P planned
VOUT Output voltage (Analog) @ IPVREF ± (0.625·IP/IPN)V
IP = 0 VREF ± 0.025 V
VREF Reference voltage 2) - Output voltage 2.5 ± 0.025 V
VREF Output impedance typ. 200
VREF Load impedance 200 k
R L Load resistance 2 k
ROUT Output internal resistance < 10
CLCapacitive loading < 1µF
VCSupply voltage (± 5 %) 5V
ICCurrent consumption @ VC = 5 V 22 mA
Accuracy - Dynamic performance data
XAccuracy 3) @ IPN , TA = 25°C ± 1 % of IPN
εLLinearity error 0 .. 3 x IPN ± 0.5 % of IPN
TCVOE Temperature coefficient of VOE @ IP = 0 ± 0.3 mV/K
TCVREF Temperature coefficient of VREF ± 0.01 %/K
TCVOUT / VREF Temperature coefficient of VOUT / VREF @ IP = 0 ± 0.2 mV/K
TCVOUT Temperature coefficient of VOUT ± 0.05% of reading/K
VOM Magnetic offset voltage @ IP = 0,
after an overload of 3 x IPN DC < ± 0.4 % of IPN
tra Reaction time @ 10 % of IPN < 3 µs
trResponse time to 90 % of IPN step < 5 µs
di/dt di/dt accurately followed > 100 A/µs
Vno Output voltage noise (DC ..10 kHz) < 15 mVpp
(DC .. 1 MHz) < 40 mVpp
BW Frequency bandwidth (-3 dB) 4) DC .. 50 kHz
Features
Hall effect measuring principle
Galvanic isolation between primary
and secondary circuit
Isolation test voltage 2500V
Low power consumption
Single power supply +5V
Fixed offset & gain
Bus bar version available for 50A and
100A ratings.
Isolated plastic case recognized
according to UL94-V0.
Advantages
Small size and space saving
Only one design for wide current
ratings range
High immunity to external
interference.
VREF. IN/OUT
Applications
AC variable speed drives
Static converters for DC motor drives
Battery supplied applications
Uninterruptible Power Supplies
(UPS)
Switched Mode Power Supplies
(SMPS)
Power supplies for welding
applications.
Application domain
Industrial
IPN = 50 .. 400 A
Notes :1) -TP version is equipped with a primary bus bar.
2) It is possible to overdrive VREF with an external reference voltage
between 2 - 2.8 V providing its ability to sink or source approximately
2.5 mA.
3) Excluding offset and hysteresis.
4) Small signal only to avoid excessive heatings of the magnetic core.
070827/7 www.lem.com
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
Page 1/3
Current Transducer HAIS 50..400-P and HAIS 50..100-TP
General data
TAAmbient operating temperature - 40 .. + 85 °C
TSAmbient storage temperature - 40 .. + 85 °C
mMass (in brackets : TP version) 20 (30) g
Standards EN 50178: 1997
Isolation characteristics
VbRated isolation voltage rms 300 V rms
with IEC 61010-1 standards and following conditions
-Single insulation
-Over voltage category III
-Pollution degree 2
-Heterogeneous field
VbRated isolation voltage rms 600 V rms
with EN 50178 standards and following conditions
-Reinforced insulation
-Over voltage category III
-Pollution degree 2
-Heterogeneous field
VdRms voltage for AC isolation test, 50 Hz, 1 min 2.5 kV
VePartial discharge extinction voltage rms @ 10pC
HAIS 50..400-P > 1 kV
HAIS 50..100-TP > 1.4 kV
VwImpulse withstand voltage 1.2/50 µs8 kV
dCp Creepage distance > 8 mm
dCl Clearance distance > 8 mm
CTI Comparative tracking index (Group I) > 600
If insulated cable is used for the primary circuit, the
voltage category could be improved with the following table :
Cable insulation (primary) Category
HAR 03 450V CAT III
HAR 05 550V CAT III
HAR 07 650V CAT III
070827/7 www.lem.com
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
Page 2/3
Safety
This transducer must be used in electric/electronic equipment with respect to
applicable standards and safety requirements in accordance with the following
manufacturer's operating instructions.
Caution! Risk of electrical shock
When operating the transducer, certain parts of the module can carry hazardous
voltage (eg. primary busbar, power supply).
Ignoring this warning can lead to injury and/or cause serious damage.
This transducer is a built-in device, whose conducting parts must be inaccessible
after installation.
A protective housing or additional shield could be used.
Main supply must be able to be disconnected.
8
0.5
16
15
33
29
3
3.5
2-D1.0
6.5
1.5
11
6
14.5 11
33
29
0.5
2-D1.0
10
14.5 11
6.5
1.5
11
14
1.5
1.5
3
3.5
6
25.9
19.9
41
4 1
5
5
6
6
Terminal Pin Identification Recommended connection circuit
1...+5V
HAIS 50..400-PHAIS 50..100-TP
2...0V
3...OUTPUT
4...Vref. (IN/OUT)
5...Core Earth
6...NC.
1
2
3
4
5
+5V
0V
OUTPUT
Vref. (IN/OUT)
47nF
47nF
4.3
3-P1.8
4.3
3-P1.8
4-0.25x0.45
(*)4.7nF
Front view Front view Right view
Bottom view Bottom view
(*) should be connected to 0V of Power Supply for better dv/dt immunity.
Arrow indicates positive current direction.
General tolerance : ±0.2mm
Unit : mm
Recommended PCB hole
Pin 1-4 : 0.7 ±0.1mm
Pin 5-6 : 1.5 ±0.1mm
Primary bus bar : 2.3 ±0.1mm
Ip 0V
Vref.(IN/OUT)
Vout
+Vc
Operation Principle
Required Connection Circuit
Dimensions HAIS 50..400-P and HAIS 50..100-TP (in mm. 1 mm = 0.0394 inch)
070827/7 www.lem.com
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
Page 3/3