Data sheet
Z-series
ZDU 10/3AN BL
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data
Creation date November 30, 2018 11:01:03 PM CET
Catalogue status 26.11.2018 / We reserve the right to make technical changes. 3
Conductors for clamping (rated connection)
Blade size 1.0 x 5.5 mm Clamping range, max. 16 mm²
Clamping range, min.
1.31 mm²
Connection cross-section, stranded,
max. 16 mm²
Connection cross-section, stranded, min. 1.5 mm² Connection direction top
Gauge to IEC 60947-1 A6 Number of connections 3
Stripping length 18 mm Type of connection Tension clamp connection
Wire connection cross section AWG,
max. AWG 6
Wire connection cross section AWG,
min. AWG 16
Wire connection cross section, finely
stranded, max.
10 mm²
Wire connection cross-section, finely
stranded with wire-end ferrules DIN
46228/1, max. 10 mm²
Wire connection cross-section, finely
stranded with wire-end ferrules DIN
46228/1, min. 1.5 mm²
Wire connection cross-section, finely
stranded with wire-end ferrules DIN
46228/4, max. 10 mm²
Wire connection cross-section, finely
stranded with wire-end ferrules DIN
46228/4, min. 1.5 mm²
Wire connection cross-section, finely
stranded, min.
1.5 mm²
Wire connection cross-section, solid
core, max. 16 mm²
Wire connection cross-section, solid
core, min. 1.5 mm²
Rating data
Rated cross-section 10 mm² Rated voltage 800 V
Rated current 57 A Current at maximum wires 57 A
Standards
IEC 60947-7-1
Volume resistance according to IEC
60947-7-x 0.56 mΩ
Rated impulse withstand voltage 8 kV Pollution severity 3
UL rating data
Certificate No. (UR) E60693 Conductor size Factory wiring max. (UR) 6 AWG
Conductor size Factory wiring min. (UR) 16 AWG Conductor size Field wiring max. (UR) 6 AWG
Conductor size Field wiring min. (UR) 16 AWG Current size C (UR) 60 A
Voltage size C (UR) 600 V
Classifications
ETIM 3.0 EC000897 ETIM 4.0 EC000897
ETIM 5.0 EC000897 ETIM 6.0 EC000897
UNSPSC 30-21-18-11 eClass 5.1 27-14-11-20
eClass 6.2 27-14-11-20 eClass 7.1 27-14-11-20
eClass 8.1 27-14-11-20 eClass 9.0 27-14-11-20
eClass 9.1 27-14-11-20
Product information
Descriptive text ordering data 1000 VDC rated voltage tested.
Descriptive text technical data Cross-connection of ZDU 10 and ZDU 16 is possible using the ZQV 16-10. Cross-connection of ZDU 10 and
ZDU 35 is possible using the ZQV 35-10.