https://www.phoenixcontact.com/us/products/2810625
04/15/2021Page1/6
Current transducers-MACX MCR-SL-CAC- 5-I-UP-2810625
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Current measuring transducer for 1 A and 5 A AC, the output signal 0...20 mA or 4...20 mA, can be configured
using a DIP switch with an operating mode indication through an LED
Product Description
The MACX MCR-SL-CAC-5-I(-UP) current measuring transducers convert sinusoidal alternating currents of 1 A or 5 A into standard analog signals
0...20 mA or 4...20 mA. The DIP switches, which can be accessed on the upper side of the housing, can be used to configure the input and output
current.
The MACX MCR-SL-CAC-5-I current transducer contains a supply voltage range of 19.2 V DC to 30 V DC.
The MACX MCR-SL-CAC-5-I current transducer contains a long range version with a supply voltage range of 19.2 V AC/DC to 253 V AC/DC.
Your advantages
Input/output can be configured via DIP switches
Key Commercial Data
Packing unit 1 pc
GTIN
GTIN 4046356153782
Weight per Piece (excluding packing) 183.100 g
Custom tariff number 85437090
Country of origin Germany
Technical data
Note
Utilization restriction EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width 22.5 mm
https://www.phoenixcontact.com/us/products/2810625
04/15/2021Page2/6
Current transducers-MACX MCR-SL-CAC- 5-I-UP-2810625
Technical data
Dimensions
Height 104 mm
Depth 114.5 mm
Ambient conditions
Ambient temperature (operation) -20 °C ... 65 °C (-4°F...149°F)
Ambient temperature (storage/transport) -40 °C ... 85 °C (-40°F...185°F)
Maximum altitude 2000 m
Permissible humidity (operation) 10 % ... 95 % (non-condensing)
Degree of protection IP20
Noise immunity EN 61000-6-2 When being exposed to interference, there may be minimal
deviations.
Input data
Configurable/programmable Via DIP switches
Input current range 0 A ... 5 A
Setting range for min. input current 0 A AC ... 1 A (configurable)
Setting range for max. input current 0 A AC ... 5 A (configurable)
Overload capacity 2 x IN (continuous)
Surge strength 20 x IN (1 s)
Nominal frequency fN50 Hz
Frequency measuring range 45 Hz ... 65 Hz
Connection method Screw terminal block
Output data
Output name Current output
Configurable/programmable Via DIP switches
Current output signal 0 mA ... 20 mA (configurable)
4 mA ... 20 mA (configurable)
Max. output current 25 mA
Load/output load current output < 500 Ω (20mA)
Ripple < 10 mVPP (for 500 Ω at 20 mA)
Status display LED red (error), LED green (ready)
Switching output
Output name No switching output
Power supply
Supply voltage range 19.2 V AC/DC ... 253 V AC/DC
Max. current consumption < 30 mA (at UB=24 V DC, IOUT=20 mA)
< 13 mA (at UB= 230 V AC, IOUT=20 mA)
https://www.phoenixcontact.com/us/products/2810625
04/15/2021Page3/6
Current transducers-MACX MCR-SL-CAC- 5-I-UP-2810625
Technical data
Power supply
Power consumption < 0.9 W (at UB=24 V DC, IOUT=20 mA)
< 3.4 W (at UB= 230 V AC, IOUT=20 mA)
Connection data
Connection method Screw connection
Stripping length 8 mm
Screw thread M3
Conductor cross section solid 0.2 mm² ... 2.5 mm²
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section AWG 24 ... 14
General
Maximum transmission error ≤ 0.5 % (of nominal range value under nominal conditions)
Maximum temperature coefficient < 0.02 %/K
Temperature coefficient, typical < 0.015 %/K
Step response (10-90%) ≤ 300 ms
typ. 200 ms
Overvoltage category III
Degree of pollution 2
Test voltage input/output 4 kV (50Hz, 1min.)
Test voltage output/power supply 2 kV (50Hz, 1min.)
Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-4
Noise immunity EN 61000-6-2 When being exposed to interference, there may be minimal
deviations.
Color gray
Housing material Polyamide PA non-reinforced
Mounting position any
Standards and Regulations
Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-4
Connection in acc. with standard CUL
Standards/regulations EN 61000-4-2
EN61000-4-3
EN61000-4-4
Comments Criterion B
Standards/regulations EN61000-4-5
EN61000-4-6
https://www.phoenixcontact.com/us/products/2810625
04/15/2021Page4/6
Current transducers-MACX MCR-SL-CAC- 5-I-UP-2810625
Technical data
Conformance/approvals
Designation CE
Designation ATEX
Identification  II 3 G Ex nA IIC T4 Gc X
Designation UL, USA/Canada
Identification UL508 Recognized
Environmental Product Compliance
REACh SVHC N,N-dimethylacetamide 127-19-5
Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50 years
For details about hazardous substances go to tab “Downloads”, Category
“Manufacturer's declaration”
Drawings
Application drawing
24V
5A
1000A
0...20mA
Mainsvoltage
Current measurement
Dimensional drawing
104 22,5 7
114,5
Classifications
eCl@ss
eCl@ss 10.0.1 27210123
eCl@ss 11.0 27210123
eCl@ss 4.0 27271100
eCl@ss 4.1 27200300
eCl@ss 5.0 27200300
eCl@ss 5.1 27200300
eCl@ss 6.0 27210100
https://www.phoenixcontact.com/us/products/2810625
04/15/2021Page5/6
Current transducers-MACX MCR-SL-CAC- 5-I-UP-2810625
Classifications
eCl@ss
eCl@ss 7.0 27210123
eCl@ss 9.0 27210123
ETIM
ETIM 3.0 EC002475
ETIM 4.0 EC002475
ETIM 6.0 EC002475
ETIM 7.0 EC002475
UNSPSC
UNSPSC 6.01 30211506
UNSPSC 7.0901 39121008
UNSPSC 11 39121008
UNSPSC 12.01 39121008
UNSPSC 13.2 39121032
UNSPSC 18.0 39121032
UNSPSC 19.0 39121032
UNSPSC 20.0 39121032
UNSPSC 21.0 39121032
Approvals
Approvals
Approvals
UL Recognized / cUL Recognized / cULus Recognized
Ex Approvals
ATEX / EAC Ex / ATEX
Approval details
UL Recognized http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 238705
https://www.phoenixcontact.com/us/products/2810625
04/15/2021Page6/6
Current transducers-MACX MCR-SL-CAC- 5-I-UP-2810625
Approvals
cUL Recognized http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 238705
cULus Recognized
Accessories
Accessories
DIN rail connector
DIN rail bus connectors-ME 22,5 TBUS 1,5/ 5-ST-3,81 GY-2201937
DIN rail connector, color: gray, nominal current: 8 A (parallel contacts), rated voltage (III/2): 125 V, Number of positions
per row: 5, pitch: 3.81 mm, mounting: DIN rail mounting, Locking: without, Assembly: without, type of packaging: packed
in cardboard, Item with gold-plated contacts, bus connectors for connecting with electronics housings, 5 parallel contacts
Phoenix Contact 2021 © - all rights reserved
http://www.phoenixcontact.com