Surge Arrester 2-Electrode-Arrester A70-A230X Ordering code: B88069X2120C102 DC spark-over voltage 1) 220 ... 300 V Impulse spark-over voltage at 5 kV/s < 1000 V Insulation resistance at 100 Vdc > 10 G Capacitance at 1 MHz < 1.5 pF Service life according to TKZ-TS 0065/00, 04/99 (Austria) 300 operations 10/1000 s 10 operations 8/20 s 3 operations 8/20 s 10 operations 50 Hz, 1 s 100 5 15 20 A kA kA A Arc voltage at 1 A Glow to arc transition current Glow voltage ~ 15 < 0.5 ~ 60 V A V Weight ~ 1.5 g Operation and storage temperature -40 ... +90 C Climatic category (IEC 60068-1) 40/ 90/ 21 Marking, green 230 YY O 230 YY O - Nominal voltage - Year of production - Non radioactive 1) At delivery AQL 0.65 level II, DIN ISO 2859 Terms in accordance with ITU-T Rec. K.12 and DIN 57845/VDE0845 AB E / AB PM Issue 02, 04.04.2002 Page 1 of 2 Surge Arrester 2-Electrode-Arrester A70-A230X Ordering code: B88069X2120C102 Not to scale Dimensions in mm Non controlled document EPCOS AG 2002. Reproduction, publication and dissemination of this data sheet, enclosures hereto and the information contained therein without EPCOS' prior express consent is prohibited. Purchase orders are subject to the General Conditions for the Supply of Products and Services of the Electrical and Electronics Industry recommended by the ZVEI (German Electrical and Electronic Manufacturers' Association), unless otherwise agreed. AB E / AB PM Issue 02, 04.04.2002 Page 2 of 2