(1/2)
003-01 / 20080817 / e9141_zac_00u.fm
• All specifications are subject to change without notice.
EMC Filters for AC Power Line
For Single-phase, Mid-size Box Cased ZAC-00U Series
FEATURES
• The ZAC-00U series is a highly compact, large current EMC
filter.
• They exhibit outstanding attenuation characteristics with respect
to both differential mode and common mode noise components.
• Leakage current is maintained at less than 1mA.
• These filters are highly reliable and provide stable attenuation
performance even in harsh environments, where the filters may
be subjected to humidity, vibration, and shock.
• It is a product conforming to RoHS directive.
APPLICATIONS
Computers and peripheral terminals, general control devices,
office automation equipment, and other industrial devices.
SAFETY STANDARDS
SHAPES AND DIMENSIONS
Dimensions in mm
• Case: metal, terminal: stud
ELECTRICAL CHARACTERISTICS
Conformity to RoHS Directive
Part No.
Standard and standard No.
U.S.A. Canada Europe
UL1283 CSA C22.2 No.8 EN60939
ZAC2205-00U E62388 LR76849C P08209027
ZAC2210-00U E62388 LR76849C P08209027
ZAC2215-00U E62388 LR76849C P08209027
ZAC2220-00U E62388 LR76849C P08209027
UL CSA NEMKO
Part No. ABCDEF øGøHI J K
ZAC2205-00U, 2210-00U, 2215-00U, 2220-00U 50.8 63.5 38 85 74.7 95 M4 4.8 25.4 26.5 9.3
Part No. ZAC2205-00U ZAC2210-00U ZAC2215-00U ZAC2220-00U
Rated voltage Eac(V) 250 250 250 250
Rated current(A) 5 10 15 20
Test voltage Eac(V)[Between terminal and case] 1500 1500 1500 1500
Insulation resistance(MΩ)[DC. 500V, 1min/between terminal and case] 100min. 100min. 100min. 100min.
Leakage current(mA)[250V • 60Hz] 1max. 1max. 1max. 1max.
DC resistance(mΩ) 300max. 40max. 40max. 10max.
Operating temperature range(°C)[Including self-temperature rise] –10 to +85 –10 to +85 –10 to +85 –10 to +85
With derating over(°C) 55 55 55 55
Temperature rise(°C) 30max. 30max. 30max. 30max.
Attenuation frequency range
(MHz)[+5 to +35°C]
Differential mode at 40dB 0.5 to 30 0.7 to 30 1.5 to 30 1.5 to 30
Common mode at 40dB 0.15 to 30 0.5 to 30 1.5 to 30 5 to 30
Weight(g) 250 255 275 285
1
2
4
3
K
J
C
I
A
B
E
D
F
øG
øH
Ground
terminal
• Conformity to RoHS Directive: This means that, in conformity with EU Directive 2002/95/EC, lead, cadmium, mercury, hexavalent chromium, and specific
bromine-based flame retardants, PBB and PBDE, have not been used, except for exempted applications.