Product datasheet
Characteristics
GV7RS80
TeSys GV7 - circuit breaker - 3P - AC-3 - 48...80
A - thermal-magnetic
Price* : 468.08 GBP
Main
Range TeSys
Product name TeSys GV7
Device short name GV7R
Device application Motor
Poles description 3P
Network type AC
Utilisation category AC-3 conforming to IEC 60947-4-1
Network frequency 50/60 Hz conforming to IEC 60947-4-1
Breaking capacity 50kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
65kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
100kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
70kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
10kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit
breaking capacity
100% at 440 V AC 50/60 Hz conforming to IEC 60947-2
100% at 500 V AC 50/60 Hz conforming to IEC 60947-2
100% at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
100% at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
100% at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Thermal protection adjustment range 48…80A
Trip unit technology Thermal-magnetic
Complementary
Mounting mode By screws
By clips
Mounting support Kit for fixing the switchgear
Rail
Flush
Panel mounting
Mounting position Vertical
Motor power kW 37kW at 400...415 V AC 50/60 Hz
45kW at 500 V AC 50/60 Hz
55kW at 500 V AC 50/60 Hz
55kW at 660...690 V AC 50/60 Hz
Control type Rocker lever
[Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Jul 13, 2019
1
[Ui] rated insulation voltage 750V AC 50/60 Hz conforming to IEC 60947-2
[Ith] conventional free air thermal
current
80A conforming to IEC 60947-4-1
[Uimp] rated impulse withstand voltage 8kV conforming to IEC 60947-2
Power dissipation per pole 5 W
Power dissipation per pole 5W
Mechanical durability 50000cycles
Electrical durability 30000cycles for AC-3 at 440 V In
50000cycles for AC-3 at 440 V In/2
Maximum operating rate 25cyc/h
Rated duty Continuous conforming to IEC 60947-4-1
Connection pitch 35mm without spreaders
45mm with spreaders
Connections - terminals Bars
Cable with lug - external diameter: 10mm
Screw
Bare cable connectors 1.5…95mm²
Tightening torque 10N.m on screw M6 screw type
15N.m on bare cable connectors for cable 1.5…95mm²
Mechanical robustness Shocks: 15 Gn for 11 ms conforming to IEC 60068-2-27
Vibrations: 2.5 Gn, 0...25 Hz conforming to IEC 60068-2-6
Suitability for isolation Yes conforming to IEC 60947-1
Phase failure sensitivity Yes conforming to IEC 60947-4-1 § 7-2-1-5-2
Height 125mm
Width 105mm
Depth 111mm
Net weight 2.04kg
Environment
Standards EN/IEC 60947-1
EN/IEC 60947-4-1
EN/IEC 60947-2
NF C 79-130
NF C 63-120
VDE 0660
VDE 0113
NF C 63-650
Product certifications UL
DNV
Protective treatment TC
IP degree of protection IP405 conforming to IEC 60529 (with terminal shrouds)
Pollution degree 3
Ambient air temperature for operation -25…70°C
Ambient air temperature for storage -55…95°C
Fire resistance 960°C conforming to IEC 60695-2-1
Operating altitude 2000 m
Offer Sustainability
EU RoHS Directive Not applicable, out of EU RoHS legal scope
Environmental Disclosure Product Environmental Profile
Contractual warranty
Warranty 18 months
2
Product datasheet
Dimensions Drawings
GV7RS80
GV7R
Dimensions
(1) 126 for GV7R220.
Minimum Electrical Clearance
x1 x2
Painted or insulated metal plate, insulation or insulated bar 0 30
U ≤ 440V 5 35
440V < U < 600V 10 35
Bare metal plate
U ≥600V 20 35
GV7R
Panel Mounting
Mounting on 2 Mounting Rails DZ5 MB201
Flush-Mounting
3
1 circuit breaker GV7R
n circuit breakers GV7R side by side
Connection
Smooth terminals
a
GV7R40…R150 19.5
GV7R220 21.5
Connectors
4
Product datasheet
Connections and Schema
GV7RS80
Motor Circuit Breakers
GV7 R
5