Specifications are subject to change without notice 1
Type EID
Current and Voltage Controls
AC/DC under current metering (closed
circuit) relay
Current measuring through internal shunt
3 position rotary switch for selection of measuring range
Measuring ranges: 0.4 mA - 10 A
Adjustable current limit on relative scale
Adjustable time function (0.1-10 s)
Adjustable hysteresis
Output: 5 A SPDT
For mounting on DIN-rail in accordance with
DIN/EN 50 022
22.5 mm Euronorm housing
LED-indication for relay and power supply ON
Galvanically separated power supply
Ordering Key
Housing
Function
Type
Output
Power supply
Measuring range
Input Specifications
Input
Through terminals Y 1 & Y2 current level
Measuring ranges Internal resist. Max. curr.
20 mA type
Rotary 1: 0.4 - 2 mA 50 50 mA
Switch 2: 1 - 5 mA 50 50 mA
Position 3: 4 - 20 mA 50 50 mA
500 mA type
Rotary 1: 10 - 50 mA 3.9 600 mA
Switch 2: 40 - 200 mA 3.9 600 mA
Position 3: 100 - 500 mA 3.9 600 mA
5 A type
Rotary 1: 0.2 - 1 A 0.05 6 A
Switch 2: 0.4 - 2 A 0.05 6 A
Position 3: 1 - 5 A 0.05 6 A
10 A type
Rotary 1: 0.4 - 2 A 0.01 12 A
Switch 2: 1 - 5 A 0.01 12 A
Position 3: 2 - 10 A 0.01 12 A
Max. current for 10 s 40 A
Max. line voltage 277/480 VAC/DC
Output Specifications
Output SPDT relay
Rated insulation voltage 250 VAC, (contact/elect.)
Contact ratings (AgCdO) µ (micro gap)
Resistive loads
AC 1
5 A, 250 VAC
DC 1
5 A, 24 VDC
Small inductive loads
AC 15
2 A, 250 VAC
DC 13
3 A, 24 VDC
Mechanical life 40 x 106operations
Electrical life 105operations
(at max. load)
Operating frequency 7200 operations/h
Dielectric strength
Dielectric voltage 2 kVAC (rms)
Rated impulse withstand volt. 4 kV (1.2/50 µs)
EID is a precise AC/DC under
current metering relay and of-
ten used in applications where
small loads have to be con-
trolled. The built-in LED's in-
dicate the exact status of the
output relay. Through the built-
in shunt it is possible to meas-
ure loads up to 10 A.
Product Description
Type Selection
1-Phase AC/DC Under Current
Mounting Output Measuring range Supply: 24 VAC Supply: 115 VAC Supply: 230 VAC
For DIN-rail SPDT 0.4 - 20 mA EID C 024 20mA EID C 115 20mA EID C 230 20mA
SPDT 10 - 500 mA EID C 024 500mA EID C 115 500mA EID C 230 500mA
SPDT 0.2 - 5 A EID C 024 5A EID C 115 5A EID C 230 5A
SPDT 0.4 - 10 A EID C 024 10A EID C 115 10A EID C 230 10A
EID C 230 20mA
2Specifications are subject to change without notice
Power supply
Overvoltage cat. III (IEC 60664)
Rated operational voltage (IEC 60038)
Through pins A1 & A2 024
24 VAC ±15%, 45 to 65 Hz
115
115 VAC ±15%, 45 to 65 Hz
230
230 VAC ±15%, 45 to 65 Hz
Voltage interruption 40 ms
Dielectric voltage 2 kVAC (rms)
Rated impulse withstand
voltage 4 kV (1.2/50 µs)
Rated operational power 1.5 VA
General Specifications
EID
Power ON delay < 2 s
Power OFF delay > 200 ms
Reaction time τ< 200 ms
worst case reaction time
may be up to 5 x τ
Adjustable delay on release
built-in (0.1-10 s)
Accuracy
Input ±10% (DC/AC @ 50 Hz)
OFF delay 10 s, -1/+3 s on max.
< 0.1 s on min.
Temperature drift 0.2%/°C (0.11%/°F)
Indication for
Power supply ON LED, green
Output ON LED, yellow
Environment
Degree of protection IP 20
Pollution degree 3
Operating temperature - 2 0 ° to + 5 0 ° C ( - 4 ° to +122°F)
Storage temperature
-50° to +85°C (-58° to +185°F)
Weight 140 g
Screw terminals
Tightening torque
Max. 0.5 Nm acc. to IEC 60947
Approvals UL, CSA
EID measures both AC and
DC under current through an
internal shunt.
Example 1
The relay operates when the
measured value exceeds the
set level plus hysteresis.
When the current dr ops below
the set level for more than
the set delay, or when power
supply is interrupted, the relay
releases.
The yellow LED is flashing until
the delay has expired, or until
the measured value exceeds
the set level plus the hystere-
sis.
Mode of Operation Wiring Diagram
Example 1
Relay ON
Operation Diagram
Power supply
Set level Hysteresis
Upper knob:
Setting of current range on
rotary switch.
Centre knob:
Current level setting on rela-
tive scale.
Lower knob:
Setting of OFF delay on abso-
lute scale (0.1-10 s).
Hysteresis
Normally 5%. The hysteresis
can be extended by inserting
a resistor between terminals
Z1 & Z2.
Approx.
10%: 39 k
25%: 12 k
50%: 4.7 k
75%: 2.2 k
100%: 1.5 k
Range/Level/Time Setting
µ
Hysteresis
adjustment
Supply Specifications