EMC Filters for AC Power Line
For Single-phase, Mid-size Box Cased ZAC-00U Series
FEATURES
The ZAC-00U series is a highly compact, large current EMC
filter.
They exhibit outstanding attenuation characteristics with respect
to both differential mode and common mode noise components.
Leakage current is maintained at less than 1mA.
These filters are highly reliable and provide stable attenuation
performance even in harsh environments, where the filters may
be subjected to humidity, vibration, and shock.
It is a product conforming to RoHS directive.
APPLICATIONS
Computers and peripheral terminals, general control devices,
office automation equipment, and other industrial devices.
SAFETY STANDARDS
SHAPES AND DIMENSIONS
Dimensions in mm
Case: metal, terminal: stud
ELECTRICAL CHARACTERISTICS
Conformity to RoHS Directive
Part No.
Standard and standard No.
U.S.A. Canada Europe
UL1283 CSA C22.2 No.8 EN60939
ZAC2205-00U E62388 LR76849C P08209027
ZAC2210-00U E62388 LR76849C P08209027
ZAC2215-00U E62388 LR76849C P08209027
ZAC2220-00U E62388 LR76849C P08209027
UL CSA NEMKO
Part No. ABCDEF øGøHI J K
ZAC2205-00U, 2210-00U, 2215-00U, 2220-00U 50.8 63.5 38 85 74.7 95 M4 4.8 25.4 26.5 9.3
Part No. ZAC2205-00U ZAC2210-00U ZAC2215-00U ZAC2220-00U
Rated voltage Eac(V) 250 250 250 250
Rated current(A) 5 10 15 20
Test voltage Eac(V)[Between terminal and case] 1500 1500 1500 1500
Insulation resistance(M)[DC. 500V, 1min/between terminal and case] 100min. 100min. 100min. 100min.
Leakage current(mA)[250V • 60Hz] 1max. 1max. 1max. 1max.
DC resistance(m) 300max. 40max. 40max. 10max.
Operating temperature range(°C)[Including self-temperature rise] –10 to +85 –10 to +85 –10 to +85 –10 to +85
With derating over(°C) 55 55 55 55
Temperature rise(°C) 30max. 30max. 30max. 30max.
Attenuation frequency range
(MHz)[+5 to +35°C]
Differential mode at 40dB 0.5 to 30 0.7 to 30 1.5 to 30 1.5 to 30
Common mode at 40dB 0.15 to 30 0.5 to 30 1.5 to 30 5 to 30
Weight(g) 250 255 275 285
1
2
4
3
K
J
C
I
A
B
E
D
F
øG
øH
Ground
terminal
Conformity to RoHS Directive: This means that, in conformity with EU Directive 2002/95/EC, lead, cadmium, mercury, hexavalent chromium, and specific
bromine-based flame retardants, PBB and PBDE, have not been used, except for exempted applications.
(2/2)
003-01 / 20080817 / e9141_zac_00u.fm
• All specifications are subject to change without notice.
TYPICAL ELECTRICAL CHARACTERISTICS
ATTENUATION vs. FREQUENCY CHARACTERISTICS
ZAC2205-00U ZAC2210-00U
ZAC2215-00U ZAC2220-00U
CIRCUIT DIAGRAM
100
80
60
40
20
00.1 0.3 1 3 10 30 100
Common mode
Differential mode
Frequency(MHz)
Attenuation(dB)
100
80
60
40
20
00.1 0.3 1 3 10 30 100
Common mode
Differential mode
Frequency(MHz)
Attenuation(dB)
100
80
60
40
20
00.1 0.3 1 3 10 30 100
Common mode
Differential mode
Frequency(MHz)
Attenuation(dB)
100
80
60
40
20
00.1 0.3 1 3 10 30 100
Common mode
Differential mode
Frequency(MHz)
Attenuation(dB)
1
2
4
3
R
R
R: Bleeder resistor Case GND